6.0CUSTOMER CONFIGURATION AND CALIBRATION

Use this procedure to determine the configuration of the TX82B customized setup. The procedure is general; customers can specify any two current inputs and their corresponding digital readings. Pin-groups are shown in Figure 5-1.

6.1FORMULA

Base all your calculations on either the 1-5, 4-20 or 10-50 mA range.

1. Determine the lowest input current, I1, which is specified by the customer:

I1 =

 

mA

2.Determine the highest input current, I2, which is specified by the customer:

I2 =

 

mA

3.Determine the reading, N1, at input current I1, which is specified by the customer.

N1 =

 

counts

4.Determine the reading, N2, at input current I2, which is specified by the customer:

 

N2 =

 

counts

5. Calculate the Gain, G1:

 

 

 

(N2 - N1)

 

 

G1 =

 

=

 

 

counts per mA

(I2 - I1)

 

 

(If G1 is greater than 125, it is out of range for a standard unit.)

6.Calculate the Required Zero Range number, RZR: RZR = N1 - (I1 x G1) =

7.Select the Zero Range required from the following chart where the Required Zero Range number falls between the upper and lower limits of that range:

ZR1 = -2510 to -1420

ZR2 = -1580 to -420

ZR3 = -470 to +850

ZR4 = +760 to +2000

ZR =

9

Image 13
Contents TX82B USA Servicing North AmericaTable of Contents QTY Description Unpacking InstructionsGeneral Information Input SpecificationsAccuracy AT 25C ConversionEnvironment DisplayMechanical Safety Considerations Mechanical Assembly and InstallationExploded View includes rear panel INSTALLATION/REMOVALSignal Input Connections P3 Standard Setup ConfigurationField Configuration Chart Configuration Jumper InstallationSpan ADJ Zero ADJ VR2 Formula Customer Configuration and CalibrationFACTORY-SETUP Label Configuration ProceduresCalibration Wiring Diagram for TX82B Usage for FM Factory Mutual Wiring DiagramPage Page Page WARRANTY/DISCLAIMER Temperature