Outdoor Unit Installation
Outdoor installation precaution
•Install the outdoor unit on a rigid base to prevent increasing noise level and vibration.
•Determine the air outlet direction where the discharged air is not blocked. If the installation place is exposed to strong winds, ensure the unit is lengthwise along the wall or provide a suitable air baffle.
•If suspending the unit, follow the bracket manu- facturer’s instructions.
•Use a raised concrete pad or concrete blocks to provide a solid, level surface. Securely anchor the unit down with bolts.
•Be sure there are no obstacles which block radiat- ing air.
•In a snowy area, install the outdoor unit on a raised platform that is higher than drifting snow.
Anchoring outdoor unit
Anchor the outdoor unit with 5/16" (8mm) or 3/8" |
|
| |
(10mm) bolt and nut tightly and horizontally on a |
| Fig. 45 | |
concrete or rigid mount. |
|
| |
|
|
|
|
Outdoor unit dimensions | Mounting Dimensions |
| |
WxHxD in. (mm) | A in. (mm) | B in. (mm) |
|
29.9 x 23.2 x 11.2 (760 x 590 x 285) | 20.9 (530) | 11.4 (290) |
|
|
|
|
|
33.3 x 27.4 x 13.2 (845 x 695 x 335) | 22 (560) | 13.2 (335) |
|
|
|
|
|
35.2 x 33.9 x 13.0 (895 x 860 x 330) | 23.2 (590) | 13.1 (333) |
|
|
|
|
|
39.0 x 38.0 x 14.0 (990 x 965 x 355) | 24.5 (623) | 14.4 (366) |
|
|
|
|
|