Heat Controller, Inc. | INSTALLATION MANUAL | VMH InverterFlex |
|
|
|
Indoor unit installation (wall-mounted type)
1.Installation Plate
A.Mount the installation plate horizontally on struc- tural parts (studs) of the wall with proper clear- ance around the installation plate.
B.If the wall is made of brick, concrete or the like, drill eight (8) 5mm (0.2in.) diameter holes in the wall.Insert anchor for appropriate mounting screws.
C.Fit the installation plate on the wall with eight (8) type “A” screws.
NOTE:
Fit the Installation Plate and drill holes in the wall ac- cording to the wall structure and corresponding mount- ing points on the installation plate. The Installation Plate may be slightly different according to the different models of indoor unit.
Model | A in. (mm) | B in. (mm) |
| 28 (710) | 10 (250) |
<12,000 Btu/h | 30 (750) | 10 (250) |
| 31 (780) | 11 (270) |
| 32 (790) | 10 (265) |
≥12,000 Btu/h | 31 (780) | 11 (270) |
| 32 (815) | 11 (280) |
2.Drill a hole in the wall
A.Determine hole positions according to the dia- gram detailed in Fig.5. Drill one (1) hole ( 3in. (65mm)) slanting slightly toward the outdoors, as shown in Fig. 6.
B.Always use wall hole conduit when drilling metal grid, metal plate or the like.
3.Connective Pipe and Drainage Installation
A.Run the drain hose sloping downward. Do not install the drain hose as illustrated in Fig.7.
6