Heat Controller VMH 36, VMH 27 Refrigerant Pipe Connection, Tightening Connection, Flaring work

Page 12

VMH InverterFlex Mini-Split

INSTALLATION MANUAL

Heat Controller, Inc.

Refrigerant Pipe Connection

D: Flaring work

Firmly hold copper pipe in a die in the dimension shown in the table below.

Outer diameter

A in. (mm)

in. (mm)

 

 

Max.

Min.

o 1/4" (6.35)

0.5 (1.3)

0.276 (0.7)

o 3/8" (9.35)

0.63 (1.6)

0.394 (1.0)

 

 

 

o 1/2" (12.7)

0.709 (1.8)

0.394 (1.0)

Tightening Connection

Align the center of the pipes.

Sufficiently tighten the flare nut with fingers, and then tighten it with a spanner and torque wrench as shown in Fig.51 & 52.

Outer

Tightening

Additional tightening

Diameter

torque

torque

o 1/4" (6.35)

11.57 ft-lb

14.46 ft-lb

(160 kgf-cm)

(200 kgf-cm)

 

o 3/8" (9.35)

21.69 ft-lb

25.3 ft-lb

(300 kgf-cm)

(350 kgf-cm)

 

o 1/2" (12.7)

36.17 ft-lb

39.78 ft-lb

(500 kgf-cm)

(550 kgf-cm)

 

Caution

Excessive torque can break nut depending on installation conditions.

11

Image 12
Contents Installation Manual Table of Contents This symbol denotes item that is Prohibited from doing Selecting installation place Rooftop installationWall-mounted type Indoor unitAccessories Single-Dual Zone Single-Tri Zone Single-Quad Zone Indoor unit installation wall-mounted type Installation PlateConnective Pipe and Drainage Installation Drill a hole in the wallIndoor unit Indoor unit installation Outdoor Unit Installation Outdoor installation precautionAnchoring outdoor unit Refrigerant Pipe Connection Refrigerant Pipe Connection Tightening ConnectionFlaring work Electrical Work Connect the cable to the outdoor unit Air Purging Air purging with vacuum pumpWhen Using the Vacuum Pump Leak Check Safety and leakage check Electrical safety check Testing the System Wellorks. well09/2010