Connecting Refrigerant Tubing Between

the Indoor & Outdoor Unit

CAUTION:

When servicing, cover or seal openings to minimize the exposure of the refrigerant system to air to prevent accumulation of moisture and other contaminants.

After outdoor and indoor unit placement has been determined, route refrigerant tubing between the equipment in accordance with sound installation practices.

When connecting refrigerant linesets together, it is recommended that dry nitrogen be flowing through the joints during brazing.This will prevent internal oxidation and scaling from occurring.

Refrigerant tubing should be routed in a manner that minimizes the length of tubing and the number of bends in the tubing.

Refrigerant tubing should be supported in a manner that the tubing will not vibrate or abrade during system operation.

Tubing should be kept clean of foreign debris during installation.

Every effort should be made by the installer to ensure that the field installed refrigerant containing components of the system have been installed in accordance with these instructions and sound installation practices to insure reliable system operation and longevity.

The maximum recommended interconnecting refrigerant line length is 75 feet, and the vertical elevation difference between the indoor and outdoor sections should not exceed 20 feet.

If precise forming of refrigerant lines is required, a copper tubing bender is recommended. Avoid sharp bends and contact of the refrigerant lines with metal surfaces.

A filter dryer is provided with the unit and must be installed in the liquid line of the system.If the installation replaces a system with a filter dryer already present in the liquid line, the filter dryer must be replaced with the one supplied with the unit. The filter dryer must be installed in strict accordance with the manufacturer’s installation instructions.

Optional equipment such as liquid line solenoid valves, low ambient, etc., should be installed in strict accordance with the manufacturer’s installation instructions.

ELECTRICAL WIRING

WARNING:

To avoid risk of electrical shock, personal injury, or death, disconnect all electrical power to the unit before performing any maintenance or service. The unit may have more than one electrical supply.

Label all wires prior to disconnection when servicing the unit. Wiring errors can cause improper and dangerous operation

All electrical connections must be in compliance with all applicable local codes and ordinances, and with the current revision of the National Electric Code (ANSI/ NFPA 70).

For Canadian installations the electrical connections and grounding shall comply with the current Canadian Electrical Code (CSA C22.1 and/or local codes).

Pre-Electrical Checklist

Verify that the voltage, frequency, and phase of the supply source match the specifications on the unit rating plate.

Verify that the service provided by the utility is sufficient to handle the additional load imposed by this equipment. Refer to the unit wiring label for proper high and low voltage wiring.

Verify factory wiring is in accordance with the units wiring diagram (Figures 8-10, pages 12-14). Inspect for loose connections.

Line Voltage

A wiring diagram is located on the inside cover of the electrical box of the outdoor unit. The installer should become familiar with the wiring diagram before making any electrical connections to the outdoor unit.

An electrical disconnect must be located within sight of and readily accessible to the unit. This switch shall be capable of electrically de-energizing the outdoor unit.

Line voltage to the unit should be supplied from a dedicated branch circuit containing the correct fuse or circuit breaker for the unit. Incoming field wiring and minimum size of electrical conductors and circuit protection must be in compliance with information listed on the outdoor unit data label.Any other wiring methods must be acceptable to authority having jurisdiction.

The outdoor unit requires both power and control circuit electrical connections. Refer to the wiring diagrams for identification and location of outdoor unit field wiring interfaces.Make all electrical connections in accordance with all applicable codes and ordinances.

Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit rating label and according to applicable local codes. See the unit rating plate for minimum circuit ampacity and maximum overcurrent protection limits.

Provide power supply for the unit in accordance with the unit wiring diagram, and the unit rating plate. Connect

4

Image 4
Contents Outdoor Split System Heat Pump TWO-STAGE, R-410A ModelsImportant Safety Information Electrical SHOCK, Fire or Explosion HazardHeat Pump Installation General Information Before You Install the Heat PumpLocating the Heat Pump Packaging RemovalConnecting Refrigerant Tubing Between Indoor & Outdoor Unit Electrical WiringPre-Electrical Checklist Line VoltageThermostat / Low Voltage Connections GroundingOutdoor Fan Motor Heat Pump Maintenance Start UP & Adjustments Pre-Start Check ListStart-Up Procedures Optional EquipmentShort Cycle Protection Defrost Test ProcedureDefrost Cycle Control Anti Short Cycle Timer Test Adjustment of Refrigerant ChargeApplication Notes for using the Charging Charts Cooling Charging Charts500 Psig Wiring Diagram ¢711016q¤ ¢711017w¤ 711017A Page Installation / Performance Check List Replacement Parts
Related manuals
Manual 24 pages 62.98 Kb

R-410A specifications

The Heat Controller R-410A is an advanced refrigerant used in various heating and cooling applications, particularly in residential and commercial air conditioning systems. Recognized for its efficiency and eco-friendliness, R-410A has become a popular choice among HVAC manufacturers and professionals.

One of the main features of R-410A is its high efficiency. It operates at a higher pressure than traditional refrigerants, which allows it to transfer heat more effectively. This results in improved energy efficiency ratings (SEER and EER) for systems utilizing R-410A, leading to lower energy bills and reduced environmental impact.

R-410A is also known for its environmental sustainability. Unlike its predecessor, R-22, R-410A has zero ozone depletion potential (ODP) due to its composition of hydrofluorocarbons (HFCs). Although it does have a global warming potential (GWP), the advancements in technology have made R-410A a more environmentally friendly option compared to many older refrigerants.

Developed through innovative technological advancements, R-410A systems often incorporate variable speed compressors and efficient heat exchangers. These technologies allow for better modulation of cooling and heating outputs, ensuring that the indoor environment remains comfortable while using the least amount of energy possible.

Another significant characteristic of R-410A is its compatibility with a wide range of HVAC equipment. Many new air conditioning systems are designed specifically to use R-410A, which has led to the creation of a robust market for these units. Additionally, R-410A systems tend to require less maintenance and have longer lifespans compared to those using older refrigerants.

Safety is another consideration for R-410A users. While R-410A is non-toxic and non-flammable, technicians who work with this refrigerant need to be trained and certified due to its high-pressure properties. Proper handling and installation are crucial to ensure system efficiency and reliability.

In summary, the Heat Controller R-410A stands out in the HVAC industry for its efficiency, environmental benefits, advanced technologies, and compatibility with modern systems. As the industry continues to evolve, R-410A remains a key player, paving the way towards more sustainable and efficient heating and cooling solutions.