Intellivox DDC Installation Manual Appendix | EN 18 |
|
|
Network configuration.
A network is composed of one master device and one or more slave devices. A master device can exist of a PC running the
Because all slave devices share the same bus, the outputs (YZ) of these units are only enabled during transmission of data from the unit to the master. The implemented network protocol sets the output of all other units in a high impedance state during this period to prevent conflicts. For this reason each device has its own network address.
The official
The
Cable length
The maximum cable length is heavily depending on the cable characteristics and the baud rate. The
Cable termination
According to the official
In practice, termination resistors will only be needed in combination with large cable lengths and large stub lengths.
Cable type
The required cable type for implementation of the network is twin twisted cable of which both twisted pairs are individually shielded.
An example of a preferred extended range cable type is:
Type: BELDEN ‘Datalene’ series nr. 9729
Characteristic impedance : | 100 Ohms |
Core to core capacity : | 41 pF/m |
Core to shield capacity : | 72.5 pF/m |
DC resistance core : | 78.7 Ohms/km. |
DC resistance shield : | 59.1 Ohms/km. |
This cable has a foil shielding with drain wire and a tinned litze core.
Fig 15 Connection of twin twisted network cable to the unit
Alternative cable types are
:Belden 1902A or equivalent.
:BICC