BLOWER PERFORMANCE DATA - SINGLE PHASE

 

 

 

 

*PG1336045M41A* - Rise Range: 30 -60°

 

 

 

 

Unit

 

LOW

 

 

MEDIUM

 

 

HIGH

 

Static

CFM

WATTS

AMPS

RISE

CFM

WATTS

AMPS

RISE

CFM

WATTS

AMPS

RISE

0.1

1,029

346

1.51

34

1,337

471

2.08

NR

1,462

596

2.64

NR

0.2

982

334

1.46

35

1,265

452

2.01

NR

1,398

563

2.58

NR

0.3

946

329

1.40

36

1,227

448

1.97

NR

1,326

550

2.50

NR

0.4

888

313

1.38

39

1,159

429

1.87

30

1,260

534

2.42

NR

0.5

823

304

1.29

42

1,073

405

1.73

32

1,188

513

2.34

NR

0.6

750

287

1.23

46

1,008

393

1.71

34

1,090

496

2.22

32

0.7

668

271

1.16

52

895

371

1.61

39

997

478

2.18

35

0.8

454

238

1.00

NR

760

346

1.49

45

852

454

2.12

40

 

 

 

 

*PG1336070M41A* - Rise Range: 35° -65°

 

 

 

 

 

Unit

 

LOW

 

 

 

MEDIUM

 

 

 

HIGH

 

 

Static

CFM

WATTS

AMPS

RISE

CFM

WATTS

AMPS

RISE

 

CFM

WATTS

AMPS

RISE

 

0.1

1,029

346

1.51

50

 

1,337

471

2.08

39

 

1,462

596

2.64

35

 

0.2

982

334

1.46

53

 

1,265

452

2.01

41

 

1,398

563

2.58

37

 

0.3

946

329

1.40

55

 

1,227

448

1.97

42

 

1,326

550

2.50

39

 

0.4

888

313

1.38

58

 

1,159

429

1.87

45

 

1,260

534

2.42

41

 

0.5

823

304

1.29

63

 

1,073

405

1.73

48

 

1,188

513

2.34

44

 

0.6

750

287

1.23

NR

 

1,008

393

1.71

51

 

1,090

496

2.22

47

 

0.7

668

271

1.16

NR

 

REMOVED AA & USED A*

997

478

2.18

52

 

 

895

371

1.61

58

 

 

0.8

454

238

1.00

NR

 

760

346

1.49

68

 

852

454

2.12

61

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*PG1336090M41A* - Rise Range: 45° -75°

 

 

 

 

 

Unit

 

LOW

 

 

 

MEDIUM

 

 

 

HIGH

 

 

Static

CFM

WATTS

AMPS

RISE

CFM

WATTS

AMPS

RISE

 

CFM

WATTS

AMPS

RISE

 

0.1

1,029

346

1.51

50

 

1,337

471

2.08

NR

 

1,462

596

2.64

NR

 

0.2

982

334

1.46

53

 

1,265

452

2.01

NR

 

1,398

563

2.58

NR

 

0.3

946

329

1.40

55

 

1,227

448

1.97

NR

 

1,326

550

2.50

NR

 

0.4

888

313

1.38

58

 

1,159

429

1.87

45

 

1,260

534

2.42

NR

 

0.5

823

304

1.29

63

 

1,073

405

1.73

48

 

1,188

513

2.34

NR

 

0.6

750

287

1.23

69

 

1,008

393

1.71

51

 

1,090

496

2.22

47

 

0.7

668

271

1.16

NR

 

895

371

1.61

58

 

997

478

2.18

52

 

0.8

454

238

1.00

NR

 

760

346

1.49

68

 

852

454

2.12

61

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*PG1342070M41A* - Rise Range: 35° - 65°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit

 

LOW

 

 

 

MEDIUM

 

 

 

HIGH

 

 

Static

CFM

WATTS

AMPS

RISE

 

CFM

WATTS

AMPS

RISE

 

CFM

WATTS

AMPS

RISE

 

0.1

1,100

340

1.55

46

 

1,450

480

2.15

35

 

1,575

585

2.64

NR

 

0.2

1,040

325

1.49

49

 

1,390

460

2.06

37

 

1,515

565

2.58

NR

 

0.3

1,000

320

1.44

51

 

1,300

445

1.98

39

 

1,430

550

2.50

36

 

0.4

925

305

1.38

55

 

1,215

425

1.89

42

 

1,340

525

2.42

38

 

0.5

860

290

1.32

59

 

1,115

395

1.79

46

 

1,240

505

2.34

41

 

0.6

800

275

1.22

64

 

1,030

375

1.71

50

 

1,130

465

2.22

45

 

0.7

690

255

1.16

NR

 

945

350

1.60

54

 

1,010

450

2.18

51

 

0.8

--------

--------

--------

NR

 

860

335

1.54

59

 

910

430

2.12

56

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*PG1342090M41A* - Rise Range: 45° - 75°

 

 

 

 

 

Unit

 

LOW

 

 

 

MEDIUM

 

 

 

HIGH

 

 

Static

CFM

WATTS

AMPS

RISE

 

CFM

WATTS

AMPS

RISE

 

CFM

WATTS

AMPS

RISE

 

0.1

1,100

340

1.55

62

 

1,450

480

2.15

47

 

1,575

585

2.64

NR

 

0.2

1,040

325

1.49

66

 

1,390

460

2.06

49

 

1,515

565

2.58

45

 

0.3

1,000

320

1.44

68

 

1,300

445

1.98

52

 

1,430

550

2.50

48

 

0.4

925

305

1.38

74

 

1,215

425

1.89

56

 

1,340

525

2.42

51

 

0.5

860

290

1.32

NR

 

1,115

395

1.79

61

 

1,240

505

2.34

55

 

0.6

800

275

1.22

NR

 

1,030

375

1.71

66

 

1,130

465

2.22

60

 

0.7

690

255

1.16

NR

 

945

350

1.60

72

 

1,010

450

2.18

67

 

0.8

--------

--------

--------

NR

 

860

335

1.54

NR

 

910

430

2.12

75

 

NR = Heating Temperature Rise Not Recommended.

NOTE: The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation, external static pressure should not exceed 0.5" w.c.

20

Image 20
Contents GPG13 M Series W/R410A Ansi Z21.47CSA-2.3 Central FurnacesReplacement Parts Safety InstructionsPropane Gas Installations Electrical WiringReplacement Parts Safety InstructionsUnit Location Carbon Monoxide Poisoning HazardOutside Slab Installation Rooftop InstallationRoof Curb Installation General InformationRigging Rigging DetailsGAS Piping Natural Gas Connection Proper Piping PracticePropane Gas Pipe Sizing Electrical WiringTypical Propane Gas Piping Low Voltage Wiring Typical Electrical Wiring Unit VoltageTypical Thermostat and Unit 24 V Wiring Hookup Duct Cover Installation Down Discharge ApplicationsFilter Installation Circulating AIR and FiltersSTARTUP, ADJUSTMENTS, and Checks VentingCondensate Drain Normal Sequences of OperationWhite-Rodgers 36G22 Secondary Limit Control Pre-Operation ChecksWhite-Rodgers Model 36G22 Honeywell Model VR8215 Single-StageTemperature Rise Check Blower Speed AdjustmentsGas Input Natural Gas Only Check Main Burner Flame CheckTroubleshooting Maintenance Burner Flame Manifold AssemblyFlame Sensor Accessories and Functional Parts Functional Parts ListBlower Performance Data Single Phase CFM Watts Amps RiseRemoved AA & Used a T1 Heating Speed T2 Heating Speed T3 Heating Speed CFM Watts AmpsPG136090M41A* Rise Range 45 Blower Performance Data Heating Speeds Three Phase CFM Watts RPM Amps CFMRPM Heating Timing Chart Appendix Unit Dimensions PG1324,30,36,421** Wiring Diagram INSTALLER/SERVICEMAN THC-FIELD Wiring YL RD BL BL BLINSTALLER/SERVICEMAN Thermostat Field Wiring VMRGPG13363** Wiring Diagram INSTALLER/SERVICEMAN EconomizerGPG1348,603** Wiring Diagram BL BL BL RD RDOption Minimum Clearances Recommended Filter SizesThat’s why we know. . .There’s No Better Quality Quality Makes the Difference

A/GPG13 M specifications

Goodman Manufacturing is known for producing high-quality HVAC systems, and one of its standout offerings is the Goodman A/GPG13 M series. This air conditioning and heating unit delivers exceptional performance, reliability, and efficiency, making it a preferred choice for residential settings.

The Goodman A/GPG13 M is specifically designed to provide homeowners with an efficient and affordable solution for climate control. One of its main features is the energy-efficient compressor, which operates with a SEER rating of up to 13, ensuring reduced electricity consumption while effectively cooling your living space. This efficiency not only minimizes utility bills but also helps to lower your carbon footprint.

Another standout characteristic of the Goodman A/GPG13 M is its durable construction. The unit is engineered with a heavy-gauge, galvanized steel cabinet that has a polyester finish, providing protection against rust and corrosion. This durability ensures that the system can withstand the elements and lasting performance even in challenging climates.

The Goodman A/GPG13 M series also boasts advanced technology to enhance comfort levels in any home. The unit is equipped with a two-stage cooling system that can adjust to varying temperature demands, ensuring that your living space remains comfortable throughout the hot summer months. Additionally, the unit includes a multi-speed blower for more even air distribution, enhancing overall comfort.

Furthermore, the Goodman A/GPG13 M complies with rigorous environmental standards. It uses R-410A refrigerant, which is more environmentally friendly than older refrigerants like R-22, making it an excellent choice for eco-conscious consumers.

Installation of the Goodman A/GPG13 M is made easier with its lightweight design and user-friendly features, allowing HVAC professionals to install the system efficiently. The unit is backed by a comprehensive warranty, reflecting Goodman Manufacturing’s commitment to quality and customer satisfaction.

In summary, the Goodman A/GPG13 M series showcases an impressive combination of energy efficiency, durable construction, advanced technology, and eco-friendly refrigerant choices. It represents an ideal option for homeowners who seek a reliable HVAC solution that delivers consistent comfort while maintaining an eye on energy consumption and environmental impact.