DEHUMIDIFYING OPERATION (continued)

Operation mode

Auto

Dehumidifying

Quick Laundry

Condensation

Control

In this situation

In damp weather

To dry the laundry quickly

When controlling condensation formed on windows in winter time

Operating mechanism

In most of the cases, the room temperature at the time the button is pressed becomes the preset temperature.

(When room temperature is below 12°C, set 13°C. When it is 13°C~22°C, set +2°C. When it is below 23°C~26°C, set room temperature. When it is above 26°C, set 26°C)

Target humidity is around 50~60%. If the humidity becomes lower than the target value, operation stops. If it becomes higher than the target value, operation resume.

The operation mode may automatically be switched to cooling or heating for temperature control. (Refer to table below)

Detects outdoor temperature, room temperature and humidity to automatically select the most suitable combination of heating and powerful dehumidifying operations.

This operation is performed together with stainless plasma air purifying operation.

Priority is given to laundry drying.

Be sure use this mode when no one is in the room as the room temperature and humidity will be high temporarily.

3-hour timer function is used for this operation mode.

To control the condensation, priority is given to the operation for lowering humidity. Therefore, the room temperature goes down in this operation mode. The operation stops if the room temperature becomes 1°C or below.

2-hour timer function is used for this operation mode.

ENGLISH

Be careful when condensation control operation is performed if the outside temperature is low as it will lower the room temperature.

(OFF TIMER) and (ON TIMER) (page 26), which are to be set using clock function, are not available during dehumidifying (quick laundry and condensation control modes) operation. However, the timer (for 30 minutes and 1-9 hours) can be set for quick laundry and condensation control modes with the (SLEEP) button.

To set to your desired temperature and humidity while executing dehumidifying, it is recommended to use manual dehumidifying function. (Page 17)

If you do not wish room temperature to be too high when drying the laundry, use the preference (Powerful) mode instead of quick laundry mode. (Page 18)

The operation mode may automatically be switched to cooling or heating for temperature control. At this time, the room humidity may vary by approximately 10%.

 

 

 

 

 

Dehumidifying operation

 

 

 

 

Operation

 

Heating

 

 

 

 

Approx. 3°C if outside temp. is

Cooling

 

 

 

 

 

 

 

 

 

 

below approx. 32°C.

 

 

stop

 

operation

 

 

 

 

 

 

operation

 

 

 

 

 

Approx. 1°C if outside temp. is

 

 

 

 

 

 

 

 

 

 

 

 

 

About 3°C

 

 

above approx. 32°C.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1ºC

 

 

 

Room temperature set

Current room temperature

COOLING OPERATION

Press the (COOL) button to start cooling operation.

Press the (COOL) button.

Adjust the room temperature and fan speed to your preference. Temperature range between 16°C~32°C can be set.

 

 

 

 

 

 

 

 

 

 

 

 

 

STOP

Press the

 

 

 

(STOP) button.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A short beep sounds and cooling operation stops.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– 15 –

Image 15
Contents RAS-SX10HAK RAS-SX13HAK РУССКИЙ ∂ÏÏËÓÈο PORTUGUÊS SPANISH ITALIANO FRANÇAIS DEUTSCH ENGLISHRAS-SX10HAK / RAC-SX10HAK RAS-SX13HAK / RAC-SX13HAK INDOOR UNIT OUTDOOR UNITSAFETY PRECAUTION PRECAUTIONS DURING INSTALLATIONPRECAUTIONS DURING SHIFTING OR MAINTENANCE PRECAUTIONS DURING OPERATIONENGLISH ABOUT OUTDOOR UNIT NAMES AND FUNCTIONS OF EACH PARTINDOOR UNIT OUTDOOR UNITHow to Attach the Nano Titanium Air Cleaning Mesh Preparation INDOOR UNIT CONTROL PANEL / CLEANING UNITSTART OPERATIONS REMOTE CONTROLLERNAMES AND FUNCTIONS OF EACH PART continued BUTTONS TOPOWERFULL Button FUNCTION SELECTORINSTALLING ANTI-MOLD WASABI CASSETTE 2 Install the anti-mold wasabi cassette1 Open the front panel Close the front panel Perform the filter cleaning unit operation check FILTER CLEANING UNIT OPERATION CHECK1 Make sure the power plug is firmly plugged into the power outlet 2 Performing operation check after the power is turned onABOUT ADDRESS SELECTOR SWITCH PREPARE THE REMOTE CONTROLLERInstall the batteries Open the cover and press the RESETPREPARE THE REMOTE CONTROLLER continued Ampere setting Standard/Save can be selectedWHEN OPERATING THE REMOTE CONTROLLER AUTOMATIC OPERATION Adjust the room temperatureAUTOMATIC OPERATION STOPDEHUMIDIFYING OPERATION HEATING OPERATIONCOOLING OPERATION DEHUMIDIFYING OPERATION continuedDRY COOL OPERATION Setting Range of AUTO/MANUAL Operation 40 %~70 %10C~32C 16C~32CSTOP POWERFUL OPERATIONCANCEL STAINLESS PLASMA AIR PURIFYING FAN OPERATIONExample Cooling INFRARED HUMAN PRESENCE SENSING FUNCTIONDYNAMIC AIR DEFLECTION FUNCTION TRACING/EVASION Set the detection speed of the sensor to “Slow”Fine tune the detection speed of the sensor STOP While INTERNAL CLEANING OPERATIONSLEEP OPERATION MOLD MONITOR OPERATION Vertical air flow of your preference ADJUSTING THE VERTICAL AIRFLOW DIRECTIONSet automatically Vertical airflow swingADJUSTING THE HORIZONTAL AIRFLOW DIRECTION Adjust the horizontal airflow directionHorizontal angle of your preference TIMER PRESET OPERATION How to preset the timerHow to preset the OFF TIMER ON TIMER How to cancel the preset timer ITALIANO FRANÇAIS DEUTSCHРУССКИЙ ∂ÏÏËÓÈο PORTUGUÊS SPANISH Combination of ON TIMER and DEHUMIDIFY button FURTHER CONVENIENT TIMER FUNCTIONCombination of Sleep Timer and On Timer operation SLEEP TIMER OPERATION1 Automatic filter cleaning operation FILTER CLEANING OPERATIONSTOP Press Conditions under which automatic filter cleaning is performedAbout the noise during filter cleaning ITALIANO FRANÇAIS DEUTSCH ENGLISHHOW TO PROHIBIT THE FILTER CLEANING OPERATION FILTER CLEANING OPERATION continued2 Manual filter cleaning operation 3 MaintenanceSet to prohibit the filter cleaning operation again Set to prohibit the filter cleaning operationReturn to the filter cleaning operation setting Operate the manual filter cleaning operation. Page3 Turn on the power supply or turn on the circuit breaker MAINTENANCEMaintenance of dust box Stop the operation with the remote controller andor turn off the circuit breaker Maintenance of Stainless Mesh Filtercontroller and unplug the power plug Stop the operation with the remoteVacuum the dust MAINTENANCE continuedMaintenance of mesh stainless filter continued Turn on the power supply or turn on the circuit breakerRemove the front panel Maintenance of dust catcherthe power supply or turn off the circuit breaker Stop the operation with the remote controller and unplugand unplug the power supply or turn off the Maintenance of electric dust collector electrodes4 Turn on the power supply. or turn on the circuit breaker Stop the operation with the remote controllerNAMES AND FUNCTIONS OF EACH PART Page UNDERSTANDING THE OPERATING MECHANISMTHE IDEAL WAYS OF OPERATION FILTER CLEANING OPERATION TROUBLESHOOTINGTROUBLESHOOTING continued PLEASE CHECK THE FOLLOWING BEFORE SERVICEANTI-MOLD WASABI CASSETTE THE FOLLOWING CASES DOES NOT INDICATE MALFUNCTION Unplug the power Disconnect the power supplyReconnect the power supply Automatic operation starts when the temporary switchREGULAR INSPECTION INSPECTION AND MAINTENANCEDisplay OPERATION DISPLAY CHARTDuring internal cleaning operation page During preset of the mold monitor operation pageMEMO 474 A 分 体 式 冷 气 机 РУССКИЙ ∂ÏÏËÓÈο PORTUGUÊS SPANISH ITALIANO FRANÇAIS 中 国 语室内机 室外机 室内机/室外机使用上的注意事项 安全注意事项安装方面的注意事项 搬移或修理时的注意事项使用上的注意事项 室外机的说明 各部的名称和功能中 国 语 室内机操作部和清扫部纳米钛空清网的安装方法 可以使运转开始的按钮 各部的名称和功能 继续功能选择部 防霉芥末盒的安装 1 打开前面板。2 安装防霉芥末盒。 3 关上前面板。 过滤网清扫部的动作确认 1 将电源线可靠地接入电源中。 警告2 进行接通电源后的动作检查。 进行过滤网清扫部的动作检查。 用有尖细端头的物品按下复位 请准备好遥控器装入电池。 打开盖板请准备好遥控器 继续 4 能够设定电流值标准/节省切换。操作遥控器时 风速的切换 自动运转自动运转 室温的微调节围为 40% ~ 70% 。 制热运转乾爽除湿运转 可设定的温度范围为16C ~ 32C。制冷运转 乾爽除湿运转 继续凉快运转 16 ~32 干燥除湿、凉快运转的自动/手动切换10 ~32 50 %~60 %不锈等离子空气清净送风运转 全功率运转乾爽除湿 以冷房运转为例 红外线人体检知传感器传感器检测速度微调 动态导风(追踪/回避)运转机能以暖房运转为例 传感器的检测速度设定为「慢速」内部清洁运转 功能选择 钮 快眠运转霉菌监视运转 上下喜好风向 上下风向的调节自动设定 上下风向摆动左右风向的调节 左右风向的摆动左右喜好调节 定时器的预约方法 1 按3 按 定时器预约运转定时预约的取消方法 4 按开机定时 与 乾爽除湿 钮的组合 更方便的定时器使用方法1 预约 开机定时。 74, 75页 睡眠定时运转睡眠定时运转和开机定时的组合 开机定时 进行第二天早上的运转等。过滤网清扫运转 1 自动过滤网清扫运转在过滤网清扫运转结束时 , 返回到 过滤网清扫运转时的声音 进行自动过滤网清扫运转的条件过滤网清扫运转禁止的设定方法 3 维护过滤网清扫运转(继续) 2 手动过滤网清扫运转1 过滤网清扫运转禁止的设定方法。 2 重新设定过滤网清扫运转禁止的方法。 3 进行手动过滤网清扫运转 80页 4 再一次设定过滤网清扫运转禁止的方法。 1 , 2 , 4 的设定方法, 80页清洁 指示灯反复出现闪烁、亮灯和变暗现象。非故障 在清扫机体前,请使用遥控器停止操作或者切断断路器。 集尘盒的保养方法请用遥控器停止操作, 断开电源。 或者切断断路器 用水清洗集尘盒。 接入电源。 或打开断路器)4 拆下前面的不锈过滤网。 不锈过滤网的保养方法1 请用遥控器停止操作,并断开电源。 或者切断断路器 2 打开前面板。 3 拆下前面板。6 安装不锈过滤网。 维护(继续)不锈过滤网的保养方法(继续) 5 用吸尘器等吸掉灰尘。拆下捕尘器。 捕尘器的保养方法请用遥控器停止操作,并断开电源。 或者切断断路器 。3 用牙刷清除电气集尘器电极的脏污。 维护 继续电气集尘器电极的保养方法 1 请用遥控器停止操作,并断下电源。 或者切断断路器 2 请用双手轻轻打开上下导风板。 注意各部的名称和功能 52页 运转的原理和希望用户事前了解的事项3. 要外出时, 可有效利用霉菌监视功能。 (请参照霉菌监视运转) 4. 就寝时, 可有效利用定时功能。 更理想的使用方法1. 建议用户设定为“恰当的室温”, 既省钱又有益於身体。 请不要将室温设定得过低或过高。对健康不利,且浪费电力。 拉上窗帘或百叶遮帘, 可以减少热量的进出, 更有效地用电。 2. 请时常换气。 注意 如果与燃气器具同一室使用时,必要进行换气。过滤网清扫部的动作的说明 遇到问题时遇到问题时 继续 防霉芥茉盒的说明请服务人员维修以前,请先检查以下事项 运转 指 这非有故障按下暂时运转开关后, 会进行自动运转。 出现下述情况时,请迅即向销售店咨询暂时运转 进行暂时运转时,请先断开电源。 或切断断路器。) 再次接入电源。或打开断路器。)检查整备 定期检查内部清洁运转中 运转显示快查表Page 474 A