Goodman Mfg GSZ/VSZ 13 SEER 386, 65.0 60.7, 56.2, 33.4 31.2, 28.9, 11.4 10.7, 13.0 12.4, 11.7

Page 40

SPLIT SYSTEM HEATING PERFORMANCE

EXPANDED PERFORMANCE DATA

MODEL: GSZ130483A* / AR*F486016**

 

 

 

 

 

 

 

 

 

HEATING OPERATION

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

65

60

55

50

47

45

40

35

30

25

20

17

15

10

5

0

-5

-10

MBh

55.3

52.4

49.3

46.1

44.0

42.6

39.6

36.5

33.6

31.1

28.6

27.0

26.0

23.3

20.7

18.0

15.4

12.6

DT

32.0

30.3

28.5

26.7

25.5

24.7

22.9

21.1

19.5

18.0

16.5

15.6

15.0

13.5

12.0

10.4

8.9

7.3

KW

3.94

3.87

3.80

3.72

3.68

3.65

3.58

3.51

3.49

3.42

3.34

3.30

3.27

3.20

3.12

3.05

2.98

2.90

AMPS

11.1

10.3

9.7

9.1

8.8

8.6

8.2

7.8

7.5

7.2

6.8

6.7

6.6

6.3

5.9

5.6

5.2

4.7

COP

4.10

3.96

3.80

3.62

3.50

3.42

3.24

3.05

2.82

2.66

2.50

2.39

2.33

2.14

1.94

1.73

1.51

1.27

EER

14.0

13.5

13.0

12.4

11.9

11.7

11.1

10.4

9.6

9.1

8.6

8.2

7.9

7.3

6.6

5.9

5.2

4.3

HI PR

386

370

356

340

332

326

313

300

288

275

264

258

253

243

234

224

216

209

LO PR

126

117

110

101

95

91

84

75

68

60

53

49

48

40

35

29

26

20

MODEL: GSZ130484A* / AR*F486016**

 

 

 

 

 

 

 

 

 

HEATING OPERATION

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

65

60

55

50

47

45

40

35

30

25

20

17

15

10

5

0

-5

-10

MBh

55.3

52.4

49.3

46.1

44.0

42.6

39.6

36.5

33.6

31.1

28.6

27.0

26.0

23.3

20.7

18.0

15.4

12.6

DT

32.0

30.3

28.5

26.7

25.5

24.7

22.9

21.1

19.5

18.0

16.5

15.6

15.0

13.5

12.0

10.4

8.9

7.3

KW

3.94

3.87

3.80

3.73

3.68

3.65

3.58

3.51

3.49

3.42

3.34

3.30

3.27

3.20

3.12

3.05

2.98

2.90

AMPS

6.1

5.7

5.4

5.1

4.9

4.8

4.6

4.4

4.2

4.0

3.8

3.8

3.7

3.5

3.3

3.2

3.0

2.7

COP

4.10

3.96

3.80

3.62

3.50

3.42

3.24

3.05

2.82

2.66

2.50

2.39

2.33

2.14

1.94

1.73

1.51

1.27

EER

14.0

13.5

13.0

12.4

11.9

11.7

11.1

10.4

9.6

9.1

8.6

8.2

7.9

7.3

6.6

5.9

5.2

4.3

HI PR

386

370

356

340

332

326

313

300

288

275

264

258

253

243

234

224

216

209

LO PR

126

117

110

101

95

91

84

75

68

60

53

49

48

40

35

29

26

20

MODEL: GSZ130603A* /AR*F486016**

 

 

 

 

 

 

 

 

 

HEATING OPERATION

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

65

60

55

50

47

45

40

35

30

25

20

17

15

10

5

0

-5

-10

MBh

72.9

69.0

65.0

60.7

58.0

56.2

52.2

48.1

44.9

41.4

38.1

36.0

34.7

31.1

27.6

24.0

20.5

16.8

DT

37.5

35.5

33.4

31.2

29.8

28.9

26.9

24.8

23.1

21.3

19.6

18.5

17.8

16.0

14.2

12.4

10.6

8.6

KW

5.21

5.11

5.01

4.91

4.86

4.81

4.72

4.62

4.65

4.55

4.45

4.39

4.34

4.24

4.14

4.04

3.94

3.84

AMPS

13.1

12.2

11.4

10.7

10.3

10.1

9.5

9.0

8.6

8.2

7.8

7.7

7.6

7.2

6.7

6.3

5.8

5.2

COP

4.10

3.95

3.79

3.62

3.50

3.42

3.24

3.05

2.82

2.67

2.51

2.40

2.34

2.15

1.95

1.74

1.53

1.28

EER

14.0

13.5

13.0

12.4

11.9

11.7

11.1

10.4

9.6

9.1

8.6

8.2

8.0

7.3

6.7

6.0

5.2

4.4

HI PR

416

399

383

367

358

351

338

324

310

296

285

278

273

262

252

242

233

225

LO PR

133

123

115

106

100

96

89

79

71

64

56

52

50

42

37

31

27

21

MODEL: GSZ130604A* /AR*F486016**

 

 

 

 

 

 

 

 

 

HEATING OPERATION

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

65

60

55

50

47

45

40

35

30

25

20

17

15

10

5

0

-5

-10

MBh

72.9

69.0

65.0

60.7

58.0

56.2

52.2

48.1

44.9

41.4

38.1

36.0

34.7

31.1

27.6

24.0

20.5

16.8

DT

37.5

35.5

33.4

31.2

29.8

28.9

26.9

24.8

23.1

21.3

19.6

18.5

17.8

16.0

14.2

12.4

10.6

8.6

KW

5.21

5.11

5.01

4.91

4.86

4.81

4.72

4.62

4.65

4.55

4.45

4.39

4.34

4.24

4.14

4.04

3.94

3.84

AMPS

6.5

6.1

5.7

5.4

5.2

5.1

4.8

4.6

4.4

4.2

4.1

4.0

3.9

3.7

3.5

3.3

3.1

2.8

COP

4.10

3.95

3.79

3.62

3.50

3.42

3.24

3.05

2.82

2.67

2.51

2.40

2.34

2.15

1.95

1.74

1.53

1.28

EER

14.0

13.5

13.0

12.4

11.9

11.7

11.1

10.4

9.6

9.1

8.6

8.2

8.0

7.3

6.7

6.0

5.2

4.4

HI PR

416

399

383

367

358

351

338

324

310

296

285

278

273

262

252

242

233

225

LO PR

133

123

115

106

100

96

89

79

71

64

56

52

50

42

37

31

27

21

High pressure is measured at the liquid service valve (the smaller valve). Low pressure is measured at the gauge port connection.

Calculations are based on nominal CFM and 70 °F indoor dry bulb.

AMPS = Outdoor unit amps (comp.+fan) KW = Total system power

*Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temberature

40

Image 40
Contents Technical Manual 024 Product IdentificationProduct Identification Product Design AA AAProduct Dimensions Model Dimensions W x D x HHeat Pump Specifications VSZ13018-601AVSZ13024,36B SZ130241B SZ130361BGSZ13036-603,4A GSZ130363A GSZ130483A GSZ130484A GSZ130603A GSZ130604ACooling Performance Data VSZ130181A375 17.4147 VSZ130241A Airflow 23.0378 141VSZ130241B 800700 357381 140VSZ130301A 28.4 10.3383 145VSZ130361A 35.0 12.6400 146VSZ130361B Outdoor Ambient Temperature 105 115 11.5397 145Model GSZ130363A* / AR*F364216 GZ130363A32.92 1425 13.3 VSZ130421A 13.9 40.5363 VSZ130481A 46.0 15.8390 150Model GSZ130483A* / AR*F486016 GSZ130483A373 398 Model GSZ130484A* / AR*F486016 GSZ130484A380 405 VSZ130601A Expanded Perform Ance Data Model GSZ130603A* /AR*F486016 GSZ130603A10.8 11.2 57.0138 GSZ130604A Model GSZ130604A* /AR*F486016227 244 258 269 255 274 290 302 312 Odel G/VSZ130301A AR*F30301 Split System Heating PerformanceOutdoor Am bient Tem perature Outdoor Ambient Temperature 34.0Expanded Performance Data Outdoor Am bie nt Te m pe rature386 65.0 60.756.2 33.4 31.2Performance Data Performance TestWiring VSZ13018-601A/BWiring Diagrams Wiring is subject to change, always refer to