HEAT PUMP SPECIFICATIONS

GSZ130[36-60][3,4]A*

 

GSZ130363A*

GSZ130483A*

GSZ130484A*

GSZ130603A*

GSZ130604A*

 

 

 

 

 

 

Nominal Capacities

 

 

 

 

 

Cooling Capacity, BTUH

36,000

48,000

48,000

60,000

60,000

Heating Capacity, BTUH

34,000

44,000

44,000

58,000

58,000

 

 

 

 

 

 

Decibels

74

76

76

75

75

 

 

 

 

 

 

Compressor

 

 

 

 

 

R.L. Amps

10.4

13.1

6.1

16.0

7.8

L.R. Amps

73.0

83.1

41.0

110.0

52.0

Type

Scroll

Scroll

Scroll

Scroll

Scroll

 

 

 

 

 

 

Condenser Fan Motor

 

 

 

 

 

Horsepower

1/4

1/4

1/4

1/4

1/4

F.L. Amps

1.50

1.50

0.80

1.50

0.80

 

 

 

 

 

 

Refrigerant System

 

 

 

 

 

Liquid Line, Inches O.D.* 3

3/8"

3/8"

3/8"

3/8"

3/8"

Suction Line, Inches O.D.* 3

7/8"

1 1/8"

1 1/8"

1 1/8"

1 1/8"

Liquid Valve Connection, Inches O.D.*

3/8"

3/8"

3/8"

3/8"

3/8"

Suction Valve Connection, Inches O.D.*

3/4"

7/8"

7/8"

7/8"

7/8"

Refrigerant Charge

171.0

222.0

222.0

245.0

245.0

Piston Size

0.068

0.078

0.078

0.088

0.088

 

 

 

 

 

 

Power Supply

208/230-60-3

208/230-60-3

460-60-3

208/230-60-3

460-60-3

Minimum Circuit Ampacity(1)

14.5

17.9

8.4

21.5

10.6

Maximum Overcurrent Device(2)

20

30

15

35

15

Min / Max Volts

197 / 253

197 / 253

414 / 506

197 / 253

414 / 506

 

 

 

 

 

 

Electrical Conduit Size

 

 

 

 

 

Power Supply (Inches)

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

 

 

 

 

 

 

Approximate Shipping W eight

232

235

234

262

261

 

 

 

 

 

 

(1)Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes.

(2)Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.

(3)Tested and rated in accordance with AHRI Standard 210/240

NOTES:

Always check the S & R plate for electrical data on the unit being installed.

Installer will need to supply 7/8" to 1-1/8" adapters for suction line connections (4 & 5 ton units).

Installer will need to supply 3/4" to 7/8" adapters for suction line connections (3 ton unit).

Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.

Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE OUTDOOR UNIT, NOT THE INDOOR COIL.

NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.

Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial plate for the most up-to-date general and electrical information.

8

Image 8
Contents Technical Manual 024 Product IdentificationProduct Identification Product Design AA AAProduct Dimensions Model Dimensions W x D x HHeat Pump Specifications VSZ13018-601AVSZ13024,36B SZ130241B SZ130361BGSZ13036-603,4A GSZ130363A GSZ130483A GSZ130484A GSZ130603A GSZ130604ACooling Performance Data VSZ130181A147 17.4375 VSZ130241A Airflow 23.0378 141VSZ130241B 800700 357381 140VSZ130301A 28.4 10.3383 145VSZ130361A 35.0 12.6400 146VSZ130361B Outdoor Ambient Temperature 105 115 11.5397 14532.92 GZ130363AModel GSZ130363A* / AR*F364216 1425 13.3 VSZ130421A 363 40.513.9 VSZ130481A 46.0 15.8390 150373 GSZ130483AModel GSZ130483A* / AR*F486016 398 380 GSZ130484AModel GSZ130484A* / AR*F486016 405 VSZ130601A Expanded Perform Ance Data 10.8 GSZ130603AModel GSZ130603A* /AR*F486016 138 57.011.2 GSZ130604A Model GSZ130604A* /AR*F486016227 244 258 269 255 274 290 302 312 Outdoor Am bient Tem perature Split System Heating PerformanceOdel G/VSZ130301A AR*F30301 Outdoor Ambient Temperature 34.0Expanded Performance Data Outdoor Am bie nt Te m pe rature386 65.0 60.756.2 33.4 31.2Performance Data Performance TestWiring VSZ13018-601A/BWiring Diagrams Wiring is subject to change, always refer to