Bard Q24A1 Description of Standard Equipment, Optional CFM Q36A1, Q42A1, Q48A1 and Q60A1 only

Page 28

START UP

DESCRIPTION OF STANDARD

EQUIPMENT

High Pressure Switch

Provides refrigerant circuit high pressure protection. Includes lockout circuit that is resettable from room thermostat.

Compressor Control Module

Provides short cycle protection for the compressor which extends compressor life, as well as high and low pressure switch monitoring and alarm functions.

Service Lights

One service light indicates when service is required.

Check System – detects high or low pressure switch operation for compressor protection.

OPTIONAL CFM (Q36A1, Q42A1, Q48A1 AND Q60A1 ONLY)

These units are shipped from the factory set to operate at the optional CFM level shown in Table 7. This provides lower operating sound levels for non-ducted, free discharge applications. This CFM level will reduce the system capacity performance by approximately 2% at the same energy efficiency.

Rated CFM is required for ducted applications for maximum performance rating. To obtain full CFM on these models, connect jumper wire as follows:

1.Disconnect all power to the unit. Failure to do so may result in damage to the motor.

2.Open return air service panel

3.Open inner control panel cover

4.Locate low voltage terminal strip. There is a pink jumper wire with both ends attached to terminal marked “G2”. Move one end of this jumper to terminal “Y”.

5.Reverse steps to reassemble.

IMPORTANT INSTALLER NOTE

For improved start-up performance, wash the indoor coil with a dishwasher detergent.

CAUTION

Do not plug in or unplug blower motor

connectors while the power is on.

Failure to do so may result in motor failure.

PHASE MONITOR

All units with three phase scroll compressors are equipped with a 3 phase line monitor to prevent compressor damage due to phase reversal.

The phase monitor in this unit is equipped with two LEDs. If the Y signal is present at the phase monitor and phases are correct the green LED will light and the compressor contactor is allowed to energize.

If phases are reversed, the red fault LED will be lit and compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply leads to the unit. Do not reverse any of the unit factory wires as damage may occur.

THREE PHASE SCROLL COMPRESSOR START UP INFORMATION

Scroll compressors, like several other types of compressors, will only compress in one rotational direction. Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction.

However, three phase compressors will rotate in either direction depending upon phasing of the power. Since there is a 50-50 chance of connecting power in such a way as to cause rotation in the reverse direction, verification of proper rotation must be made. Verification of proper rotation direction is made by observing that suction pressure drops and discharge pressure rises when the compressor is energized. Reverse rotation also results in an elevated sound level over that with correct rotation, as well as, substantially reduced current draw compared to tabulated values.

Verification of proper rotation must be made at the time the equipment is put into service. If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor. However, reverse operation for even one hour may have a negative impact on the bearing due to oil pump out.

Manual

2100-522B

Page

28 of 38

Image 28
Contents Models Contents Getting Other Information and Publications For More INFORMATION, Contact These PublishersTECSeries General Information Tecmodel NomenclatureFactory BUILT-IN Electric Heat Table Electrical Specifications Unit Dimensions Shipping Damage Unit Removal from SkidAIR Seal Under Qtec Unit Removal of Unit from SkidMinimum Installation Height Handling Unit After Removal from SkidGeneral Unit on Appliance CartInstallation with Free Blow Plenum Ducted Application Duct Work FiltersSupply Duct Connections Filter LocationService Light Fresh AIR IntakeCondensate Drain Optional Rear Drain KitsOptional Side Drain Side View Installation Standard Rear Drain Rear Drain TOP ViewWall Sleeve Plug Installed If Used MIS-2472 Unit Mounting Mounting the Unit Installation InstructionsRemoving Locking Screws from Wheels Wiring Main Power Wiring LOW Voltage WiringComponent Location Operating Voltage RangeLOW Voltage Connections LOW Voltage Connections For DDC ControlThermostat Predominant Features Wall ThermostatsRemote Thermostat Wiring Diagram Thermostat OptionUnit Mounted Thermostat Wiring Diagram Thermostat Option Thermostat Option8403-060 Plug #2 Orange Purple Brown/White Yellow Blue Red Red/White Black Black/White Yellow Brown Start UP Safety PracticesTopping OFF System Charge Important Installer Note Phase MonitorThree Phase Scroll Compressor Start UP Information Description of Standard EquipmentService Hints Compressor Control ModuleVent Options Mist Eliminator ServiceEconomizer or Commercial Room Tecenergy Recovery Ventilator OptionFresh AIR Damper Removal Qerv Removal Pressure Service Ports Sequence of OperationOptional Climate Controls Sequence of Operation CO2 Controller Factory SET to PPMTroubleshooting GE ECM Motors Don’tTroubleshooting GE ECM Motors CONT’D Replacing ECM Control ModuleFAN Blade Setting Dimensions FAN Blade SettingFAN Blade Dimensions Refrigerant ChargeCooling Pressure ALL Temperatures in Degrees F Model Temp Pressure

Q48A1, Q24A1, Q60A1, Q42A1, Q36A1 specifications

The Bard Q60A1, Q48A1, Q30A1, Q36A1, and Q42A1 are innovative medical devices designed for versatile applications in various healthcare settings. These models are known for their adaptability, precision, and advanced technologies, making them essential tools for healthcare professionals.

The Q60A1 model stands out due to its user-friendly interface and high-resolution display. It is equipped with advanced sensors that provide real-time monitoring and feedback. The device's portability allows it to be easily moved between different areas of a facility, making it ideal for both inpatient and outpatient services. The Q60A1 also integrates seamlessly with electronic health records, enabling better data management and streamlined clinical workflows.

The Q48A1 model emphasizes flexibility and customization. With multiple configurations, this device is adept at accommodating a range of medical procedures. Its modular design allows healthcare providers to adjust the setup to meet their specific needs, enhancing both efficiency and patient comfort. The Q48A1 is favored for its rapid setup time, facilitating quick responses in critical situations.

In contrast, the Q30A1 prioritizes compactness without sacrificing functionality. This device is specifically engineered for smaller spaces, making it a perfect fit for clinics and smaller hospitals. Despite its size, the Q30A1 boasts a robust set of features, including wireless connectivity and the ability to store a significant amount of patient data. Its intuitive controls simplify operation, even for those with minimal training.

The Q36A1 model is notable for its durability and resilience in challenging environments. Constructed with high-grade materials, it withstands wear and tear while maintaining precise performance. The Q36A1 also includes advanced safety features, such as automatic shut-off mechanisms, which ensure safe operation in emergency conditions. Its reliability makes it a trusted choice across various healthcare sectors.

Lastly, the Q42A1 model focuses on user experience, combining technology with ease of use. It is equipped with voice-activated controls and touch-sensitive displays, streamlining interaction for medical staff. This model also features advanced data analytics tools, providing insights that can drive improvements in patient care.

Overall, the Bard Q60A1, Q48A1, Q30A1, Q36A1, and Q42A1 reflect the latest advancements in medical technology, each serving unique functions suited to different healthcare needs. These devices not only enhance operational efficiency but also improve patient outcomes through better monitoring and data management capabilities.