INSTALLATION INSTRUCTIONS

MOUNTING THE UNIT

When installing a Q-TECunit near an interior wall on the left side, a minimum of 8 inches is required; 12 inches is preferred.

When installing a Q-TECunit near an interior wall on the right side, a minimum of 18 inches is required as additional space is required to connect the side drain. If the rear condensate drain kit QCDS48 is used the minimum can be reduced to 8 inches.

This clearance is required to allow for the attachment of the unit to the sleeve and side trim pieces to the wall.

This unit is to be secured to the wall sleeve with mounting brackets provided. The unit itself, the supply duct and the free blow plenum are suitable of “0” clearance to combustible material.

Following are the steps for mounting the Q-TEC. For reference see Figure 13A for external mounting bracket or 13B for internal bolt secured bracket (recommended).

1.Attach mounting brackets to the wall sleeve with screws provided. Either use external mounting bracket (Fig. 13A) or internal bolt bracket (Fig. 13B).

2.Position the unit in front of the sleeve with the condenser section toward the sleeve.

3.Remove the locking screws from the wheels. Refer to Figure 14.

4.Roll the unit into the sleeve. Make sure to check both sides of the unit as it is being rolled to keep it centered in the sleeve. Also check the

alignment to the mounting brackets. This unit must be level from side to side. If adjustments are necessary, shim up under the rollers with sheets of steel or any substance that is not affected by moisture.

5.Make sure the gasket on the rear of the unit is touching the sleeve across the top and down both sides. This is a rain water seal.

6.Secure the mounting brackets to the unit with screws provided, #10 hex head sheet metal screws (Figure 13A) or use nut and washer to secure sleeve (Figure 13B).

7.Bottom trim extensions are provided for use when wall is less than 14 inches but greater than 10.5 inches. Secure to wall with screws (not provided).

8.Attach the bottom trim piece to the unit with the screws provided (dark colored).

9.Position side trim pieces to wall and attach with field supplied screws. There are two long pieces and two short pieces supplied. The long pieces are to enclose the gap behind the unit. The short pieces are to fill the gap behind the cabinet extension or the free blow plenum box. They may be cut to suit your ceiling height or overlap the unit side trim. There is sufficient length to trim up to a 10'2" ceiling.

NOTE: If the exterior wall thickness is between 5 inches to 10.5 inches, a side trim extension piece kit, model QSTX42, is available.

FIGURE 14

REMOVING LOCKING SCREWS FROM WHEELS

REMOVE SCREWS FROM WHEELS

BEFORE ROLLING INTO PLACE

Manual

2100-522B

Page

19 of 38

Image 19
Contents Models Contents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsTecmodel Nomenclature TECSeries General InformationFactory BUILT-IN Electric Heat Table Electrical Specifications Unit Dimensions Removal of Unit from Skid Shipping DamageUnit Removal from Skid AIR Seal Under Qtec UnitUnit on Appliance Cart Minimum Installation HeightHandling Unit After Removal from Skid GeneralInstallation with Free Blow Plenum Ducted Application Filter Location Duct WorkFilters Supply Duct ConnectionsOptional Rear Drain Kits Service LightFresh AIR Intake Condensate DrainStandard Rear Drain Rear Drain TOP View Optional Side Drain Side View InstallationWall Sleeve Plug Installed If Used MIS-2472 Unit Mounting Mounting the Unit Installation InstructionsRemoving Locking Screws from Wheels Operating Voltage Range Wiring Main PowerWiring LOW Voltage Wiring Component LocationLOW Voltage Connections For DDC Control LOW Voltage ConnectionsWall Thermostats Thermostat Predominant FeaturesThermostat Option Remote Thermostat Wiring DiagramThermostat Option Unit Mounted Thermostat Wiring Diagram Thermostat Option8403-060 Plug #2 Orange Purple Brown/White Yellow Blue Red Red/White Black Black/White Yellow Brown Start UP Safety PracticesTopping OFF System Charge Description of Standard Equipment Important Installer NotePhase Monitor Three Phase Scroll Compressor Start UP InformationCompressor Control Module Service HintsVent Options Mist Eliminator ServiceEconomizer or Commercial Room Option Tecenergy Recovery VentilatorFresh AIR Damper Removal Qerv Removal CO2 Controller Factory SET to PPM Pressure Service PortsSequence of Operation Optional Climate Controls Sequence of OperationDon’t Troubleshooting GE ECM MotorsReplacing ECM Control Module Troubleshooting GE ECM Motors CONT’DRefrigerant Charge FAN Blade Setting DimensionsFAN Blade Setting FAN Blade DimensionsModel Temp Pressure Cooling Pressure ALL Temperatures in Degrees F

Q48A1, Q24A1, Q60A1, Q42A1, Q36A1 specifications

The Bard Q60A1, Q48A1, Q30A1, Q36A1, and Q42A1 are innovative medical devices designed for versatile applications in various healthcare settings. These models are known for their adaptability, precision, and advanced technologies, making them essential tools for healthcare professionals.

The Q60A1 model stands out due to its user-friendly interface and high-resolution display. It is equipped with advanced sensors that provide real-time monitoring and feedback. The device's portability allows it to be easily moved between different areas of a facility, making it ideal for both inpatient and outpatient services. The Q60A1 also integrates seamlessly with electronic health records, enabling better data management and streamlined clinical workflows.

The Q48A1 model emphasizes flexibility and customization. With multiple configurations, this device is adept at accommodating a range of medical procedures. Its modular design allows healthcare providers to adjust the setup to meet their specific needs, enhancing both efficiency and patient comfort. The Q48A1 is favored for its rapid setup time, facilitating quick responses in critical situations.

In contrast, the Q30A1 prioritizes compactness without sacrificing functionality. This device is specifically engineered for smaller spaces, making it a perfect fit for clinics and smaller hospitals. Despite its size, the Q30A1 boasts a robust set of features, including wireless connectivity and the ability to store a significant amount of patient data. Its intuitive controls simplify operation, even for those with minimal training.

The Q36A1 model is notable for its durability and resilience in challenging environments. Constructed with high-grade materials, it withstands wear and tear while maintaining precise performance. The Q36A1 also includes advanced safety features, such as automatic shut-off mechanisms, which ensure safe operation in emergency conditions. Its reliability makes it a trusted choice across various healthcare sectors.

Lastly, the Q42A1 model focuses on user experience, combining technology with ease of use. It is equipped with voice-activated controls and touch-sensitive displays, streamlining interaction for medical staff. This model also features advanced data analytics tools, providing insights that can drive improvements in patient care.

Overall, the Bard Q60A1, Q48A1, Q30A1, Q36A1, and Q42A1 reflect the latest advancements in medical technology, each serving unique functions suited to different healthcare needs. These devices not only enhance operational efficiency but also improve patient outcomes through better monitoring and data management capabilities.