Bard Q60A1, Q30A1, Q36A1, Q42A1, Q24A1, Q48A1 Start UP, Topping OFF System Charge, Safety Practices

Page 27

START UP

THESE UNITS REQUIRE R-410A REFRIGERANT AND POLYOL ESTER OIL.

GENERAL:

1.Use separate service equipment to avoid cross contamination of oil and refrigerants.

2.Use recovery equipment rated for R-410A refrigerant.

3.Use manifold gauges rated for R-410A (800 psi/250 psi low).

4.R-410A is a binary blend of HFC-32 and HFC-125.

5.R-410A is nearly azeotropic - similar to R-22 and R-12. Although nearly azeotropic, charge with liquid refrigerant.

6.R-410A operates at 40-70% higher pressure than R-22, and systems designed for R-22 cannot withstand this higher pressure.

7.R-410A has an ozone depletion potential of zero, but must be reclaimed due to its global warming potential.

8.R-410A compressors use Polyol Ester oil.

9.Polyol Ester oil is hygroscopic; it will rapidly absorb moisture and strongly hold this moisture in the oil.

10.A liquid line dryer must be used - even a deep vacuum will not separate moisture from the oil.

11.Limit atmospheric exposure to 15 minutes.

12.If compressor removal is necessary, always plug compressor immediately after removal. Purge with small amount of nitrogen when inserting plugs.

TOPPING OFF SYSTEM CHARGE

If a leak has occurred in the system, Bard Manufacturing recommends reclaiming, evacuating (see criteria above), and charging to the nameplate charge. If done correctly, topping off the system charge can be done without problems.

With R-410A, there are no significant changes in the refrigerant composition during multiple leaks and recharges. R-410A refrigerant is close to being an azeotropic blend (it behaves like a pure compound or single component refrigerant). The remaining refrigerant charge, in the system, may be used after leaks have occurred and then “top-off” the charge by utilizing the pressure charts on the inner control panel cover as a guideline.

REMEMBER: When adding R-410A refrigerant, it must come out of the charging cylinder/tank as a liquid to avoid any fractionation, and to insure optimal system performance. Refer to instructions for the cylinder that is being utilized for proper method of liquid extraction.

WARNING

Failure to conform to these practices could lead to damage, injury or death.

SAFETY PRACTICES:

1.Never mix R-410A with other refrigerants.

2.Use gloves and safety glasses. Polyol Ester oils can be irritating to the skin, and liquid refrigerant will freeze the skin.

3.Never use air and R-410A to leak check; the mixture may become flammable.

4.Do not inhale R-410A – the vapor attacks the nervous system, creating dizziness, loss of coordination and slurred speech. Cardiac irregularities, unconsciousness and ultimate death can result from breathing this concentration.

5.Do not burn R-410A. This decomposition produces hazardous vapors. Evacuate the area if exposed.

6.Use only cylinders rated DOT4BA/4BW 400.

7.Never fill cylinders over 80% of total capacity.

8.Store cylinders in a cool area, out of direct sunlight.

9.Never heat cylinders above 125°F.

10.Never trap liquid R-410A in manifold sets, gauge lines or cylinders. R-410A expands significantly at warmer temperatures. Once a cylinder or line is full of liquid, any further rise in temperature will cause it to burst.

Manual

2100-522B

Page

27 of 38

Image 27
Contents Models Contents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsTecmodel Nomenclature TECSeries General InformationFactory BUILT-IN Electric Heat Table Electrical Specifications Unit Dimensions Removal of Unit from Skid Shipping DamageUnit Removal from Skid AIR Seal Under Qtec UnitUnit on Appliance Cart Minimum Installation HeightHandling Unit After Removal from Skid GeneralInstallation with Free Blow Plenum Ducted Application Filter Location Duct WorkFilters Supply Duct ConnectionsOptional Rear Drain Kits Service LightFresh AIR Intake Condensate DrainStandard Rear Drain Rear Drain TOP View Optional Side Drain Side View InstallationWall Sleeve Plug Installed If Used MIS-2472 Unit Mounting Installation Instructions Mounting the UnitRemoving Locking Screws from Wheels Operating Voltage Range Wiring Main PowerWiring LOW Voltage Wiring Component LocationLOW Voltage Connections For DDC Control LOW Voltage ConnectionsWall Thermostats Thermostat Predominant FeaturesThermostat Option Remote Thermostat Wiring DiagramThermostat Option Unit Mounted Thermostat Wiring Diagram Thermostat Option8403-060 Plug #2 Orange Purple Brown/White Yellow Blue Red Red/White Black Black/White Yellow Brown Safety Practices Start UPTopping OFF System Charge Description of Standard Equipment Important Installer NotePhase Monitor Three Phase Scroll Compressor Start UP InformationCompressor Control Module Service HintsMist Eliminator Service Vent OptionsEconomizer or Commercial Room Option Tecenergy Recovery VentilatorFresh AIR Damper Removal Qerv Removal CO2 Controller Factory SET to PPM Pressure Service PortsSequence of Operation Optional Climate Controls Sequence of OperationDon’t Troubleshooting GE ECM MotorsReplacing ECM Control Module Troubleshooting GE ECM Motors CONT’DRefrigerant Charge FAN Blade Setting DimensionsFAN Blade Setting FAN Blade DimensionsModel Temp Pressure Cooling Pressure ALL Temperatures in Degrees F

Q48A1, Q24A1, Q60A1, Q42A1, Q36A1 specifications

The Bard Q60A1, Q48A1, Q30A1, Q36A1, and Q42A1 are innovative medical devices designed for versatile applications in various healthcare settings. These models are known for their adaptability, precision, and advanced technologies, making them essential tools for healthcare professionals.

The Q60A1 model stands out due to its user-friendly interface and high-resolution display. It is equipped with advanced sensors that provide real-time monitoring and feedback. The device's portability allows it to be easily moved between different areas of a facility, making it ideal for both inpatient and outpatient services. The Q60A1 also integrates seamlessly with electronic health records, enabling better data management and streamlined clinical workflows.

The Q48A1 model emphasizes flexibility and customization. With multiple configurations, this device is adept at accommodating a range of medical procedures. Its modular design allows healthcare providers to adjust the setup to meet their specific needs, enhancing both efficiency and patient comfort. The Q48A1 is favored for its rapid setup time, facilitating quick responses in critical situations.

In contrast, the Q30A1 prioritizes compactness without sacrificing functionality. This device is specifically engineered for smaller spaces, making it a perfect fit for clinics and smaller hospitals. Despite its size, the Q30A1 boasts a robust set of features, including wireless connectivity and the ability to store a significant amount of patient data. Its intuitive controls simplify operation, even for those with minimal training.

The Q36A1 model is notable for its durability and resilience in challenging environments. Constructed with high-grade materials, it withstands wear and tear while maintaining precise performance. The Q36A1 also includes advanced safety features, such as automatic shut-off mechanisms, which ensure safe operation in emergency conditions. Its reliability makes it a trusted choice across various healthcare sectors.

Lastly, the Q42A1 model focuses on user experience, combining technology with ease of use. It is equipped with voice-activated controls and touch-sensitive displays, streamlining interaction for medical staff. This model also features advanced data analytics tools, providing insights that can drive improvements in patient care.

Overall, the Bard Q60A1, Q48A1, Q30A1, Q36A1, and Q42A1 reflect the latest advancements in medical technology, each serving unique functions suited to different healthcare needs. These devices not only enhance operational efficiency but also improve patient outcomes through better monitoring and data management capabilities.