Siemens SITRANS RD100 operating instructions Optional Panel Mounting Kit, Instructions

Page 7

Optional Panel Mounting Kit

mounting bracket

self tapping

screw

washers

panel

mounting plate

RD100

Notes

The optional panel mounting kit does not provide a NEMA 4X seal to panel.

Mounting brackets require 20 mm (0.8") clearance on either the top or the side of the meter for installation.

Allowable panel thickness: 1.5 mm - 3.2 mm (0.060" - 0.125")

Mounting plate dimensions: 163.3 mm x 102.9 mm x 3.2 mm (6.43" x 4.05" x 0.125")

Panel cutout required:

138.4 mm x 77.5 mm (5.45" x 3.05")

Instructions

1.Insert the RD100 through the mounting plate.

2.Mount the complete assembly on the panel.

3.Secure with 4 brackets and 4 screws (supplied) at the corners of the meter. Use washers as needed to allow for panel thickness.

7ML19985JU01

SITRANS RD100 – INSTRUCTION MANUAL

Page 5

Image 7
Contents Page Contact Smpi Technical Publications Sitrans RD100 Loop Powered Meter Specifications Conversion Rate CalibrationCalibration Range AccuracyMounting DimensionsWall Mounting Instructions Optional Panel Mounting KitControl loop connected to input signal PCB Calibrator connected to input signal PCBConnections DP1 DP2 DP3 Calibrator connected to display PCBDecimal point selection SetupInstallation Calibration connectionsServicing display PCB outside the loop Loop connectionsRemoving display PCB from the loop Restoring display PCB to the loop7ml19985JU01