IBM manual Installing a 2104 Model DU3

Page 17

Installing a 2104 Model DU3

Important

The installation of this product is a customer responsibility.

Attention:

Before continuing with any of the actions described in this book, please refer to Appendix B, “Translated Safety Notices”, on page 63.

These instructions describe how to:

vInstall a 2104 Model DU3 into an RS/6000or IBMERserver pSeries rack (system rack or expansion rack)

vConnect the 2104 Model DU3 to a power source

vConnect the 2104 Model DU3 to the using system

vSwitch on and test the installation

The instructions assume that:

vThe rack has already been set up

vA stabilizer has been correctly attached to the bottom front of the rack to prevent the rack from tipping forward while the 2104 Model DU3 is being installed into the rack. (If necessary, see the Installation and Service Guide, or equivalent, for the rack.)

vYou have access to:

Preinstallation planning information for the system

2104 configuration information

If the 2104 Model DU3 has already been installed in the rack:

vGo to “Connecting the 2104 Model DU3 to the Power Source” on page 29 if the power cables for the 2104 have not been installed.

vGo to “Connecting the 2104 to the Using System” on page 31 if the power cables for the 2104 have been installed.

Notes:

1.Each rack-mounted 2104 requires an airflow of 1.1 m³ per minute (40 ft³ per minute). When racks containing many 2104s are to be installed together, the following requirements must be met to ensure that the 2104s are adequately cooled:

vThe airflow enters at the front of the rack and leaves at the back. To prevent the air that is leaving the rack from entering the intake of another piece of equipment, racks should be positioned in alternate rows, back-to-back and front-to-front.

vThe front of racks should be positioned on floor-tile seams, with a full line of perforated tiles immediately in front of the racks. Each perforated tile should have an air flow of at least 11.34 m³ per minute (400 ft³ per minute). The underfloor temperature must not exceed 15°C (60°F).

vWhere racks are in rows front-to-front or back-to-back, there should be a gap of at least 1220 mm (48 in) separating the rows.

vTo ensure correct air flow within each rack, the rack filler plates must be installed in unused positions. Also, all the gaps in the front of the racks must be sealed, including the gaps between the 2104s.

1

Image 17
Contents Model DU3 Installation Guide Page Model DU3 Installation Guide Fourth Edition June Contents Appendix B. Translated Safety Notices Korean Government Ministry of Communication MOC Statement Federal Communications Commission FCC StatementNew Zealand Compliance Statement International Electrotechnical Commission IEC StatementIndustry Canada Compliance Statement Avis de conformité à la réglementation d’Industrie CanadaUnited Kingdom Telecommunications Requirements European Union EU StatementTaiwan Class a Compliance Statement Viii 2104 Model DU3 Installation Guide Safety Notice for Installing, Relocating, or Servicing Definitions of Safety NoticesModel DU3 Installation Guide Electrostatic Discharge ESD Xii 2104 Model DU3 Installation Guide Trademarks Numbering ConventionRelated Publications Xiv 2104 Model DU3 Installation Guide Installing a 2104 Model DU3 Recommended operating temperature is 22C 72F or lower Installing a 2104 Model DU3 into a Rack Refer to Figure Checking the Items for a 2104 Model DU3Preparing the Rack System or Expansion Installing the Support Rails Removing the Disk Drive Modules and Dummy Disk Drive Modules Opening the Handle of a Disk Drive Module Removing a Disk Drive Module Disk Drive Module on its Side for Safe Storage Removing a Dummy Disk Drive Module Installing the 2104 Model DU3 into the Rack Install the two front mounting screws 1 and tighten them Installing the Back Mounting Screws Reinstalling a Disk Drive Module Closing the Handle of a Disk Drive Module Go to Connecting the 2104 Model DU3 to the Power Source on Setting the Box ID Setting the Options on the 2104 Model DU3Now look at the option switches. Refer to Figure Using-system software Unscrew the thumbscrew 1 Opening the Lever on the Switch Card Assembly Pull the switch card assembly out from Scsi Modules Reinstall the switch card assembly a. Refer to Figure Closing the Lever on the Switch Card Assembly Tighten the thumbscrew 1 fully Connecting the Power Plugs Connecting the 2104 Model DU3 to the Power SourceCheck Power Supply Switch and Lights Do not USE a POWER-DRIVEN Screwdriver Connecting the 2104 to the Using System32 2104 Model DU3 Installation Guide Checking the Lights Switching On and Testing34 2104 Model DU3 Installation Guide Configuring a 2104 to the using system Scsi Service AidsIdentifying 2104s and Disk Drive Modules LinuxAppropriate Linux utilities to partition your drives Rmdev -l enclosurenumber -d Unconfiguring a 2104 from the using systemValid 2104 Model DU3 Configurations Summary of Valid 2104 Model DU3 Configurations Single-Bus Mode Configurations To connect to the 2104 Model DU3 or 2104 Model TU3 Type 4-Y, feature Installed 44 2104 Model DU3 Installation Guide Scsi adapter of one of these types For Hacmp configurations in standby or mutual takeover mode Dual-Bus Mode Configurations Valid configuration 1 Operating system Type 4-Y, feature 2104s Dual-Bus Mode Two Adapters in One Using System Connected to One Configurations That are Not ValidInterface Cards. This configuration is not valid 3 56 2104 Model DU3 Installation Guide Using System Subsystem Cluster multiprogramming Hacmp Web Support Pages Collecting Errors60 2104 Model DU3 Installation Guide Related Publications 62 2104 Model DU3 Installation Guide Appendix B. Translated Safety Notices 64 2104 Model DU3 Installation Guide Appendix B. Translated Safety Notices 66 2104 Model DU3 Installation Guide Appendix B. Translated Safety Notices 68 2104 Model DU3 Installation Guide Appendix B. Translated Safety Notices 70 2104 Model DU3 Installation Guide Appendix B. Translated Safety Notices 72 2104 Model DU3 Installation Guide Appendix B. Translated Safety Notices 74 2104 Model DU3 Installation Guide Appendix B. Translated Safety Notices 76 2104 Model DU3 Installation Guide Appendix B. Translated Safety Notices 78 2104 Model DU3 Installation Guide Appendix B. Translated Safety Notices 80 2104 Model DU3 Installation Guide Appendix B. Translated Safety Notices 82 2104 Model DU3 Installation Guide Appendix B. Translated Safety Notices 84 2104 Model DU3 Installation Guide Appendix B. Translated Safety Notices 86 2104 Model DU3 Installation Guide Appendix B. Translated Safety Notices 88 2104 Model DU3 Installation Guide Appendix B. Translated Safety Notices 90 2104 Model DU3 Installation Guide Appendix B. Translated Safety Notices 92 2104 Model DU3 Installation Guide Appendix B. Translated Safety Notices 94 2104 Model DU3 Installation Guide Appendix B. Translated Safety Notices 96 2104 Model DU3 Installation Guide Appendix B. Translated Safety Notices Part Number 97P1455