Bard R-410A manual Optional Equipment Roof Hood, Model No Applicable To

Page 7

Optional Equipment — Roof Hood

• Shipped knocked down

Built-in filter

• Polyester baked enamel galvanneal cabinet

• Fresh air damper assembly provides up to 15% outside air.

• Heavy insulation - 1/2 inch

• Requires prefabricated roof curb 9042-003 or 9042-004.

 

 

Order separately.

Model No.

Applicable To

Shipping Weight

 

 

 

 

RHP313-A

2, 2-1/2 and 3 ton models

110

 

RHP513-A

3-1/2, 4 and 5 ton models

120

 

 

 

 

 

† Equivalent units - Shipping

Performance and Application Data — RHP

RHP313-A Ventilation Air

Supply Air

 

 

 

 

 

 

 

 

 

 

 

 

Static

 

 

 

Ventilation Air

(CFM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.00

N/A

N/A

133

183

226

260

 

283

290

304

320

370

 

 

 

 

 

 

 

 

 

 

 

 

 

0.20

N/A

N/A

133

183

226

260

 

283

290

304

N/A

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

0.40

N/A

N/A

133

183

2.26

260

 

283

290

N/A

N/A

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Return Static

0.00

0.05

0.10

0.15

0.20

0.25

 

0.30

0.35

0.40

0.45

0.50

 

 

 

 

 

 

 

 

 

 

 

 

 

RHP513-A BFAD Ventilation Air

Supply Air

 

 

 

Ventilation Air (CFM)

 

 

 

Static

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.00

N/A

N/A

80

165

215

250

280

310

340

370

400

 

 

 

 

 

 

 

 

 

 

 

 

0.20

N/A

N/A

80

165

215

250

280

310

340

370

400

 

 

 

 

 

 

 

 

 

 

 

 

0.40

N/A

N/A

80

165

215

250

280

310

340

370

400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Return Static

0.00

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0.50

 

 

 

 

 

 

 

 

 

 

 

 

D

AIR CONDITIONING UNIT

MIS-2254

38 1/4

X A WIDTH

ROOF HOOD

FILTER

C

FRESH AIR

OPENING

12 1/2"

RETURN AIR

SUPPLY AIR

1 1/2"

 

H

J

Unit Dimensions

Roof Hood

 

Nominal

 

 

 

1"

Model

Model

Tonnage

A

C

D

Filter

 

PA1324 / PH1324

2 Ton

 

 

 

(1) 16 x 16

RHP313-A

PA1330 / PH1330

2½ Ton

38-1/8

26

53-1/4

and

 

PA1336 / PH1336

3 Ton

 

 

 

(1) 16 x 20

 

PA1342 / PH1342

3½ Ton

 

 

 

 

RHP513-A

PA1348 / PH1348

4 Ton

42

33

55-1/4

(2) 16 x 20

 

PA1360 / PH1360

5 Ton

 

 

 

 

Optional Equipment — Pre-Fabricated Roof Curb

Heavy gauge galvanized with wood nailing strip.

Prefabricated roof curb requires roof hood RHP313-A & RHP513-A. Order separately.

Model No.

Applicable To

E.U.†

Shipping Weight

9042-003

2, 2-1/2 and 3 ton models

.80

144

9042-004

3-1/2, 4 and 5 ton models

.80

160

† Equivalent units - Shipping

Heavy gauge galvanized with wood nailing strip, welded/leakproof one piece construction - ready to install.

 

Used With

 

 

 

 

 

 

 

 

 

 

Roof Hood

 

 

 

 

 

 

 

 

Heat Pump and

Model

Model

A

B

C 1

D

E

F

J 1

H 1

Air Conditioning Units

9042-003

RHP313-A

80-3/8

40-1/4

37-1/4

38-3/8

35-3/8

42

14-3/4

19-1/8

All 2, 2-1/2, & 3 Ton Models

(P36 Curb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9042-004

RHP513-A

82-3/8

44-1/8

41-1/8

38-3/8

35-3/8

44

14-3/4

19-1/8

All 3-1/2, 4 & 5 Ton Models

(P60 Curb)

 

 

 

 

 

 

 

 

 

 

1 Duct Sizing Information:

Return air dimension “C” is length / Supply air dimension “C” is length. Return air dimension “H” is width / Supply air dimension “J” is width.

Form No.

S3383-1112

Supersedes

S3383-510

Page

7 of 8

Image 7
Contents Field Installed Accessories Standard Engineered FeaturesCooling Capacities and Efficiency Ratings General SpecificationsIndoor Blower Performance Optional Field Installed Electric Heater through 5 Ton Optional Field Installed Electric Heater Packages Cooling Application Data Outdoor Temperature Top Optional Control Modules Field Installed Unit DimensionsField Installed Part Applicable To Description Model No Applicable To Optional Equipment Roof HoodWHR WVL Optional Equipment Energy Recovery VentilatorVentilation Rate WHR