Bard R-410A manual Cooling Capacities and Efficiency Ratings, General Specifications

Page 2

Cooling Capacities and Efficiency Ratings

MODELS

Phase

BTUH

SEER

PA13242-A

1

23,000

13.00

PA13302-A

1

29,000

13.00

 

 

 

 

PA13362-A, -B

1 and 3

34,000

13.00

PA13422-A, -B, -C

1 and 3

43,000

13.50

PA13482-A, -B, -C

1 and 3

46,500

13.00

 

 

 

 

PA13602-A, -B, -C

1 and 3

56,000

13.00

Tested and Certified in accordance with ARI Standard 210/240-2003.

General Specifications

Model

PA13242-A

PA13302-A

PA13362-A

PA13362-B

PA13422-A

PA13422-B

PA13422-C

PA13482-A

PA13482-B

PA13482-C

PA13602-A

PA13602-B

PA13602-C

Electric Rating –

230/208-60-1

230/208-60-1

230/208-60-1

230/208-60-3

230/208-60-1

230/208-60-3

460-60-3

230/208-60-1

230/208-60-3

460-60-3

230/208-60-1

230/208-60-3

460-60-3

60 Hz – Circuit A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating Voltage Range

197 - 253

197 - 253

197 - 253

187 - 253

197 - 253

187 - 253

414 -506

197 - 253

187 - 253

414 -506

197 - 253

187 - 253

414 -506

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Circuit Ampacity 4

15

18

24

16

33

23

12

33

29

14

39

26

17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BCSC

9

11

15

10

21

15

8

22

14

8

26

16

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Field Wire Size 3

12

10

8

12

10

10

14

8

10

12

8

10

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ground Wire Size

12

10

8

12

10

10

14

8

10

14

8

10

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Delay Fuse – Max. 2

20

25

35

20

50

35

15

50

40

20

60

40

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total unit Amps – 230/208

10.8/11.8

13.3/14.8

16.4/18.4

17.0/13.3

16.2/18.1

14.1/15.4

10.4

23.0/24.7

16.9/18.0

10.7

25.3/28.9

17.7/19.9

11.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor – Circuit A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor Type

Recip.

Recip.

Recip.

Recip.

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Volts

230/208

230/208

230/208

230/208

230/208

230/208

460

230/208

230/208

460

230/208

230/208

460

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated Load Amps

7.5/8.5

9.5/11

12/14

7.6/8.9

11.8/13.7

8.3/9.6

7.7

17/18.7

10.9/12

7.7

19.3/22.9

11.7/13.9

8.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lock Rotor Amps

48/48

57/57

74/74

75/75

115/115

115/115

50

117/117

83.1/83.1

50

134/134

110/110

52

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan Motor and

 

 

 

 

 

 

 

 

 

 

 

 

 

Condenser

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan Motor – HP

1/6 - 825

1/6 - 825

1/6 - 825

1/6 - 825

1/4 - 825

1/4 - 825

1/4 - 825

1/4 - 825

1/4 - 825

1/4 - 825

1/4 - 825

1/4 - 825

1/4 - 825

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan Motor Amps

1.1

1.1

1.1

1.1

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan – Dia./CFM

24"/2700

24"/2600

24"/2600

24"/2600

24"/3400

24"/3400

24"/3400

24"/3400

24"/3400

24"/3400

24"/3400

24"/3400

24"/3400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor and Evaporator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blower Motor – HP 1

1/3 - ECM

1/2 - ECM

1/2 - ECM

1/2 - ECM

1/2 - ECM

1/2 - ECM

1/2 - ECM

3/4 - ECM

3/4 - ECM

3/4 - ECM

3/4 - ECM

3/4 - ECM

3/4 - ECM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blower Motor – Amps

2.2

2.7

3.3

3.3

3.9

3.9

3.9

4.5

4.5

4.5

5.0

5.0

5.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Charge (R-410 oz.)

75

85

120

120

160

160

160

160

160

160

160

160

160

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shipping Weight (pounds)

360

410

410

410

440

440

490

440

440

490

450

450

500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1ECM = Electronically Commutated Motor

2Maximum time delay fuse or HACR type circuit breaker for protection of field wiring devices.

3Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.

4These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to National Electric Code (latest revision), Article 310 for power conductor sizing.

Indoor Blower Performance 1

 

 

 

2

3

4

MODEL

Rated

MAX

Continuous

Rated

Rated

ESP

ESP

Airflow

Cooling

Electric Heat

 

 

 

 

 

CFM

CFM

PA1324

0.10

0.50

600

800

1000

PA1330

0.15

0.50

750

1000

1000

 

 

 

 

 

 

PA1336

0.15

0.50

825

1100

1100

PA1342

0.20

0.50

925

1400

1400

PA1348

0.20

0.50

1025

1550

1750

 

 

 

 

 

 

PA1360

0.20

0.50

1150

1750

1750

1Motor will deliver consistent CFM through voltage supply range with no deterioration (197-253V for all 230/208V models).

2 Continuous CFM is the total air being circulated during continuous (manual fan) mode. 3 Will occur automatically with a call for “Y” for cooling mode operation.

4 Will occur automatically with a call for “W1” for heating mode operation.

Form No.

S3383-1112

Supersedes

S3383-510

Page

2 of 8

Image 2
Contents Standard Engineered Features Field Installed AccessoriesIndoor Blower Performance General SpecificationsCooling Capacities and Efficiency Ratings Optional Field Installed Electric Heater Packages Optional Field Installed Electric Heater through 5 TonCooling Application Data Outdoor Temperature Top Field Installed Part Applicable To Description Unit DimensionsOptional Control Modules Field Installed Optional Equipment Roof Hood Model No Applicable ToWHR Optional Equipment Energy Recovery VentilatorVentilation Rate WHR WVL
Related manuals