Cooling Capacities and Efficiency Ratings
MODELS | Phase | BTUH | SEER |
1 | 23,000 | 13.00 | |
1 | 29,000 | 13.00 | |
|
|
|
|
1 and 3 | 34,000 | 13.00 | |
1 and 3 | 43,000 | 13.50 | |
1 and 3 | 46,500 | 13.00 | |
|
|
|
|
1 and 3 | 56,000 | 13.00 |
Tested and Certified in accordance with ARI Standard
General Specifications
Model | ||||||||||||||
Electric Rating – | ||||||||||||||
60 Hz – Circuit A | ||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Operating Voltage Range | 197 - 253 | 197 - 253 | 197 - 253 | 187 - 253 | 197 - 253 | 187 - 253 | 414 | 197 - 253 | 187 - 253 | 414 | 197 - 253 | 187 - 253 | 414 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Minimum Circuit Ampacity 4 | 15 | 18 | 24 | 16 | 33 | 23 | 12 | 33 | 29 | 14 | 39 | 26 | 17 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
BCSC | 9 | 11 | 15 | 10 | 21 | 15 | 8 | 22 | 14 | 8 | 26 | 16 | 9 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Field Wire Size 3 | 12 | 10 | 8 | 12 | 10 | 10 | 14 | 8 | 10 | 12 | 8 | 10 | 10 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Ground Wire Size | 12 | 10 | 8 | 12 | 10 | 10 | 14 | 8 | 10 | 14 | 8 | 10 | 12 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Delay Fuse – Max. 2 | 20 | 25 | 35 | 20 | 50 | 35 | 15 | 50 | 40 | 20 | 60 | 40 | 25 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Total unit Amps – 230/208 | 10.8/11.8 | 13.3/14.8 | 16.4/18.4 | 17.0/13.3 | 16.2/18.1 | 14.1/15.4 | 10.4 | 23.0/24.7 | 16.9/18.0 | 10.7 | 25.3/28.9 | 17.7/19.9 | 11.9 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Compressor – Circuit A |
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Compressor Type | Recip. | Recip. | Recip. | Recip. | Scroll | Scroll | Scroll | Scroll | Scroll | Scroll | Scroll | Scroll | Scroll | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Volts | 230/208 | 230/208 | 230/208 | 230/208 | 230/208 | 230/208 | 460 | 230/208 | 230/208 | 460 | 230/208 | 230/208 | 460 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Rated Load Amps | 7.5/8.5 | 9.5/11 | 12/14 | 7.6/8.9 | 11.8/13.7 | 8.3/9.6 | 7.7 | 17/18.7 | 10.9/12 | 7.7 | 19.3/22.9 | 11.7/13.9 | 8.6 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Lock Rotor Amps | 48/48 | 57/57 | 74/74 | 75/75 | 115/115 | 115/115 | 50 | 117/117 | 83.1/83.1 | 50 | 134/134 | 110/110 | 52 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Fan Motor and |
|
|
|
|
|
|
|
|
|
|
|
|
| |
Condenser |
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Fan Motor – HP | 1/6 - 825 | 1/6 - 825 | 1/6 - 825 | 1/6 - 825 | 1/4 - 825 | 1/4 - 825 | 1/4 - 825 | 1/4 - 825 | 1/4 - 825 | 1/4 - 825 | 1/4 - 825 | 1/4 - 825 | 1/4 - 825 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Fan Motor Amps | 1.1 | 1.1 | 1.1 | 1.1 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Fan – Dia./CFM | 24"/2700 | 24"/2600 | 24"/2600 | 24"/2600 | 24"/3400 | 24"/3400 | 24"/3400 | 24"/3400 | 24"/3400 | 24"/3400 | 24"/3400 | 24"/3400 | 24"/3400 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Motor and Evaporator |
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Blower Motor – HP 1 | 1/3 - ECM | 1/2 - ECM | 1/2 - ECM | 1/2 - ECM | 1/2 - ECM | 1/2 - ECM | 1/2 - ECM | 3/4 - ECM | 3/4 - ECM | 3/4 - ECM | 3/4 - ECM | 3/4 - ECM | 3/4 - ECM | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Blower Motor – Amps | 2.2 | 2.7 | 3.3 | 3.3 | 3.9 | 3.9 | 3.9 | 4.5 | 4.5 | 4.5 | 5.0 | 5.0 | 5.0 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Charge | 75 | 85 | 120 | 120 | 160 | 160 | 160 | 160 | 160 | 160 | 160 | 160 | 160 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Shipping Weight (pounds) | 360 | 410 | 410 | 410 | 440 | 440 | 490 | 440 | 440 | 490 | 450 | 450 | 500 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1ECM = Electronically Commutated Motor
2Maximum time delay fuse or HACR type circuit breaker for protection of field wiring devices.
3Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
4These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to National Electric Code (latest revision), Article 310 for power conductor sizing.
Indoor Blower Performance 1
|
|
| 2 | 3 | 4 | |
MODEL | Rated | MAX | Continuous | Rated | Rated | |
ESP | ESP | Airflow | Cooling | Electric Heat | ||
| ||||||
|
|
|
| CFM | CFM | |
PA1324 | 0.10 | 0.50 | 600 | 800 | 1000 | |
PA1330 | 0.15 | 0.50 | 750 | 1000 | 1000 | |
|
|
|
|
|
| |
PA1336 | 0.15 | 0.50 | 825 | 1100 | 1100 | |
PA1342 | 0.20 | 0.50 | 925 | 1400 | 1400 | |
PA1348 | 0.20 | 0.50 | 1025 | 1550 | 1750 | |
|
|
|
|
|
| |
PA1360 | 0.20 | 0.50 | 1150 | 1750 | 1750 |
1Motor will deliver consistent CFM through voltage supply range with no deterioration
2 Continuous CFM is the total air being circulated during continuous (manual fan) mode. 3 Will occur automatically with a call for “Y” for cooling mode operation.
4 Will occur automatically with a call for “W1” for heating mode operation.
Form No. | |
Supersedes | |
Page | 2 of 8 |