Page | Supersedes | Form No. |
4 of 8 |
Cooling Application Data — Outdoor Temperature 1
|
| Cooling |
|
|
|
|
| Outdoor Temperature°F |
|
|
|
|
| ||||
Model | D.B./W.B.2 | Capacity | 55°F | 60°F | 65°F | 70°F | 75°F | 80°F | 85°F | 90°F | 95°F | 100°F | 105°F | 110°F | 115°F | 120°F | |
| 75/62 | Total Cooling | 30,100 | 29,000 | 27,900 | 26,750 | 25,650 | 24,550 | 23,500 | 22,400 | 21,300 | 20,100 | 18,850 | 17,650 | 16,450 | 15,200 | |
| Sensible Cooling | 20,600 | 20,100 | 19,700 | 19,250 | 18,800 | 18,400 | 17,950 | 17,500 | 17,100 | 16,650 | 16,200 | 15,750 | 15,250 | 14,800 | ||
|
| ||||||||||||||||
PA1324 | 80/67 | Total Cooling | 31,900 | 30,750 | 29,650 | 28,500 | 27,400 | 26,300 | 25,200 | 24,100 | 23,000 | 21,800 | 20,600 | 19,400 | 18,200 | 17,000 | |
Sensible Cooling | 20,750 | 20,250 | 19,800 | 19,300 | 18,800 | 18,300 | 17,750 | 17,250 | 16,700 | 16,350 | 15,000 | 15,700 | 15,350 | 15,000 | |||
|
| ||||||||||||||||
| 85/72 | Total Cooling | 35,600 | 34,350 | 33,150 | 31,950 | 30,750 | 29,600 | 28,450 | 27,300 | 26,150 | 24,650 | 23,200 | 21,750 | 20,250 | 18,800 | |
| Sensible Cooling | 20,900 | 20,450 | 19,950 | 19,500 | 19,000 | 18,500 | 18,000 | 17,500 | 16,950 | 16,600 | 16,300 | 15,950 | 15,600 | 15,250 | ||
|
| ||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 75/62 | Total Cooling | 38,150 | 36,700 | 35,300 | 33,900 | 32,500 | 31,100 | 29,700 | 28,300 | 26,850 | 25,450 | 24,000 | 22,550 | 21,100 | 19,700 | |
| Sensible Cooling | 27,050 | 26,450 | 25,850 | 25,250 | 24,600 | 24,050 | 23,450 | 22,900 | 22,300 | 21,600 | 20,850 | 20,150 | 19,400 | 18,700 | ||
|
| ||||||||||||||||
PA1330 | 80/67 | Total Cooling | 40,400 | 38,950 | 37,550 | 36,100 | 34,700 | 33,300 | 31,850 | 30,450 | 29,000 | 27,600 | 26,200 | 24,800 | 23,400 | 22,000 | |
Sensible Cooling | 27,300 | 26,650 | 25,950 | 25,300 | 24,600 | 23,900 | 23,200 | 22,500 | 21,800 | 21,200 | 20,650 | 20,050 | 19,500 | 18,900 | |||
|
| ||||||||||||||||
| 85/72 | Total Cooling | 45,050 | 43,550 | 42,000 | 40,450 | 38,900 | 37,400 | 35,950 | 34,450 | 32,950 | 31,200 | 29,500 | 27,750 | 26,050 | 24,300 | |
| Sensible Cooling | 27,500 | 26,850 | 26,200 | 25,550 | 24,850 | 24,200 | 23,500 | 22,800 | 22,150 | 21,550 | 20,950 | 20,400 | 19,800 | 19,200 | ||
|
| ||||||||||||||||
| 75/62 | Total Cooling | 43,200 | 41,700 | 40,200 | 38,700 | 37,150 | 35,750 | 34,350 | 32,900 | 31,500 | 29,600 | 27,750 | 25,850 | 23,950 | 22,100 | |
| Sensible Cooling | 48,150 | 45,450 | 42,800 | 40,100 | 37,450 | 34,350 | 31,250 | 28,150 | 25,050 | 24,050 | 23,000 | 21,950 | 20,900 | 19,850 | ||
|
| ||||||||||||||||
PA1336 | 80/67 | Total Cooling | 45,750 | 44,250 | 42,700 | 41,200 | 39,700 | 38,300 | 36,850 | 35,450 | 34,000 | 32,150 | 30,300 | 28,400 | 26,550 | 24,700 | |
Sensible Cooling | 48,400 | 45,650 | 42,900 | 40,150 | 37,400 | 34,200 | 30,950 | 27,750 | 24,500 | 23,600 | 22,750 | 21,850 | 21,000 | 20,100 | |||
|
| ||||||||||||||||
| 85/72 | Total Cooling | 51,050 | 49,400 | 47,800 | 46,150 | 44,500 | 43,050 | 41,550 | 40,100 | 38,600 | 36,350 | 34,100 | 31,850 | 29,550 | 27,300 | |
| Sensible Cooling | 48,850 | 46,100 | 43,350 | 40,550 | 37,800 | 34,600 | 31,350 | 28,100 | 24,900 | 24,000 | 23,100 | 22,200 | 21,300 | 20,400 | ||
|
| ||||||||||||||||
| 75/62 | Total Cooling | 54,250 | 52,450 | 50,650 | 48,900 | 47,100 | 45,300 | 43,450 | 41,650 | 39,850 | 38,150 | 36,450 | 34,750 | 33,100 | 31,400 | |
| Sensible Cooling | 39,500 | 38,700 | 37,950 | 37,150 | 36,400 | 35,650 | 34,950 | 34,250 | 33,550 | 32,500 | 31,400 | 30,300 | 29,250 | 28,150 | ||
|
| ||||||||||||||||
PA1342 | 80/67 | Total Cooling | 57,400 | 55,650 | 53,850 | 52,100 | 50,300 | 48,500 | 46,650 | 44,850 | 43,000 | 41,400 | 39,850 | 38,250 | 36,700 | 35,100 | |
Sensible Cooling | 39,900 | 39,000 | 38,100 | 37,250 | 36,350 | 35,450 | 34,600 | 33,700 | 32,800 | 31,950 | 31,100 | 30,200 | 29,350 | 28,500 | |||
|
| ||||||||||||||||
| 85/72 | Total Cooling | 64,050 | 62,150 | 60,250 | 58,300 | 56,400 | 54,500 | 52,650 | 50,750 | 48,850 | 46,850 | 44,850 | 42,850 | 40,800 | 38,800 | |
| Sensible Cooling | 40,200 | 39,350 | 38,450 | 37,600 | 36,750 | 35,900 | 35,050 | 34,150 | 33,300 | 32,450 | 31,550 | 30,700 | 29,800 | 28,950 | ||
|
| ||||||||||||||||
| 75/62 | Total Cooling | 57,550 | 55,700 | 53,900 | 52,050 | 50,250 | 48,452 | 46,650 | 44,850 | 43,100 | 41,100 | 39,100 | 37,150 | 35,150 | 33,200 | |
| Sensible Cooling | 42,200 | 41,300 | 40,400 | 39,500 | 38,600 | 37,700 | 36,850 | 35,950 | 35,100 | 34,050 | 33,050 | 32,000 | 30,950 | 29,950 | ||
|
| ||||||||||||||||
PA1348 | 80/67 | Total Cooling | 60,850 | 59,050 | 57,250 | 55,450 | 53,650 | 51,850 | 50,100 | 48,300 | 46,500 | 44,600 | 42,750 | 40,850 | 39,000 | 37,100 | |
Sensible Cooling | 42,600 | 41,600 | 40,550 | 39,550 | 38,550 | 37,500 | 36,450 | 35,350 | 34,300 | 33,500 | 32,700 | 31,900 | 31,100 | 30,300 | |||
|
| ||||||||||||||||
| 85/72 | Total Cooling | 67,900 | 66,000 | 64,050 | 62,100 | 60,150 | 58,350 | 56,500 | 54,650 | 52,800 | 50,450 | 48,100 | 45,750 | 43,400 | 41,000 | |
| Sensible Cooling | 42,950 | 41,950 | 40,950 | 39,950 | 38,950 | 37,950 | 36,900 | 35,850 | 34,850 | 34,026 | 33,200 | 32,400 | 31,600 | 30,800 | ||
|
| ||||||||||||||||
| 75/62 | Total Cooling | 66,400 | 64,550 | 62,700 | 60,900 | 59,050 | 57,350 | 55,700 | 54,000 | 52,350 | 49,800 | 47,300 | 44,750 | 42,250 | 39,700 | |
| Sensible Cooling | 46,950 | 46,250 | 45,550 | 44,850 | 44,200 | 43,850 | 43,550 | 43,250 | 42,900 | 40,750 | 38,550 | 36,350 | 34,200 | 32,000 | ||
|
| ||||||||||||||||
PA1360 | 80/67 | Total Cooling | 70,250 | 68,450 | 66,650 | 64,850 | 63,050 | 61,400 | 59,800 | 58,150 | 56,000 | 54,100 | 51,650 | 49,250 | 46,800 | 44,400 | |
Sensible Cooling | 47,450 | 46,600 | 45,800 | 44,950 | 44,150 | 43,600 | 43,050 | 42,500 | 41,950 | 40,050 | 38,150 | 36,200 | 34,300 | 32,400 | |||
|
| ||||||||||||||||
| 85/72 | Total Cooling | 78,350 | 76,450 | 74,500 | 72,600 | 70,700 | 69,050 | 67,450 | 65,800 | 64,200 | 61,200 | 58,150 | 55,150 | 52,100 | 49,100 | |
| Sensible Cooling | 47,800 | 47,000 | 46,200 | 45,450 | 44,650 | 44,100 | 43,600 | 43,100 | 42,600 | 40,650 | 38,700 | 36,800 | 34,850 | 32,900 | ||
|
| ||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1Below 55°F, unit requires a field installed low ambient control model
2 Return air temperature °F.