Clearance Requirements

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Environmental

The UltraNet Edge 3000 requires an environment that is within the

 

 

Specifications

specifications listed in Table A-3.

 

Table A-3Environmental Specifications

Environmental

Specification

 

Parameter

 

 

 

 

Operation

Ambient Temperature (°F)

40°–104°

Environment

Ambient Temperature (°C)

5°–40°

 

Relative Humidity

5%–80% (non-condensing)

 

 

 

Heat Generated

BTU/hour

844

 

Kgram Cal./hour

211

 

 

 

Air Flow

CFM (Cubic Feet/Minute)

40

 

Liters/second

19

 

 

 

Electromagnetic

United States

FCC Class A

Emissions

Canadian

Class A Digital Apparatus, CAN/CSA-CISPR 22-96

 

Japan

VCCI Class A

 

Australia/New Zealand

AS/NZS 3548 Class A

 

European Communities

CISPR 22, EN 55022, Class A

 

 

 

Electromagnetic

European Communities

EN55024:1998 for Electromagnetic Immunity in an IT

Immunity

 

Environment.

 

 

Limits for Harmonic Current Emissions (equipment input

 

 

current <16 A per phase) or equivalent (mandatory starting

 

 

January 1, 2001).

 

 

Limitation of Voltage Fluctuations and Flicker in Low

 

 

Voltage Supply Systems for Equipment with Rated Current

 

 

<16 A (mandatory starting January 1, 2001).

Safety

United States

Information Technology Equipment, including Electrical

 

 

Business Equipment: UL1950, Third Edition.

 

 

Eye Safety for Lasers Class 1: FDA,21 CFR 1040.10.

 

 

 

 

Canada

Information Technology Equipment, including Electrical

 

 

Business Equipment: CAN/CSA-C22.2 No. 950-95, Third

 

 

Edition.

 

 

CE- Information Technology Equipment, including

 

 

Electrical Business Equipment: IEC 60950, A4, A11 or EN

 

 

60950, A4, A11 or equivalent.

 

 

Eye Safety for Lasers Class 1: EN60825-1 or equivalent.

 

 

 

A-3

Page 345
Image 345
McDATA manual Environmental, Specifications, UltraNet Edge 3000 requires an environment that is within