Problem | Possible Cause | Action |
| Overload inoperative. Opens too | Check operation of unit. Replace overload if |
| soon | system operation is satisfactory |
| Compressor restarted before | Allow a minimum of 2 minutes to allow |
| pressures to equalize before attempting to | |
| system pressures equalized | |
| restart. Instruct customer of waiting period | |
|
| |
|
| Check voltage with unit operating. Check for |
Compressor runs | Low or fl uctuating voltage | other appliances on circuit. Air conditioner |
for short periods |
| should be in separate circuit for proper voltage |
only. Cycles on |
| & fused separately |
overload | Incorrect wiring | Refer to appropriate wiring diagram |
| Shorted or incorrect capacitor | Check by substituting a known good capacitor |
| of correct rating | |
|
| |
| Restricted or low air fl ow through | Check for proper fan speed or blocked |
| condenser coil | condenser |
| Compressor running abnormally | Check for kinked discharge line or restricted |
| hot | condenser. Check amperage |
Problem | Possible Cause | Action | |
| Loss of charge in | Place jumper across | |
unit operates. If unit operates, replace | |||
| |||
turn unit on | Loose or broken parts in | Check as above | |
| Incorrect wiring | Refer to appropriate wiring diagram |
Problem | Possible Cause | Action | |
| Poorly installed | Refer to Installation Manual for proper | |
| installation | ||
|
| ||
| Fan blade striking chassis | Reposition - adjust motor mount | |
Noisy operation |
| Check that compressor grommets have not | |
Compressor vibrating | deteriorated. Check that compressor mounting | ||
| |||
|
| parts are not missing | |
| Improperly mounted or loose | Check assembly & parts for looseness, | |
| cabinet parts | rubbing & rattling |
Problem | Possible Cause | Action |
| Evaporator drain pan overfl owing | Clean obstructed drain trough |
| Condensation forming on base pan | Evaporator drain pan broken or cracked. |
| Reseal or replace | |
| Poor installation resulting in rain | Check installation instructions. Reseal as |
Water leaks into | entering the room | required |
the room | Condensation on discharge grille | Clean the dirty evaporator coil. Use pressure |
| louvers | wash or biodegradable cleaning agent to clean |
| Chassis gasket not installed | Install gasket, per Installation manual |
| Downward slope of unit is too | Refer to installation manual for proper |
| steep | installation |
18