Friedrich RAC-SVC-06 service manual Problem Possible Cause Action

Page 19

Problem

Possible Cause

Action

 

Sublimation:

Ensure that foam gaskets are installed in

 

When unconditioned saturated,

between window panes & in between the

 

outside air mixes with conditioned

unit & the sleeve. Also, ensure that fresh

 

air, condensation forms on the

air/exhaust vents (on applicable models) are in

Water "spitting"

cooler surfaces

the closed position & are in tact

into room

Downward pitch of installation is

Follow installation instructions to ensure that

 

downward pitch of installed unit is no less than

 

too steep

 

1/4" & no more than 3/8"

 

 

 

Restricted coil or dirty fi lter

Clean & advise customer of periodic cleaning

 

& maintenance needs of entire unit

 

 

Problem

Possible Cause

Action

 

Insuffi cient air circulation thru area

Adjust louvers for best possible air circulation

 

to be air conditioned

 

 

Excessive moisture

Oversized unit

Operate in "MoneySaver" position

Inadequate vapor barrier in

 

 

 

 

building structure, particularly

Advise customer

 

fl oors

 

Problem

Possible Cause

Action

 

T-stat differential too narrow

Replace t-stat

 

Plenum gasket not sealing,

Check gasket. Reposition or replace as

T-stat short cycles

allowing discharge air to short

needed

cycle t-stat

 

Restricted coil or dirty fi lter

Clean & advise customer of periodic cleaning

 

& maintenance needs of entire unit

 

 

Problem

Possible Cause

Action

 

Anticipator (resistor) wire

Refer to appropriate wiring diagram

 

disconnected at t-stat or system

 

switch

 

Prolonged off

 

Disconnect plus from outlet. Remove resistor

Anticipator (resistor) shorted or

from bracket. Insert plug & depress "COOL"

cycles (automatic

& "FAN AUTOMATIC" buttons. Place t-stat to

operation)

open

warmest setting. Feel resistor for temperature.

 

 

 

 

If no heat, replace resistor

 

Partial loss of charge in t-stat bulb

Replace t-stat

 

causing a wide differential

 

 

Problem

Possible Cause

Action

 

Evaporator drain pan cracked or

Repair, clean or replace as required

 

obstructed

 

 

 

Water in compressor area

Detach shroud from pan & coil. Clean &

Outside water

remove old sealer. Reseal, reinstall & check

 

leaks

Obstructed condenser coil

Use pressure wash or biodegradable cleaning

 

agent to clean

 

 

 

Fan blade/slinger ring improperly

Adjust fan blade to 1/2" of condenser coil

 

positioned

 

 

19

Image 19
Contents 2006 Introduction Table of ContentsRoom AIR Conditioners Limited Warranty Routine Maintenance Unit Identification 08 L 1Chassis Performance DataReceptacle Electrical DataElectronic Controls Functional Component DefinitionsTesting the Electronic Control Error Code Listings Testing the Electronic Control XQ/WS Boards & QME BoardsSealed Refrigeration System Repairs Refrigeration System Sequence of OperationEquipment Required Hermetic Component ReplacementSpecialprocedureinthecaseofcompressor Motor Burnout Rotarycompressorspecialtroubleshooting and ServiceMethod of Charging Refrigerant ChargingOvercharged Refrigerant Systems Undercharged Refrigerant SystemsRestricted Refrigerant System Malfunction of Valve Normal Function of ValveProblem Possible Cause Action Cooling only Room AIR Conditioners Troubleshooting TipsReplace fuse, reset breaker. If repeats, check Problem Possible Cause Action Problem Possible Cause Action Heat / Cool Room AIR Conditioners Troubleshooting Tips Refrigerant System Diagnosis Heating Troubleshooting Chart CoolingYES Troubleshooting Chart HeatingElectrical Troubleshooting Chart Heat Pump System Cools When Heating is DesiredModel Models RM18L30-A, KM18L30-A, KM21L30-A, RM24L30-A, KM24L30-A SS16L30-A/B, SM18L30-A/B, SM21L30-A/B, SM24L30-A/B SL36L30-A SL28L30-A SL36L30-B EQ08L11-A ES12L33-A, ES16L33-A, EM18L34-A, EM24L35-A EL36L35-A YS09L10-A, YS09L10-B YS13L33-A, YM18L34-A YL24L35-A RAC-Svc-06