Friedrich RAC-SVC-06 Troubleshooting Chart Cooling, Refrigerant System Diagnosis Heating

Page 21

Problem

Possible Cause

Action

 

Incorrect wiring

Refer to applicable wiring diagram

 

Defective solenoid coil

Check for continuity of coil

Unit cools when

 

Block condenser coil & switch unit to cooling.

 

Allow pressure to build up in system, then

heat is called for

Reversing valve fails to shift

switch to heating. If valve fails to shift, replace

 

 

 

 

valve.

 

Inoperative system switch

Check for continuity of system switch

Problem

Possible Cause

Action

 

Heating capillary tube partially

Check for partially starved outer coil. Replace

 

restricted

heating capillary tube

 

 

Switch unit several times from heating to

Cooling adequate,

Check valve leaking internally

cooling. Check temperature rise across

coil. Refer to specifi cation sheet for correct

but heating

 

 

temperature rise

insuffi cient

 

 

De-energize solenoid coil, raise head

 

 

 

Reversing valve failing to shift

pressure, energize solenoid to break loose.

 

completely; bypassing hot gas

If valve fails to make complete shift, replace

 

 

valve.

TROUBLESHOOTING CHART — COOLING

REFRIGERANT SYSTEM DIAGNOSIS – HEATING

Low Suction Pressure

High Suction Pressure

Low Head Pressure

High Head Pressure

Low Load Conditions

High Load Conditions

Low Load Conditions

High Load Conditions

Low Air Flow Across

High Air Flow Across

Refrigerant System

Low Air Flow Across

Indoor Coil

Indoor Coil

Restriction

Outdoor Coil

Refrigerant System

Reversing Valve not

Reversing Valve not

Overcharged

Restriction

Fully Seated

Fully Seated

 

Undercharged

Overcharged

Undercharged

Noncondensables (air)

in System

 

 

 

Moisture in System

Defective Compressor

Defective Compressor

 

21

Image 21
Contents 2006 Introduction Table of ContentsRoom AIR Conditioners Limited Warranty Routine Maintenance Unit Identification 08 L 1Chassis Performance DataReceptacle Electrical DataElectronic Controls Functional Component DefinitionsTesting the Electronic Control Error Code Listings Testing the Electronic Control XQ/WS Boards & QME BoardsSealed Refrigeration System Repairs Refrigeration System Sequence of OperationSpecialprocedureinthecaseofcompressor Motor Burnout Hermetic Component ReplacementRotarycompressorspecialtroubleshooting and Service Equipment RequiredMethod of Charging Refrigerant ChargingOvercharged Refrigerant Systems Undercharged Refrigerant SystemsRestricted Refrigerant System Malfunction of Valve Normal Function of ValveProblem Possible Cause Action Cooling only Room AIR Conditioners Troubleshooting TipsReplace fuse, reset breaker. If repeats, check Problem Possible Cause Action Problem Possible Cause Action Heat / Cool Room AIR Conditioners Troubleshooting Tips Refrigerant System Diagnosis Heating Troubleshooting Chart CoolingElectrical Troubleshooting Chart Heat Pump Troubleshooting Chart HeatingSystem Cools When Heating is Desired YESModel Models RM18L30-A, KM18L30-A, KM21L30-A, RM24L30-A, KM24L30-A SS16L30-A/B, SM18L30-A/B, SM21L30-A/B, SM24L30-A/B SL36L30-A SL28L30-A SL36L30-B EQ08L11-A ES12L33-A, ES16L33-A, EM18L34-A, EM24L35-A EL36L35-A YS09L10-A, YS09L10-B YS13L33-A, YM18L34-A YL24L35-A RAC-Svc-06