ROUTINE MAINTENANCE

NOTE: Units are to be inspected and serviced by qualified service personnel only.

Routine maintenance is required annually or semi-annually, depending upon annual usage.

1.Clean the unit air intake filter at least every 250 to 300 fan hours of operation or when the unit’s indicator light is on if so equipped. Clean the filters with a mild detergent in warm water and allow to dry thoroughly before reinstalling.

2.The indoor coil (evaporator coil), the outdoor coil (condenser coil) and base pan should be inspected periodically (yearly or bi-yearly) and cleaned of all debris (lint, dirt, leaves, paper, etc.). Clean the coils and base pan with a soft brush and compressed air or vacuum. If using a pressure washer, be careful not to bend the aluminium fin pack. Use a sweeping up and down motion in the direction of the vertical aluminum fin pack when pressure cleaning coils. Cover all electrical components to protect them from water or spray. Allow the unit to dry thoroughly before reinstalling it in the sleeve.

NOTE: Do not use a caustic coil cleaning agent on coils or base pan. Use a biodegradable cleaning agent and degreaser.

Inspect the indoor blower housing, evaporator blade, condenser fan blade, and condenser shroud periodically (yearly or bi-yearly) and clean of all debris (lint, dirt, mold, fungus, etc.) Clean the blower housing area and blower wheel with an antibacterial / antifungal cleaner. Use a biodegradable cleaning agent and degreaser on condenser fan and condenser shroud. Use warm or cold water when rinsing these items. Allow all items to dry thoroughly before reinstalling them.

3.Periodically (at least yearly or bi-yearly): inspect all control components, both electrical and mechanical, as well as the power supply. Use proper testing instruments (voltmeter, ohmmeter, ammeter, wattmeter, etc.) to perform electrical tests. Use an air conditioning or refrigeration thermometer to check room, outdoor and coil operating temperatures. Use a sling psychrometer to measure wet bulb temperatures indoors and outdoors.

4.Inspect the surrounding area (inside and outside) to ensure that the units’ clearances have not been compromised or altered.

5.Inspect the sleeve and drain system periodically (at least yearly or bi-yearly) and clean of all obstructions and debris. Clean both areas with an antibacterial and antifungal cleaner. Rinse both items thoroughly with water and ensure that the drain outlets are operating correctly. Check the sealant around the sleeve and reseal areas as needed.

6.Clean the front cover when needed. Use a mild detergent. Wash and rinse with warm water. Allow it to dry thoroughly before reinstalling it in the chassis.

4

Image 4
Contents 2006 Table of Contents IntroductionRoom AIR Conditioners Limited Warranty Routine Maintenance 08 L 1 Unit IdentificationPerformance Data ChassisElectrical Data ReceptacleFunctional Component Definitions Electronic ControlsTesting the Electronic Control XQ/WS Boards & QME Boards Testing the Electronic Control Error Code ListingsRefrigeration System Sequence of Operation Sealed Refrigeration System RepairsHermetic Component Replacement Specialprocedureinthecaseofcompressor Motor BurnoutRotarycompressorspecialtroubleshooting and Service Equipment RequiredRefrigerant Charging Method of ChargingUndercharged Refrigerant Systems Overcharged Refrigerant SystemsRestricted Refrigerant System Normal Function of Valve Malfunction of ValveCooling only Room AIR Conditioners Troubleshooting Tips Problem Possible Cause ActionReplace fuse, reset breaker. If repeats, check Problem Possible Cause Action Problem Possible Cause Action Heat / Cool Room AIR Conditioners Troubleshooting Tips Troubleshooting Chart Cooling Refrigerant System Diagnosis HeatingTroubleshooting Chart Heating Electrical Troubleshooting Chart Heat PumpSystem Cools When Heating is Desired YESModel Models RM18L30-A, KM18L30-A, KM21L30-A, RM24L30-A, KM24L30-A SS16L30-A/B, SM18L30-A/B, SM21L30-A/B, SM24L30-A/B SL36L30-A SL28L30-A SL36L30-B EQ08L11-A ES12L33-A, ES16L33-A, EM18L34-A, EM24L35-A EL36L35-A YS09L10-A, YS09L10-B YS13L33-A, YM18L34-A YL24L35-A RAC-Svc-06