Lincoln Electric IM834-B manual Welding Output Cables, Standby Power Connections

Page 14

A-6

INSTALLATION

A-6

 

 

 

WELDING OUTPUT CABLES

With the engine off connect the electrode and work cables to the output studs. The welding process dic- tates the polarity of the electrode cable. These con- nections should be checked periodically and tightened with a 3/4" wrench.

Table A.1 lists recommended cable sizes and lengths for rated current and duty cycle. Length refers to the distance from the welder to the work and back to the welder. Cable diameters are increased for long cable lengths to reduce voltage drops.

TABLE A-1

TOTAL COMBINED LENGTH OF ELECTRODE AND WORK CABLES

The auxiliary power capacity is 10,000 watts Peak, 9500 Watts Continuous of 60 Hz, single phase power. The auxil- iary power capacity rating in watts is equivalent to volt- amperes at unity power factor. The max permissible current of the 240 VAC output is 40 Amps. The 240 VAC output can be split to provide two separate 120 VAC outputs with a max permissible current of 40 Amps per output to two separate 120 VAC branch circuits (these circuits cannot be paral- leled). Output voltage is within ± 10% at all loads up to rated capacity. All auxiliary power is protected by circuit breakers.

The 120 V auxiliary power receptacles should only be used with three wire grounded type plugs or approved double insulated tools with two wire plugs. The current rating of any plug used with the system must be at least equal to the cur- rent capacity of the associated receptacle.

Cable Length

0-100Ft. (0-30 meters)

100-150 Ft. (30-46m meters)

150-200 Ft. (46-61 meters)

Cable Size for

305Amps

100% Duty Cycle

1/ 0 AWG

2 / 0 AWG

3 / 0 AWG

NOTE: The 240 V receptacle has two 120 V circuits, b u t are of opposite polarities and cannot be paralleled.

STANDBY POWER CONNECTIONS

The RANGER 305G is suitable for temporary, standby or emergency power using the engine manufacturer’s recom- mended maintenance schedule.

CABLE INSTALLATION

Install the welding cables to your RANGER 305G as follows.

1.The engine must be OFF to install welding cables.

2.Remove the flanged nuts from the output terminals.

3.Connect the electrode holder and work cables to the weld output terminals. The terminals are identi- fied on the case front.

4.Tighten the flanged nuts securely.

5.Be certain that the metal piece you are welding (the “work”) is properly connected to the work clamp and cable.

6.Check and tighten the connections periodically.

CAUTION

Loose connections will cause the output termi- nals to overheat. The terminals may eventually melt.

Do not cross the welding cables at the output terminal connection. Keep the cables isolated and separate from one another.

------------------------------------------------------------------------

AUXILIARY POWER RECEPTACLES

The auxiliary power of the RANGER 305G consists of two 20 Amp-120 VAC (5-20R) duplex receptacles and one 50 Amp 120/240 VAC (14-50R) receptacle. The 240 VAC receptacle can be split for single phase 120 VAC operation.

The RANGER 305G can be permanently installed as a standby power unit for 240 VAC, 3 wire, single phase, 40 amp service. Connections must be made by a licensed elec- trician who can determine how the 120/240 VAC power can be adapted to the particular installation and comply with all applicable electrical codes.

Install the double-pole, double-throw switch between the power company meter and the premises disconnect. Switch rating must be the same or greater than the cus- tomer’s premises disconnect and service over current pro- tection.

Take necessary steps to assure load is limited to the capacity of the RANGER 305G by installing a 40 amp, 240 VAC double pole circuit breaker. Maximum rated load for each leg of the 240 VAC auxiliary is 40 amperes. Loading above the rated output will reduce output voltage below the allowable - 10% of rated voltage which may damage appliances or other motor-driven equipment and may result in overheating of the RANGER 305G engine and/or alternator windings.

Install a 50 amp, 120/240 VAC plug (NEMA Type 14-50) to the double-pole circuit breaker using No. 6, 4 conductor cable of the desired length. (The 50 amp, 120/240 VAC plug is available in the optional K802R plug kit or as part number T12153-9.)

Plug this cable into the 50 Amp, 120/240 Volt receptacle on the RANGER 305G case front.

RANGER 305G

Image 14
Contents Ranger 305G Safety California Proposition 65 WarningsElectric Shock can kill Welding Sparks can cause fire or explosion IiiPrécautions DE Sûreté Sûreté Pour Soudage a L’ArcThank You Table of Contents Section F Section DSection E P491Installation Technical Specifications Ranger 305G K1726-2, K1726-32INSTALLATIONA-2 Machine Specifications Ranger 305G K1726-2, K1726-3 Location and Ventilation Safety Precautions Additional Safety Precautions Fuel PRE-OPERATION Engine ServiceBattery Connection Gasoline Engine Cooling SystemElectrical Connections Welding Output Cables Standby Power ConnectionsAuxiliary Power Receptacles Total Combined Length of Electrode and Work CablesConnection of Ranger 305G to Premises Wiring GNDConnection of LN-15 to the Ranger 305G Connection of Lincoln Electric Wire FeedersConnection of LN-7 or LN-8 to the Ranger 305G Across The-Arc ModelConnection of Prince Spool Gun to the Ranger 350 G General Description Design FeaturesOperation Digital Output Meters Weld Mode Selector SwitchWelding Controls Output Control ARC ControlWire Feeder Voltmeter Switch PIN ConnectorWeld Terminals Control Switch Idler SwitchWelder Operation Typical Current Ranges 1 for Tungsten ELECTRODES2 Wire WELDING-CVTIG Welding Ranger 305G Extension Cord Length Recommendations Auxiliary PowerARC Gouging Accessories Kohler Engine MaintenanceEngine Maintenance Components Air Pre-cleaner Service Engine Oil Refill Capacities Without oil filter replacementAir Cleaner Service Engine Oil ChangeSpark Plug AIR Filter Paper ElementFuel Filter Engine AdjustmentBattery Maintenance Servicing Optional Spark ArrestorWelder/Generator Maintenance Troubleshooting HOW to USE Troubleshooting GuideIs Evident.Authorized Field Service Facility Contact your local Lincoln Authorized Field Service FacilityAuthorized Field Service Facility Contact your local LincolnFaulty control cable. Repair or Stick Diagrams Diagrams Diagrams Diagrams Diagrams Engine Welders /LN-8 Connection Diagram Diagrams Diagrams Diagrams Diagrams Enhanced Diagram Dimension Print Precaucion Warnung