Friedrich V(E, H)A09K25 Checking External Static Pressure, Checking Approximate Airflow

Page 15

Checking External Static Pressure

The airflow through the unit can be determined by measuring the external static pressure of the system, and consulting the blower performance data for the specifi c VERT-I-PAK.

1.Set up to measure external static pressure at the supply and return air.

2.Drill holes in the supply duct for pressure taps, pilot tubes or other accurate pressure sensing devices.

3.Connect these taps to a level inclined manometer or Magnehelic gauges.

4.Ensure the coil and fi lter are clean, and that all the registers are open.

5.Determine the external static pressure with the blower operating.

6.Refer to the Air Flow Data for your VERT-I-PAK system to fi nd the actual airfl ow for factory-selected fan speeds.

7.If the actual airfl ow is either too high or too low, the blower speed will need to be changed.

8.Select a speed, which most closely provides the required airfl ow for the system.

9.Recheck the external static pressure with the new speed. External static pressure (and actual airfl ow) will have changed to a higher or lower value depending upon speed selected. Recheck the actual airfl ow (at this "new" static pressure) to confi rm speed selection.

10.Repeat steps 8 and 9 (if necessary) until proper airfl ow has been obtained.

EXAMPLE: Airflow requirements are calculated as follows: (Having a wet coil creates additional resistance to airfl ow. This addit ional resistance must be taken into consideration to obtain accurate airfl ow information.

1 ½ TON SYSTEM ( 18,000 Btu)

Operating on high speed @ 230 volts with dry coil

measured external static pressure .20

Air Flow = 500 CFM

In the same SYSTEM used in the previous example but having a WET coil you must use a correction factor of

.94 (i.e. 500 x .94=470 CFM) to allow for the resistance (internal) of the condensate on the coil.

It is important to use the proper procedure to check external Static Pressure and determine actual airfl ow. Since in

the case of the VERT-I-PAK, the condensate will cause a reduction in measured External Static Pressure for the given airfl ow.

It is also important to remember that when dealing with VERT-l-PAK units that the measured External Static Pressure increases as the resistance is added externally to the cabinet. Example: duct work, fi lters, grilles.

Checking Approximate Airflow

If an inclined manometer or Magnehelic gauge is not available to check the External Static Pressure, or the blower performance data is unavailable for your unit, approximate air fl ow call be calculated by measuring the temperature rise, then using tile following criteria.

KILOWATTS x 3413

= CFM

Temp Rise x 1.08

Electric Heat Strips

The approximate CFM actually being delivered can be calculated by using the following formula:

DO NOT simply use the Kilowatt Rating of the heater (i.e. 2.5, 3.4, 5.0) as this will result in a less-than-correct airfl ow calculation. Kilowatts may be calculated by multiplying the measured voltage to the unit (heater) times the measured

current draw of all heaters (ONLY) in operation to obtain watts. Kilowatts are than obtained by dividing by 1000.

EXAMPLE: Measured voltage to unit (heaters) is 230 volts. Measured Current Draw of strip heaters is 11.0 amps.

230 x 11.0 = 2530 2530/1000 = 2.53 Kilowatts 2.53 x 3413 = 8635

Supply Air

 

95°F

Return Air

 

 

75°F

 

 

Temperature Rise

20°

20 x 1.08 = 21.6

8635

= 400 CFM

21.6

IMPORTANT: FLEX DUCT CAN COLLAPSE AND CAUSE AIRFLOW RESTRICTIONS. DO NOT USE FLEX DUCT FOR: 90 DEGREE BENDS, OR UNSUPPORTED RUNS OF 5 FT. OR MORE.

15

Image 15
Contents VE,HA24K25 VE,HA24K34 VE,HA09K25 VE,HA09K34VE,HA12K25 VE,HA12K34 VE,HA18K25 VE,HA18K34Table of Contents Introduction Serial Number Identification Guide VERT-I-PAKH Suffix Chassis Specifications VERT-I-PAKE & G Suffix Chassis Specifications VERT-I-PAKA D Suffix Chassis Specifications Sequence of Operation Refrigeration AssemblyControl Low Voltage Electrical SupplySupply Circuit Supply VoltageHeat Anticipators Room ThermostatsTypical Electrical & Thermostat Wiring Diagrams Typical Electrical & Thermostat Wiring Diagrams Suffix For 208 Volt Models only Move the White Wire AS Shown below Cooling Indoor Blower AirflowCondenser Fan Motors Blower Wheel InspectionChecking External Static Pressure Checking Approximate AirflowElectric Heat Strips Explanation of charts Ductwork PreparationRefrigerant Charging Undercharged Refrigerant Systems Method Of ChargingRestricted Refrigerant Systems Overcharged Refrigerant SystemsElectrical Circuit and Coil Testing CoilMetering Device Capillary Tube Systems Reversing Valve Description/OperationTouch Test in Heating/Cooling Cycle Checking Reversing ValveFrom Electrical Shock Compressor ChecksRecommended Procedure for Compressor Replacement Single Phase Resistance TestCapacitor Connections CapacitorsElectric Heat Switch Check Out Electric Heat Switch OperationWiring Diagram Index VHA09K25RTG Suffix only Suffix only Suffix only Page Page Page Page Page Page Page Page Page Electrical Troubleshooting Chart Cooling TON Electrical Troubleshooting Chart Cooling Troubleshooting Chart Cooling Electrical Troubleshooting Chart Heat Pump Page Use Factory Certified Parts