Friedrich V(E, H)A09K25 Electrical Supply, Supply Circuit, Supply Voltage, Control Low Voltage

Page 9

Electrical Supply

WARNING: Electrical shock hazard.

Turn OFF electric power at fuse box or service panel before making any electrical connections and ensure a proper ground connection is made before connecting line voltage.

All electrical connections and wiring MUST be installed by a qualified electrician and conform to the National Electrical Code and all local codes which have jurisdiction.

Failure to do so can result in property damage, personal injury and/or death.

Supply Circuit

The system cannot be expected to operate correctly unless the system is properly connected (wired) to an adequately sized single branch circuit. Check the installation manual and/or technical data for your particular unit and/or strip heaters to determine if the circuit is adequately sized.

Electrical Rating Tables

NOTE: Use copper conductors ONLY

Wire sizes are per NEC. Check local codes for overseas applications

A through D Suffix

Units Only

250 V Receptacles and Fuse Types

AMPS

15

 

20 *

 

30

 

 

 

 

 

 

 

RECEPTACLE

 

 

 

 

 

 

 

 

 

 

 

 

 

MANUFACTURER

 

PART NUMBERS

 

 

 

 

 

 

 

 

Hubbell

5661

 

5461

 

9330

P & S

5661

 

5871

 

5930

GE

GE4069-1

GE4182-1

GE4139-3

Arrow-Hart

5661

 

5861

 

5700

 

 

 

 

 

 

 

TIME-DELAY TYPE

 

 

 

 

 

 

FUSE

15

 

20

 

30

(or HACR circuit breaker)

 

 

 

 

 

 

 

 

 

 

 

 

 

HACR — Heating, Air Conditioning, Refrigeration

* May be used for 15 Amp applications if fused for 15 Amp

Recommended branch circuit wire sizes*

Nameplate maximum circuit

AWG Wire size**

breaker size

 

15A

14

20A

12

30A

10

AWG — American Wire Gauge * Single circuit from main box

** Based on copper wire, single insulated conductor at 60°C

Supply Voltage

To insure proper operation, supply voltage to the system should be within five (5) percent (plus or minus) of listed rating plate voltage.

Control (Low) Voltage

To insure proper system operation, the transformer secondary output must be maintained at a nominal 24 volts. The control (low) voltage transformer is equipped with multiple primary voltage taps. Connecting the primary, (supply) wire to the tap (i.e., 208 and 240 volts) that most closely matches the MEASURED supply voltage will insure proper transformer secondary output is maintained.

Supply Voltage

Supply voltage to the unit should be a nominal 208/230 volts. It must be between 197 volts and 253 volts. Supply voltage to the unit should be checked WITH THE UNIT IN OPERATION. Voltage readings outside the specified range can be expected to cause operating problems. Their cause MUST be investigated and corrected.

Electrical Ground

GROUNDING OF THE ELECTRICAL SUPPLY TO ALL UNITS IS REQUIRED for safety reasons.

Electrical Requirements

NOTE:

All field wiring must comply with

 

NEC and local codes. It is the

 

responsibility of the installer to

 

insure that the electrical codes are

 

met.

Wire Size

Use ONLY wiring size recommended

 

for single outlet branch circuit.

Fuse/Circuit

Use ONLY type and size fuse or

 

HACR circuit breaker

Breaker

Indicated on unit's rating plate (See

 

sample on page 6).

 

Proper current protection to the unit

 

is the responsibility of the owner.

Grounding

Unit MUST be grounded from branch

 

circuit to unit, or through separate

 

ground wire provided on permanently

 

connected units. Be sure that branch

 

circuit or general purpose outlet is

 

grounded.

Wire Sizing

Use recommended wire size given in

 

the tables below and install a single

 

branch circuit. All wiring must comply

 

with local and national codes. NOTE:

 

Use copper conductors only.

9

Image 9
Contents VE,HA12K25 VE,HA12K34 VE,HA09K25 VE,HA09K34VE,HA18K25 VE,HA18K34 VE,HA24K25 VE,HA24K34Table of Contents Introduction Serial Number Identification Guide VERT-I-PAKH Suffix Chassis Specifications VERT-I-PAKE & G Suffix Chassis Specifications VERT-I-PAKA D Suffix Chassis Specifications Sequence of Operation Refrigeration AssemblySupply Circuit Electrical SupplySupply Voltage Control Low VoltageHeat Anticipators Room ThermostatsTypical Electrical & Thermostat Wiring Diagrams Typical Electrical & Thermostat Wiring Diagrams Suffix For 208 Volt Models only Move the White Wire AS Shown below Condenser Fan Motors Indoor Blower AirflowBlower Wheel Inspection CoolingChecking External Static Pressure Checking Approximate AirflowElectric Heat Strips Explanation of charts Ductwork PreparationRefrigerant Charging Undercharged Refrigerant Systems Method Of ChargingRestricted Refrigerant Systems Overcharged Refrigerant SystemsMetering Device Capillary Tube Systems Testing CoilReversing Valve Description/Operation Electrical Circuit and CoilTouch Test in Heating/Cooling Cycle Checking Reversing ValveFrom Electrical Shock Compressor ChecksRecommended Procedure for Compressor Replacement Single Phase Resistance TestCapacitor Connections CapacitorsElectric Heat Switch Check Out Electric Heat Switch OperationWiring Diagram Index VHA09K25RTG Suffix only Suffix only Suffix only Page Page Page Page Page Page Page Page Page Electrical Troubleshooting Chart Cooling TON Electrical Troubleshooting Chart Cooling Troubleshooting Chart Cooling Electrical Troubleshooting Chart Heat Pump Page Use Factory Certified Parts