Friedrich H)A09K25, V(E service manual Sequence of Operation, Refrigeration Assembly

Page 8

Sequence of Operation

Agood understanding of the basic operation of the refrigeration system is essential for the service technician. Without this understanding, accurate troubleshooting of refrigeration system problems will be more difficult and time consuming, if not (in some cases) entirely impossible. The refrigeration system uses four basic principles (laws) in its operation they are as follows:

1."Heat always fl ows from a warmer body to a cooler body."

2."Heat must be added to or removed from a substance before a change in state can occur"

3."Flow is always from a higher pressure area to a lower pressure area."

4."The temperature at which a liquid or gas changes state is dependent upon the pressure."

The refrigeration cycle begins at the compressor. Starting the compressor creates a low pressure in the suction line which draws refrigerant gas (vapor) into the compressor. The compressor then "compresses" this refrigerant, raising its pressure and its (heat intensity) temperature.

The refrigerant leaves the compressor through the discharge line as a HOT high pressure gas (vapor). The refrigerant enters the condenser coil where it gives up some of its heat. The condenser fan moving air across the coil's finned surface facilitates the transfer of heat from the refrigerant to the relatively cooler outdoor air.

When a sufficient quantity of heat has been removed from the refrigerant gas (vapor), the refrigerant will "condense" (i.e.) change to a liquid). Once the refrigerant has been condensed (changed) to a liquid it is cooled even further by the air that continues to flow across the condenser coil.

The Vert-I-Pak design determines at exactly what point (in the condenser) the change of state (i.e. gas to a liquid) takes place. In all cases, however, the refrigerant must be totally condensed (changed) to a liquid before leaving the condenser coil.

The refrigerant leaves the condenser coil through the liquid line as a WARM high pressure liquid. It next will pass through the refrigerant drier (if so equipped). It is the function of the drier to trap any moisture present in the system, contaminants, and LARGE particulate matter.

The liquid refrigerant next enters the metering device. The metering device is a capillary tube. The purpose of the metering device is to "meter" (i.e. control or measure) the quantity of refrigerant entering the evaporator coil.

In the case of the capillary tube this is accomplished (by design) through size (and length) of device, and the pressure difference present across the device.

Since the evaporator coil is under a lower pressure (due to the suction created by the compressor) than the liquid line, the liquid refrigerant leaves the metering device entering the evaporator coil. As it enters the evaporator coil, the larger area and lower pressure allows the refrigerant to expand and lower its temperature (heat intensity). This expansion is often referred to as "boiling". Since the unit's blower is moving Indoor air across the finned surface of the evaporator coil, the expanding refrigerant absorbs some of that heat. This results in a lowering of the indoor air temperature, hence the "cooling" effect.

The expansion and absorbing of heat cause the liquid refrigerant to evaporate (i.e. change to a gas). Once the refrigerant has been evaporated (changed to a gas), it is heated even further by the air that continues to flow across the evaporator coil.

The particular system design determines at exactly what point (in the evaporator) the change of state (i.e. liquid to a gas) takes place. In all cases, however, the refrigerant must be totally evaporated (changed) to a gas before leaving the evaporator coil.

The low pressure (suction) created by the compressor causes the the refrigerant to leave the evaporator through the suction line as a COOL low pressure vapor. The refrigerant then returns to the compressor, where the cycle is repeated.

Refrigeration Assembly

1.Compressor

2.Evaporator Coil Assembly

3.Condenser Coil Assembly

4.Capillary Tube

5.Compressor Overload

8

Image 8
Contents VE,HA09K25 VE,HA09K34 VE,HA12K25 VE,HA12K34VE,HA18K25 VE,HA18K34 VE,HA24K25 VE,HA24K34Table of Contents Introduction Serial Number Identification Guide VERT-I-PAKH Suffix Chassis Specifications VERT-I-PAKE & G Suffix Chassis Specifications VERT-I-PAKA D Suffix Chassis Specifications Refrigeration Assembly Sequence of OperationElectrical Supply Supply CircuitSupply Voltage Control Low VoltageRoom Thermostats Heat AnticipatorsTypical Electrical & Thermostat Wiring Diagrams Typical Electrical & Thermostat Wiring Diagrams Suffix For 208 Volt Models only Move the White Wire AS Shown below Indoor Blower Airflow Condenser Fan MotorsBlower Wheel Inspection CoolingElectric Heat Strips Checking External Static PressureChecking Approximate Airflow Refrigerant Charging Explanation of chartsDuctwork Preparation Method Of Charging Undercharged Refrigerant SystemsOvercharged Refrigerant Systems Restricted Refrigerant SystemsTesting Coil Metering Device Capillary Tube SystemsReversing Valve Description/Operation Electrical Circuit and CoilChecking Reversing Valve Touch Test in Heating/Cooling CycleCompressor Checks From Electrical ShockSingle Phase Resistance Test Recommended Procedure for Compressor ReplacementCapacitors Capacitor ConnectionsElectric Heat Switch Operation Electric Heat Switch Check OutWiring Diagram Index VHA09K25RTG Suffix only Suffix only Suffix only Page Page Page Page Page Page Page Page Page Electrical Troubleshooting Chart Cooling TON Electrical Troubleshooting Chart Cooling Troubleshooting Chart Cooling Electrical Troubleshooting Chart Heat Pump Page Use Factory Certified Parts