Friedrich H)A09K25, V(E Overcharged Refrigerant Systems, Restricted Refrigerant Systems

Page 18

Overcharged Refrigerant Systems

Compressor amps will be near normal or higher. Noncondensables can also cause these symptoms. To confirm, remove some of the charge, if conditions improve, system may be overcharged. If conditions don’t improve, Noncondensables are indicated.

Whenever an overcharged system is indicated, always make sure that the problem is not caused by air fl ow problems. Improper air fl ow over the evaporator coil may indicate some of the same symptoms as an overcharged system.

An over charge can cause the compressor to fail, since it would be "slugged" with liquid refrigerant.

The charge for any system is critical. When the compressor is noisy, suspect an overcharge, when you are sure that the air quantity over the evaporator coil is correct. Icing

of the evaporator will not be encountered because the refrigerant will boil later if at all. Gauges connected to system will usually have higher head pressure (depending upon amount of overcharge). Suction pressure should be slightly higher.

Restricted Refrigerant Systems

A quick check for either condition begins at the evaporator. With a partial restriction, there may be gurgling sounds at the metering device entrance to the evaporator. The evaporator in a partial restriction could be partially frosted or have an ice ball close to the entrance of the metering device. Frost may continue on the suction line back to the compressor.

Often a partial restriction of any type can be found by feel, as there is a temperature difference from one side of the restriction to the other.

With a complete restriction, there will be no sound at the metering device entrance. An amperage check of the compressor with a partial restriction may show normal current when compared to the unit specifi cation. With a complete restriction the current drawn may be considerably less than normal, as the compressor is running in a deep vacuum (no load.) Much of the area of the condenser will be relatively cool since most or all of the liquid refrigerant will be stored there.

The following conditions are based primarily on a system in the cooling mode.

Troubleshooting a restricted refrigerant system can be difficult. The following procedures are the more common problems and solutions to these problems. There are two types of refrigerant restrictions: Partial restrictions and complete restrictions.

A partial restriction allows some of the refrigerant to circulate through the system.

With a complete restriction there is no circulation of refrigerant in the system.

Restricted refrigerant systems display the same symptoms as a "low-charge condition." When the unit is shut off, the gauges may equalize very slowly. Gauges connected to a completely restricted system will run in a deep vacuum. When the unit is shut off, the gauges will not equalize at all.

18

Image 18
Contents VE,HA18K25 VE,HA18K34 VE,HA09K25 VE,HA09K34VE,HA12K25 VE,HA12K34 VE,HA24K25 VE,HA24K34Table of Contents Introduction Serial Number Identification Guide VERT-I-PAKH Suffix Chassis Specifications VERT-I-PAKE & G Suffix Chassis Specifications VERT-I-PAKA D Suffix Chassis Specifications Refrigeration Assembly Sequence of OperationSupply Voltage Electrical SupplySupply Circuit Control Low VoltageRoom Thermostats Heat AnticipatorsTypical Electrical & Thermostat Wiring Diagrams Typical Electrical & Thermostat Wiring Diagrams Suffix For 208 Volt Models only Move the White Wire AS Shown below Blower Wheel Inspection Indoor Blower AirflowCondenser Fan Motors CoolingChecking External Static Pressure Checking Approximate AirflowElectric Heat Strips Explanation of charts Ductwork PreparationRefrigerant Charging Method Of Charging Undercharged Refrigerant SystemsOvercharged Refrigerant Systems Restricted Refrigerant SystemsReversing Valve Description/Operation Testing CoilMetering Device Capillary Tube Systems Electrical Circuit and CoilChecking Reversing Valve Touch Test in Heating/Cooling CycleCompressor Checks From Electrical ShockSingle Phase Resistance Test Recommended Procedure for Compressor ReplacementCapacitors Capacitor ConnectionsElectric Heat Switch Operation Electric Heat Switch Check OutWiring Diagram Index VHA09K25RTG Suffix only Suffix only Suffix only Page Page Page Page Page Page Page Page Page Electrical Troubleshooting Chart Cooling TON Electrical Troubleshooting Chart Cooling Troubleshooting Chart Cooling Electrical Troubleshooting Chart Heat Pump Page Use Factory Certified Parts