Friedrich KP05A10 KP06A10 manual Evaporator, Capillary Tube

Page 10

2.4.2 EVAPORATOR

1.Remove the cabinet.

2.Discharge the refrigerant by using a refrigerant recovery system.

3.Remove the air guide upper. (Refer to Section 2.2.1)

4.After discharging the refrigerant completely, unbraze the interconnecting tube at the condenser connections.

5.Remove the evaporator.

6.Re-install by referring to the procedures above.

2.4.3 CAPILLARY TUBE

1.Remove the cabinet.

2.Discharge the refrigerant by using a refrigerant recovery system.

3.Remove the air guide upper. (Refer to Section 2.2.1)

4.After discharging the refrigerant completely, unbraze the interconnecting tube of the capillary tube.

5.Remove the capillary tube.

6.Re-install by referring to the procedures above.

NOTES

Replacement of the refrigeration cycle.

1.When replacing the refrigerating cycle, be sure to discharge the refrigerant by using a refrigerant recovery system.

2.After discharging the unit completely, remove the desired components, and unbraze the pinch-off tubes.

3.Solder service valves into the pinch-off tube ports, leaving the valves open.

4.Solder the pinch-off tubes with service valves.

5.After completing the above procedures, the valve must be closed and left in place on the system for any subsequent procedures.

6.Evacuate as follows:

6-1. Connect the vacuum pump, as illustrated in figure 21A.

6-2. Start the vacuum pump. Slowly open manifold valves A and B with two full turns counter- clockwise and leave the valves closed.

The vacuum pump is now pulling through valves A and B up to valve C by means of manifold and the entire system.

CAUTION : If high vacuum equipment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counter-clock-

wise. This will keep oil from foaming and being drawn into the vacuum pump.

6-3. Operate the vacuum pump for 20 to 30 min- utes, until 600 micron vacuum is obtained. Close valves A and B and observe vacuum gauge for a few minutes.

A rise in pressure would indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop the vacuum pump.

6-4. Remove the hose from the vacuum pump and place it on the charging cylinder. See figure 23B. Open valve C.

Discharge the line at the manifold connection. 6-5. The system is now ready for final charging.

7.Recharge as follows:

7-1. Rotary compressor systems are charged from the high-side. If the total charge cannot be put in the high-side, the balance will be put in the suction line through the access valve which is installed as the system is opened.

7-2. Connect the charging cylinder as shown in fig- ure 21B. With valve C open, discharge the hose at the manifold connection.

7-3. Open valve A and allow the proper charge to enter the system. Valve B is still closed.

7-4. If more charge is required, the high-side will not take it. Close valve A.

7-5. With the unit running, open valve B and add the balance of the charge.

a.Do not add the liquid refrigerant to the low- side.

b.Watch the low-side gauge, allow pressure to rise to 30 lbs.

c.Turn off valve B and allow the pressure to drop.

d.Repeat steps B and C until the balance of the charge is in the system.

7-6. When the unit is operating correctly, use the pinch-off tool with the unit still running and the clamp on the pinch-off tube. Using a tube cut- ter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos solder and solder the pinch-off tube closed. Turn off the unit, allow setting for a while and then test the leak- age of the pinch-off connection.

— 10—

Image 10
Contents Room Air Conditioner Service and Parts Manual KP Line Contents Preface FeaturesSpecifications ModelsLocations of Controls Safety PrecautionsInsulation Resistance Test Front Grille Disassembly InstructionsMechanical Parts CabinetAIR Guide Upper AIR Handling PartsORIFICE, Turbo FAN and FAN AIR Guide Electrical PartsOverload Protector Thermistor CompressorCapacitor Control PanelRefrigerant Cycle Power CordCondenser Evaporator Capillary TubePulling Vacuum Select the Best Location InstallationHOW to Install Window RequirementsLocating Unit in Window Before InstallationNOW Start Installation Attach L BracketSecure the Guide Panels Install the Sash Seal and Sash LockOutside Electrical Data Troubleshooting GuideUSE of Extension Cords Piping System Condenser CoilsTroubleshooting Guide Unit is running but cooling is ineffectiveFails to Start Room AIR Conditioner Voltage Limits Complaint Cause RemedyReplace if open. If the compressor temperature is Complaint Cause Remedy Circuit Diagram Description QTYExploded View W0CZZService Parts List Description Friedrich Part noMemo Memo Use Factory Certified Parts

KP05A10 KP06A10 specifications

The Friedrich KP05A10 and KP06A10 are advanced air conditioning units designed for both residential and commercial use, providing efficient cooling solutions that meet modern comfort demands. These models stand out for their cutting-edge technologies, robust features, and energy efficiency, catering to various user needs.

One of the main features of the KP05A10 and KP06A10 is their inverter technology. This innovative system adjusts the compressor speed based on the cooling requirement, which not only enhances comfort by maintaining a consistent temperature but also significantly reduces energy consumption. By operating more efficiently at varying loads, these air conditioners can achieve a higher seasonal energy efficiency ratio (SEER), making them an excellent choice for environmentally-conscious consumers.

Additionally, both units are equipped with a multi-stage filtration system. This feature ensures that the air circulated within the space is clean and free from allergens, dust, and pollutants. The filters are easy to access and maintain, promoting a healthier indoor environment for occupants. The KP05A10 and KP06A10 also come with a dehumidification mode, which effectively reduces humidity levels without overcooling the area, making it ideal for humid climates.

The design of these air conditioning units embraces modern aesthetics, featuring a sleek and compact exterior that can seamlessly blend into various interior decors. The user-friendly interface and remote control further enhance the user experience, allowing for easy temperature adjustments and mode selections from a distance.

Operationally, the KP05A10 and KP06A10 are known for their quiet performance. Equipped with sound-dampening technology, these models operate at low decibel levels, ensuring a peaceful environment. Moreover, the units boast a durable construction, ensuring longevity and reliability, which translates to fewer maintenance needs and operational disruptions.

In terms of installation, the Friedrich KP05A10 and KP06A10 offer versatility, with options for both window and wall installations. This flexibility allows consumers to select the best arrangement for their space without compromising on performance.

Overall, the Friedrich KP05A10 and KP06A10 air conditioning units exemplify a commitment to quality, efficiency, and comfort. With their modern technologies and thoughtful features, they are well-suited for diverse applications, providing effective cooling solutions for homes and businesses alike.