COMPLAINT

CAUSE

REMEDY

 

 

 

Fan motor noise.

Fan

If cracked, out of balance, or partially missing,

 

 

replace it.

 

 

 

 

Blower

If cracked, out of balance, or partially missing,

 

 

replace it.

 

 

 

 

Loose set screw

Tighten it.

 

 

 

 

Worn bearings

If knocking sounds continue when running or

 

 

loose, replace the motor. If the motor hums or

 

 

noise appears to be internal while running,

 

 

replace motor.

 

 

 

Compressor will not run,

Voltage

Check voltage. See the limits on the preceding

fan motor runs.

 

page. If not within limits, call an electrician.

 

 

 

 

Wiring

Check the wire connections; if loose, repair or

 

 

replace the terminal. If the wires are discon-

 

 

nected, refer to wiring diagram for identification,

 

 

and replace the wires. Check the wire connections;

 

 

If not according to the wiring diagram, correct

 

 

the connections.

 

 

 

 

Thermistor

Check the TEMP control. If not at the lowest

 

 

number, set TEMP control to this setting and

 

 

restart the unit.

 

 

 

 

 

Check the continuity of the thermistor. Replace

 

 

the thermistor if the circuit is open.

 

 

 

 

Capacitor (discharge

Check the capacitor.

 

capacitor before

Replace if not within ±10% of manufacturer’s

 

servicing.)

rating, replace if shorted, open, or damaged.

 

 

 

 

Compressor

Check the compressor for open circuit or

 

 

ground. If open or grounded, replace the

 

 

compressor.

 

 

 

 

Overload

Check the compressor overload if externally mounted.

 

 

Replace if open. (If the compressor temperature is

 

 

high, remove the overload, cool, and retest.)

 

 

 

Compressor cycles on

Voltage

Check the voltage. See the limits on the

overload.

 

preceding page. If voltage is not within these limits,

 

 

call an electrician.

 

 

 

 

Overload

Check overload, if externally mounted.

 

 

Replace if open. (If the compressor temperature

 

 

is high, remove the overload, cool, and retest.)

 

 

 

— 20—

Image 20
Contents Room Air Conditioner Service and Parts Manual KP Line Contents Features SpecificationsPreface ModelsInsulation Resistance Test Safety PrecautionsLocations of Controls Disassembly Instructions Mechanical PartsFront Grille CabinetORIFICE, Turbo FAN and FAN AIR Handling PartsAIR Guide Upper Overload Protector Electrical PartsAIR Guide Compressor CapacitorThermistor Control PanelCondenser Power CordRefrigerant Cycle Evaporator Capillary TubePulling Vacuum Installation HOW to InstallSelect the Best Location Window RequirementsBefore Installation NOW Start InstallationLocating Unit in Window Attach L BracketOutside Install the Sash Seal and Sash LockSecure the Guide Panels USE of Extension Cords Troubleshooting GuideElectrical Data Piping System Condenser CoilsTroubleshooting Guide Unit is running but cooling is ineffectiveFails to Start Room AIR Conditioner Voltage Limits Complaint Cause RemedyReplace if open. If the compressor temperature is Complaint Cause Remedy Circuit Diagram Description QTYExploded View W0CZZService Parts List Description Friedrich Part noMemo Memo Use Factory Certified Parts

KP05A10 KP06A10 specifications

The Friedrich KP05A10 and KP06A10 are advanced air conditioning units designed for both residential and commercial use, providing efficient cooling solutions that meet modern comfort demands. These models stand out for their cutting-edge technologies, robust features, and energy efficiency, catering to various user needs.

One of the main features of the KP05A10 and KP06A10 is their inverter technology. This innovative system adjusts the compressor speed based on the cooling requirement, which not only enhances comfort by maintaining a consistent temperature but also significantly reduces energy consumption. By operating more efficiently at varying loads, these air conditioners can achieve a higher seasonal energy efficiency ratio (SEER), making them an excellent choice for environmentally-conscious consumers.

Additionally, both units are equipped with a multi-stage filtration system. This feature ensures that the air circulated within the space is clean and free from allergens, dust, and pollutants. The filters are easy to access and maintain, promoting a healthier indoor environment for occupants. The KP05A10 and KP06A10 also come with a dehumidification mode, which effectively reduces humidity levels without overcooling the area, making it ideal for humid climates.

The design of these air conditioning units embraces modern aesthetics, featuring a sleek and compact exterior that can seamlessly blend into various interior decors. The user-friendly interface and remote control further enhance the user experience, allowing for easy temperature adjustments and mode selections from a distance.

Operationally, the KP05A10 and KP06A10 are known for their quiet performance. Equipped with sound-dampening technology, these models operate at low decibel levels, ensuring a peaceful environment. Moreover, the units boast a durable construction, ensuring longevity and reliability, which translates to fewer maintenance needs and operational disruptions.

In terms of installation, the Friedrich KP05A10 and KP06A10 offer versatility, with options for both window and wall installations. This flexibility allows consumers to select the best arrangement for their space without compromising on performance.

Overall, the Friedrich KP05A10 and KP06A10 air conditioning units exemplify a commitment to quality, efficiency, and comfort. With their modern technologies and thoughtful features, they are well-suited for diverse applications, providing effective cooling solutions for homes and businesses alike.