Friedrich XQ05M10, EQ08M11, XQ06M10, XQ10M10, XQ08M10 Do not try to operate your air conditioner

Page 32

GENERAL TROUBLESHOOTING TIPS (CONTINUED)

PROBLEM

POSSIBLE CAUSE

POSSIBLE SOLUTION

 

 

 

 

 

Do not try to operate your air conditioner in the

 

The outside temperature is below

cooling mode when the outside temperature

 

60° F (16° C).

is below 60° F (16° C). The unit will not cool

 

 

properly, and the unit may be damaged.

 

 

 

 

 

Since the fan does not circulate the room

 

 

air continuously at this setting, the room air

 

The digital control is set to fan

does not mix as well and hot (or cold) spots

 

cycling mode.

may result. Using the continuous fan setting

Unit Does Not Cool/Heat

 

is recommended to obtain optimum comfort

 

 

levels.

On And Off Too Frequently

 

 

 

Check the cooling capacity of your unit to

(continued).

cooling capacity to match the heat

ensure it is properly sized for the room in which

 

it is installed. Room air conditioners are not

 

gain of the room.

 

designed to cool multiple rooms.

 

 

 

 

 

 

 

Check the heating capacity of your unit. Air

 

 

conditioners are sized to meet the cooling load,

 

heating capacity to match the heat

and heater size is then selected to meet the

 

heating load. In extreme northern climates,

 

loss of the room.

 

room air conditioners may not be able to be

 

 

 

 

used as a primary source of heat.

 

 

 

 

 

If there are heat producing appliances in use

 

This may be due to an excessive

in the room, or if the room is heavily occupied,

 

heat load in the room.

the unit will need to run longer to remove the

 

 

additional heat.

 

 

 

 

 

Be sure to use exhaust vent fans while cooking

 

It may also be due to an improperly

or bathing and, if possible, try not to use heat

 

sized unit.

producing appliances during the hottest part of

 

 

the day.

 

 

 

 

 

your new air conditioner may result in the

Unit Runs Too Much.

This may be normal for higher

unit running longer than you feel it should.

 

This may be more apparent, if it replaced an

 

 

 

 

compared to older models.

 

 

 

 

You may notice that the discharge

 

 

air temperature of your new air

 

 

conditioner may not seem as cold

 

 

as you may be accustomed to from

capacity rating (Btu/h) listed on the unit’s rating

 

older units. This does not, however,

 

 

indicate a reduction in the cooling

 

 

capacity of the unit.

 

 

 

 

31

Image 32
Contents Volt XQ05M10*, XQ06M10*, XQ08M10*, XQ10M10 Volt EQ08M11Table Of Contents Important Safety Information Your safety and the safety of others are very importantRefrigeration System Hazards Introduction Property Damage HazardsUnit Identification 6th Digit Voltage5th Digit Model Series / Year Introduced 00001Performance Data Fire Hazard Electrical DataElectric Shock Hazard Electrical Shock Hazard How to operate the Friedrich room air conditioner XQ models How to use the remote control XQ models Electronic Control Sequence of Operation Functional Component Definitions Mechanical ComponentsElectrical Components Hermetic ComponentsComponents Testing Testing the Electronic Control Boards for XQ ModelsError Code Listings Activating Test ModeEQ08 System Control Switch Test EQ08 System Control Switch TestThermostat Adjustment TestCapacitors Capacitor Check with Capacitor AnalyzerCapacitor Connections FAN MotorDrain PAN Valve Testing the Heating Element Electric Shock HazardHeating Element Refrigeration Sequence of Operation 410A Sealed System Repair Considerations Refrigeration system under high pressure410A Sealed Refrigeration System Repairs Equipment RequiredEquipment Must be Capable Risk of Electric ShockFreeze Hazard Method Of Charging / RepairsBurn Hazard Undercharged Refrigerant Systems Overcharged Refrigerant SystemsRestricted Refrigerant System Compressor Checks Single Phase Resistance Test Ground TestCompressor Replacement Recommended procedure for compressor replacementHigh Temperatures Explosion HazardRotary Compressor Special Troubleshooting and Service Routine Maintenance Clearances Sleeve / DrainFront Cover Room AIR Conditioner Unit Performance Test Data Sheet Date Model SerialGeneral Troubleshooting Tips Unit does not operateDo not try to operate your air conditioner Cooling only Room AIR Conditioners Troubleshooting Tips Replace fuse, reset breaker. If repeats, check Fused separately Allowing discharge air to short Heat / Cool only Room AIR Conditioners Troubleshooting Tips Electronic Control Cool only Models Last character may vary Aham PUB. NO. RAC-1 DAY Cooling Load Estimate FormHeat Gain from Quantity Factors Following is an example using the heat load form Heat Load FormWindows & Doors Area, sq. ft Infiltration Windows & Doors AVGRoom AIR Conditioners Limited Warranty Technical Support Contact Information Page Friedrich AIR Conditioning CO

XQ08M10, XQ10M10, XQ05M10, XQ06M10, EQ08M11 specifications

Friedrich offers a range of innovative air conditioning units designed to provide superior comfort and energy efficiency. Among its lineup, the XQ06M10, EQ08M11, XQ05M10, XQ08M10, and XQ10M10 models stand out due to their advanced technologies and user-friendly features.

The XQ series, with models like XQ06M10 and XQ05M10, is renowned for its sleek design and exceptional performance in cooling and heating environments. These models utilize a highly efficient compressor system that reduces energy consumption while maintaining optimal temperature control. The XQ06M10, for example, is designed for medium-sized rooms, featuring a cooling capacity that caters well to residential and small office settings.

On the other hand, the EQ08M11 model is known for its enhanced energy efficiency compared to traditional units, thanks to its inverter technology. This feature allows the compressor to adjust its speed according to the cooling demand, resulting in lower energy costs and a quieter operation. The EQ08M11 is also equipped with a multi-stage filtration system, improving indoor air quality by capturing dust, allergens, and pollutants.

The XQ08M10 and XQ10M10 cater to larger spaces, with their respective higher cooling capacities making them suitable for bigger living areas or small commercial settings. Both models boast an easy-to-use digital control panel, which requires minimal effort to adjust settings. Additionally, they include a programmable timer feature, allowing users to automate operation according to their daily schedules, further enhancing energy savings.

All these models showcase Friedrich’s commitment to durability and reliability, built with high-grade materials designed to withstand varying temperatures and humidity levels. The XQ series is compact, facilitating easy installation without compromising performance.

In summary, the Friedrich XQ06M10, EQ08M11, XQ05M10, XQ08M10, and XQ10M10 models combine cutting-edge technology with practicality, ensuring an efficient and enjoyable indoor climate. With features aimed at energy efficiency, ease of use, and effective air filtration, these units represent a smart investment for anyone looking to enhance their living or working environment.