Friedrich XQ06M10 Compressor Replacement, Recommended procedure for compressor replacement

Page 26

COMPRESSOR REPLACEMENT

Recommended procedure for compressor replacement

WARNING

RISK OF ELECTRIC SHOCK

Unplug and/or disconnect all electrical power to the unit before performing inspections, maintenances or service.

Failure to do so could result in electric shock, serious injury or death.

1.Be certain to perform all necessary electrical and refrigeration tests to be sure the compressor is actually defective before replacing.

WARNING

HIGH PRESSURE HAZARD

Sealed Refrigeration System contains refrigerant and oil under high pressure.

Proper safety procedures must be followed, and proper protective clothing must be worn when working with refrigerants.

Failure to follow these procedures could result in serious injury or death.

2.Recover all refrigerant from the system though the process tubes. PROPER HANDLING OF

RECOVERED REFRIGERANT ACCORDING TO EPA REGULATIONS IS REQUIRED. Do not use gauge manifold for this purpose if there has been a burnout. You will contaminate your manifold and hoses. Use a Schrader valve adapter and copper tubing for burnout failures.

WARNING

HIGH TEMPERATURES

Extreme care, proper judgment and all safety procedures must be followed when testing, troubleshooting, handling or working around unit while in operation with high temperature components. Wear protective safety aids such as: gloves, clothing etc.

Failure to do so could result in serious burn injury.

NOTICE

FIRE HAZARD

The use of a torch requires extreme care and proper judgment. Follow all safety recommended precautions and protect surrounding areas with fi re proof materials. Have a fi re extinguisher readily available. Failure to follow this notice could result in moderate to serious property damage.

3.After all refrigerant has been recovered, disconnect suction and discharge lines from the compressor and remove compressor. Be certain to have both suction and discharge process tubes open to atmosphere.

4.Carefully pour a small amount of oil from the suction

stub of the defective compressor into a clean container.

5.Using an acid test kit (one shot or conventional kit), test the oil for acid content according to the instructions with the kit.

6.If any evidence of a burnout is found, no matter how slight, the system will need to be cleaned up following proper procedures.

7.Install the replacement compressor.

WARNING

EXPLOSION HAZARD

The use of nitrogen requires a pressure regulator. Follow all safety procedures and wear protective safety clothing etc.

Failure to follow proper safety procedures result in serious injury or death.

8.Pressurize with a combination of R410-A and nitrogen and leak test all connections with an electronic or Halide leak detector. Recover refrigerant and repair any leaks found.

Repeat Step 8 to insure no more leaks are present.

9.Evacuate the system with a good vacuum pump capable of a fi nal vacuum of 200 microns or less. The system should be evacuated through both liquid line and suction line gauge ports. While the unit is being evacuated, seal all openings on the defective compressor. Compressor manufacturers will void warranties on units received not properly sealed. Do not distort the manufacturers tube connections.

CAUTION

FREEZE HAZARD

Proper safety procedures must be followed, and proper protective clothing must be worn when working with liquid refrigerant.

Failure to follow these procedures could result in minor to moderate injury.

10.Recharge the system with the correct amount of refrigerant. The proper refrigerant charge will be found on the unit rating plate. The use of an accurate measuring device, such as a charging cylinder, electronic scales or similar device is necessary.

25

Image 26
Contents Volt XQ05M10*, XQ06M10*, XQ08M10*, XQ10M10 Volt EQ08M11Table Of Contents Important Safety Information Your safety and the safety of others are very importantRefrigeration System Hazards Introduction Property Damage Hazards5th Digit Model Series / Year Introduced Unit Identification6th Digit Voltage 00001Performance Data Fire Hazard Electrical DataElectric Shock Hazard Electrical Shock Hazard How to operate the Friedrich room air conditioner XQ models How to use the remote control XQ models Electronic Control Sequence of Operation Electrical Components Functional Component DefinitionsMechanical Components Hermetic ComponentsError Code Listings Components TestingTesting the Electronic Control Boards for XQ Models Activating Test ModeThermostat Adjustment EQ08 System Control Switch TestEQ08 System Control Switch Test TestCapacitor Connections CapacitorsCapacitor Check with Capacitor Analyzer FAN MotorDrain PAN Valve Testing the Heating Element Electric Shock HazardHeating Element Refrigeration Sequence of Operation 410A Sealed System Repair Considerations Refrigeration system under high pressureEquipment Must be Capable 410A Sealed Refrigeration System RepairsEquipment Required Risk of Electric ShockFreeze Hazard Method Of Charging / RepairsBurn Hazard Undercharged Refrigerant Systems Overcharged Refrigerant SystemsRestricted Refrigerant System Compressor Checks Single Phase Resistance Test Ground TestHigh Temperatures Compressor ReplacementRecommended procedure for compressor replacement Explosion HazardRotary Compressor Special Troubleshooting and Service Routine Maintenance Clearances Sleeve / DrainFront Cover Room AIR Conditioner Unit Performance Test Data Sheet Date Model SerialGeneral Troubleshooting Tips Unit does not operateDo not try to operate your air conditioner Cooling only Room AIR Conditioners Troubleshooting Tips Replace fuse, reset breaker. If repeats, check Fused separately Allowing discharge air to short Heat / Cool only Room AIR Conditioners Troubleshooting Tips Electronic Control Cool only Models Last character may vary Aham PUB. NO. RAC-1 DAY Cooling Load Estimate FormHeat Gain from Quantity Factors Following is an example using the heat load form Heat Load FormWindows & Doors Area, sq. ft Infiltration Windows & Doors AVGRoom AIR Conditioners Limited Warranty Technical Support Contact Information Page Friedrich AIR Conditioning CO

XQ08M10, XQ10M10, XQ05M10, XQ06M10, EQ08M11 specifications

Friedrich offers a range of innovative air conditioning units designed to provide superior comfort and energy efficiency. Among its lineup, the XQ06M10, EQ08M11, XQ05M10, XQ08M10, and XQ10M10 models stand out due to their advanced technologies and user-friendly features.

The XQ series, with models like XQ06M10 and XQ05M10, is renowned for its sleek design and exceptional performance in cooling and heating environments. These models utilize a highly efficient compressor system that reduces energy consumption while maintaining optimal temperature control. The XQ06M10, for example, is designed for medium-sized rooms, featuring a cooling capacity that caters well to residential and small office settings.

On the other hand, the EQ08M11 model is known for its enhanced energy efficiency compared to traditional units, thanks to its inverter technology. This feature allows the compressor to adjust its speed according to the cooling demand, resulting in lower energy costs and a quieter operation. The EQ08M11 is also equipped with a multi-stage filtration system, improving indoor air quality by capturing dust, allergens, and pollutants.

The XQ08M10 and XQ10M10 cater to larger spaces, with their respective higher cooling capacities making them suitable for bigger living areas or small commercial settings. Both models boast an easy-to-use digital control panel, which requires minimal effort to adjust settings. Additionally, they include a programmable timer feature, allowing users to automate operation according to their daily schedules, further enhancing energy savings.

All these models showcase Friedrich’s commitment to durability and reliability, built with high-grade materials designed to withstand varying temperatures and humidity levels. The XQ series is compact, facilitating easy installation without compromising performance.

In summary, the Friedrich XQ06M10, EQ08M11, XQ05M10, XQ08M10, and XQ10M10 models combine cutting-edge technology with practicality, ensuring an efficient and enjoyable indoor climate. With features aimed at energy efficiency, ease of use, and effective air filtration, these units represent a smart investment for anyone looking to enhance their living or working environment.