Lincoln Electric 250 GXT manual Auxiliary Power While Welding, Simultaneous Welding and Power

Page 15

A-8

INSTALLATION

A-8

 

 

 

AUXILIARY POWER WHILE WELDING

Simultaneous welding and power loads are permitted by following Table I. The permissible currents shown assume that current is being drawn from either the 120V or 240V supply (not both at the same time). Also, the “Output Control” is set at “10” for maximum auxiliary power.

TAbLE I

SIMULTANEOUS WELDING AND POWER

Output Selector

Permissible Power

Permissible Auxiliary

 

 

Setting

Watts (Unity Power

Current in Amperes

 

 

Factor)

@ 120V *-or- @ 240V

 

 

 

 

 

Max. Stick or Wire

 

 

 

 

Feed Setting

None

0

0

 

 

 

 

 

 

 

180

Stick Setting

5100

42

21

 

 

 

 

 

 

 

130

Stick Setting

7200

60**

30

 

 

 

 

 

 

 

80

Stick Setting

8750

72**

36

 

No Welding

10,000

84**

42

 

 

 

 

 

 

 

*Each duplex receptacle is limited to 20 amps.

**Not to exceed 50A per 120VAC branch circuit when

splitting the 240 VAC output.

STANDbY POWER CONNECTIONS

The Ranger® 250 GXT is suitable for temporary, standby, or emergency power using the engine manu- facturer’s recommended maintenance schedule.

The Ranger® 250 GXT can be permanently installed as a standby power unit for 240V-3 wire, single phase 42 ampere service.

WARNING

(Connections must be made by a licensed electri- cian who can determine how the 120/240V power can be adapted to the particular installation and comply with all applicable electrical codes.) The following information can be used as a guide by the electrician for most applications (refer also to the connection diagram shown in Figure 1.)

------------------------------------------------------------------------

1.Install a double pole, double throw switch between the power company meter and the premises disconnect.

Switch rating must be the same or greater than the customer’s premises disconnect and service overcurrent protection.

2.Take necessary steps to assure load is limited to the capacity of the Ranger® 250 GXT by installing

a50 amp 240V double pole circuit breaker. Maximum rated load for the 240V auxiliary is 42 amperes. Loading above 42 amperes will reduce output voltage below the allowable -10% of rated voltage which may damage appliances or other motor-driven equipment.

3.Install a 50 amp 120/240V plug (NEMA type 14-50) to the Double Pole Circuit Breaker using No. 8,

4 conductor cable of the desired length. (The

50 amp 120/240V plug is available in the optional plug kit.)

4.Plug this cable into the 50 amp 120/240V receptacle on the Ranger® 250 GXT case front.

RANGER® 250 GXT

Image 15 Contents
Ranger 250 GXT Safety Depends on YouCalifornia Proposition 65 Warnings SafetyElectric Shock can kill Iii Welding and Cutting Sparks can Cause fire or explosionPrécautions DE Sûreté IvSAFETYThank You TAbLE of Contents Installation Towing Safety PrecautionsMachine Grounding Spark ArresterFuel PRE-OPERATION ServiceGasoline Vehicle MountingHigh Altitude Operation Additional Safety PrecautionAngle of Operation LiftingLocation / Ventilation Connection of Lincoln Electric Wire FeedersAdditional Safety Precautions InstructionsWelder Operation Auxiliary PowerDevices Without Addi Tional Resistive Type Loads Auxiliary Power While Welding Simultaneous Welding and PowerSTANDbY Power Connections Connection of Ranger 250 GXT to Premises Wiring Welder Controls Function and Operation Engine SwitchOperation GENERAL DESCRIPTIONRanger 250 GXT Approximate Fuel Consumption Polarity SwitchPIN Connector Local / Remote Control SwitchSTARTING/SHUTDOWN Instructions Starting the EngineStopping the Engine TIG Constant Current Welding Wire Feed Welding Processes Constant VoltageWelding Process Stick Constant Current WeldingIdle When not To Start Process Used Mode Welding Summary of Welding Processes Control ElectrodeCAbLE Accessories K1745-1 Welding GAS Cylinder LPG Tank HolderK857 25 ft.7.5m or K857-1100 ft.30.4m TIG WIRE FEEDRECOMMENDED EQUIPMENT StickEngine OIL Change MaintenanceSafety Precautions Routine MaintenanceOIL Filter Change AIR Cleaner and Other MaintenanceHardware Engine AdjustmentsEngine Maintenance Parts Slip RingsTROUbLESHOOTING Cause Recommended Course of Action SymptomsTROUbLESHOOTING Diagrams Diagrams Diagrams GXT DimensionPrint RangerPrecaucion Warnung