Lincoln Electric 10,000 PLUS, 11395 Auxiliary Power While Welding, Simultaneous Welding and Power

Page 15

A-8

INSTALLATION

A-8

 

 

 

AUXILIARY POWER WHILE WELDING

Simultaneous welding and power loads are permitted by following Table I. The permissible currents shown assume that current is being drawn from either the 120V or 240V supply (not both at the same time). Also, the “Output Control” is set at “10” for maximum auxiliary power.

TABLE I

SIMULTANEOUS WELDING AND POWER

Output Selector

Permissible Power

Permissible Auxiliary

 

Setting

Watts (Unity Power

Current in Amperes

 

Factor)

@ 120V *-or- @ 240V

 

 

 

 

 

Max. Stick or Wire

 

 

 

 

Feed Setting

None

0

0

 

 

 

 

 

 

145 Stick Setting

3450

32

16

 

 

 

 

 

 

90 Stick Setting

6000

50**

25

 

 

 

 

 

 

NO WELDING

9000

76**

38

 

 

 

 

 

 

*Each duplex receptacle is limited to 20 amps.

**Not to exceed 40A per 120VAC branch circuit when

splitting the 240 VAC output.

STANDBY POWER CONNECTIONS

The RANGER 10,000 PLUS AND RANGER 10,000 are suitable for temporary, standby, or emergency power using the engine manufacturer’s recommended maintenance schedule.

The RANGER 10,000 PLUS AND RANGER 10,000 can be permanently installed as a standby power unit for 240V-3 wire, single phase 38 ampere service.

WARNING

(Connections must be made by a licensed electri- cian who can determine how the 120/240V power can be adapted to the particular installation and comply with all applicable electrical codes.) The following information can be used as a guide by the electrician for most applications (refer also to the connection diagram shown in Figure 1.)

-------------------------------------------------------------------------

1.Install a double pole, double throw switch between the power company meter and the premises dis- connect.

Switch rating must be the same or greater than the customer’s premises disconnect and service over- current protection.

2.Take necessary steps to assure load is limited to the capacity of the RANGER 10,000 PLUS AND RANGER 10,000 by installing a 38 amp 240V dou- ble pole circuit breaker. Maximum rated load for the 240V auxiliary is 38 amperes. Loading above 38 amperes will reduce output voltage below the allow- able -10% of rated voltage which may damage appliances or other motor-driven equipment.

3.Install a 50 amp 120/240V plug (NEMA type 14- 50)to the Double Pole Circuit Breaker using No. 8, 4 conductor cable of the desired length. (The 50 amp 120/240V plug is available in the optional plug kit.)

4.Plug this cable into the 50 amp 120/240V recepta- cle on the RANGER 10,000 PLUS OR RANGER 10,000 case front.

RANGER 10,000 PLUS AND RANGER 10,000

Image 15
Contents Lincoln Electric Ranger 10,000 PlusCalifornia Proposition 65 Warnings SafetyElectric Shock can kill Iii Welding Sparks can cause fire or explosionSûreté Pour Soudage a L’Arc Précautions DE SûretéThank You Table of Contents Height Width Depth Weight InstallationTowing Safety PrecautionsMachine Grounding Spark ArresterPRE-OPERATION Service Battery ConnectionsGasoline Angle of Operation Welding Output CablesTotal Combined Length of Electrode and Work Cables High Altitude OperationInstructions Motor Starting Auxiliary Power120/240 Volt Dual Voltage Receptacle Duplex ReceptaclesNone Type Common Electrical Devices Possible ConcernsAuxiliary Power While Welding Simultaneous Welding and PowerStandby Power Connections Power Welder Controls Function and Operation Engine SwitchOperation General DescriptionKohler Subaru Robin Honda Polarity SwitchRange Switch Control DialStopping the Engine STARTING/SHUTDOWN InstructionsBREAK-IN Period Starting the EngineTIG Constant Current Welding Diameter Wire Speed ApproximateWelding Process Stick Constant Current WeldingStick Auto K1745-1 Welding GAS Cylinder LPG Tank Holder AccessoriesTIG Welding Wire FeedRecommended Equipment StickEngine OIL Refill Capacities MaintenanceSafety Precautions Engine OIL ChangeOIL Filter Change AIR Cleaner and Other MaintenanceSlip Rings Engine AdjustmentsBattery Overspeed is HazardousHOW to USE Troubleshooting Guide TroubleshootingTroubleshooting Troubleshooting Diagrams Ranger 10,000 Plus and Ranger10,000 Enhanced Diagram F-2 Plus RangerRanger 10,000 Ranger 10,000 PlusRanger 10,000 Plus and Ranger 10,000 Precaucion Warnung