Troubleshooting Guide

COMPLAINT

CAUSE

REMEDY

 

 

 

Compressor cycles on

Voltage

Check the voltage. See the limits on the

overload.

 

preceding page. If voltage is not within these limits,

 

 

call an electrician.

 

 

 

 

Overload

Check overload, if externally mounted.

 

 

Replace if open. (If the compressor temperature

 

 

is high, remove the overload, cool, and retest.)

 

 

 

Compressor cycles on

Fan motor

If not running, determine the cause. Replace if

overload.

 

required.

 

 

 

 

Condenser air flow

Remove the cabinet, inspect the interior surface

 

restriction

of the condenser. If restricted, clean carefully

 

 

with a vacuum cleaner (do not damage fins) or

 

 

brush. Clean the interior base before

 

 

re-assembling.

 

 

 

 

Condenser fins

If the condenser fins are closed over a large

 

(damaged)

area on the coil surface, head pressures will

 

 

increase, causing the compressor to cycle.

 

 

Straighten the fins or replace the coil.

 

 

 

 

Capacitor

Test the capacitor.

 

 

 

 

Wiring

Check the terminals. If loose, repair or replace.

 

 

 

 

Refrigeration system

Check the system for a restriction.

 

 

 

Insufficient cooling

Air filter

If restricted, clean or replace.

 

 

 

 

Unit undersized

Determine if the unit is properly sized for the

 

 

area to be cooled.

 

 

 

Excessive noise

Blower or fan

Check the set screw, or clamp. If loose or miss-

 

 

ing, correct. If the blower or fan is hitting scroll

 

 

or barrier, rearrange the air handling parts.

 

 

 

 

Copper tubing

Remove the cabinet and carefully rearrange the

 

 

tubing not to contact the cabinet,

 

 

compressor, shroud, and barrier.

 

 

 

27Room Air Conditioner

Image 27
Contents Room Air Conditioner Service and Parts Manual Table of Contents Safety Precautions Plug in the power plug properly Do not clean the air conditioner with water Outside Dimensions Symbols Used in this ManualProduct Specifications Location and Function of Controls OperationAuto Swing Control BOX Mechanical PartsFront Grille CabinetAir Handling Parts AIR Guide and BlowerFAN and Shroud Electrical Parts MotorOverload Protector Refrigerating Cycle Model Touch & Remote Control Type ModelEvaporator Pulling Vacuum Circuit Diagram Schematic DiagramElectronic Control Device Components LocationFor Main P.W.B ASM Piping System Troubleshooting GuideUnit runs but poor cooling Troubleshooting GuideFails to Start Possible Trouble Electric Parts Troubleshooting GuideCompressor does not operate Romote controller does not operate Room AIR Conditioner Voltage Limits Troubleshooting Guide Troubleshooting Guide Exploded Vie w ReplacementParts list Use Factory Certified Parts