Friedrich CP05N10A manual Compressor, Capacitor, Thermistor, Control Board

Page 8

2.3.2 COMPRESSOR

1.Remove the front grille and cabinet. (Refer to Section 2.1)

2.Discharge the refrigerant by using a refrigerant recovery system.

3.Remove the overload protector. (Refer to Section 2.3.1)

4.After discharging the unit completely, unbrace the suction and discharge pipes at the compressor connections.

5.Remove 3 nuts which fasten the compressor.

6.Remove the compressor.

7.Re-install by referring to the removal procedure above. (See Figure 14)

2.3.3 CAPACITOR

1.Remove the cabinet. (Refer to Section 2.1.2)

2.Remove the control panel. (Refer to Section 2.1.3)

3.Discharge the capacitor by placing a 20 KΩ resistor across the capacitor terminals.

4.Remove the screw which fastens the capacitor clamp.

5.Remove all the leads of capacitor terminals.

6.Re-install the components by referring to the removal procedure above. (See Figure 15)

Figure 14

Figure 15

2.3.4 THERMISTOR

1.Remove the cabinet. (Refer to Section 2.1.2)

2.Remove the control panel. (Refer to Section 2.1.3)

3.Disconnect the thermistor terminals from main P.W.B assembly.

4.Remove the thermistor.

5.Re-install the components by referring to the removal procedure above. (See Figure 16)

2.3.5 CONTROL BOARD

1.Remove the cabinet. (Refer to Section 2.1.2)

2.Remove the control panel. (Refer to Section 2.1.3)

3.Pull the control board forward and pull out it.

4.Remove 2 lead wire terminals.

5.Re-install the components by referring to the removal procedure above. (See Figure 17)

Figure 16

Figure 17

—7—

Image 8
Contents Room Air Conditioner Service and Parts Manual Contents Preface Locations of Controls Disassembly Instructions ORIFICE, Turbo FAN and FAN AIR Handling PartsAIR Guide Upper Overload Protector Electrical PartsAIR Guide Compressor CapacitorThermistor Control BoardCondenser Power CordRefrigerant Cycle Evaporator Capillary Tube0A-Pulling Vacuum Electrical Data USE of Extension CordsPiping System Condenser CoilsTroubleshooting Guide Unit is running but cooling is ineffectiveFails to Start Room AIR Conditioner Voltage Limits 203/$,17 $86 50 Complaint Cause Remedy Circuit Diagram 3/29 W0CZZ Use Factory Certified Parts