C. Indoor-Air (Conditioned Supply Air) System
The VEB/VHB series unit may be applied in either a free return air configuration or a ducted return air configuration. The supply air path is intended to be ducted. The design and construction of the
The combined pressure losses of the return and supply air paths must not exceed the external static capabilities of the system at the design airflow (See Table 2).
If the unit is installed in a closet behind a door and the return air louver or grille is directly opposite the unit RA opening, 2- in. clearance is required between the front of the unit and the back side of the louver or grille. If the louver or grille is located elsewhere on the door so it is not directly in front of the RA opening, a minimum of
Indoor Fan Performance
Table 2
| Indoor Blower Air Flow, SCFM (ARI RATED as shown) |
| RA Grille Minimum Net | |||||
Model | ESP | 0.1 | 0.2 | 0.3 | 0.4 |
| 0.5 | Free Open Area (Sq. In.) |
|
|
|
|
|
|
|
|
|
VE/HB18 | Indoor | 850 | 750 | 640 | 550 |
| 450 | 250 |
VE/HB24 | Indoor | 980 | 890 | 800 | 720 |
| 650 | 300 |
VE/HB30 | Indoor | 1120 | 1070 | 1000 | 940 |
| 830 | 375 |
VE/HB36 | Indoor | 1220 | 1120 | 1050 | 990 |
| 860 | 400 |
VE/HB42 | Indoor | 1570 | 1510 | 1470 | 1400 |
| 1350 | 525 |
VE/HB49 | Indoor | 1670 | 1610 | 1570 | 1500 |
| 1450 | 525 |
VE/HB60 | Indoor | 1980 | 1920 | 1860 | 1800 |
| 1700 | 675 |
Note: Italic indicates performance outside the required operating window of +/- 10% of rated SCFM. All values are wet coil with filter installed.
Figure 10
Return Air Options
Front Free | Front Ducted | Side Ducted |
Return | Return | Return |
NOTE: Ducted return air configurations require field fabrication of a
11