Friedrich 2007 service manual Heat / Cool Room AIR Conditioners Troubleshooting Tips

Page 21

HEAT / COOL ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS

Problem

Possible Cause

Action

 

Heat anticipator (resistor) shorted (on applicable

Disconnect power to unit. Remove resistor from

 

t-stat bulb block. Plus in unit & allow to operate.

 

models)

 

Feel resistor for heat. If not heat, replace resistor

Room temperature

 

 

 

uneven

Wide differential - partial loss of t-stat bulb charge

Replace t-stat & check

(Heating cycle)

 

 

 

 

 

 

 

Refer to appropriate wiring diagram. Resistor is

 

Incorrect wiring

energized during "ON" cycle of compressor or

 

 

fan.

Problem

Possible Cause

Action

 

Incorrect wiring

Refer to appropriate wiring diagram

 

Defrost control timer motor not advancing

Check for voltage at "TM" & "TM1" on timer. If no

 

(applicable models)

voltage, replace control

 

Defrost control out of calibration (applicable

If outside coil temperature is 25F or below, &

 

preselected time limit has elapsed, replace

 

models)

Unit will not defrost

defrost control

 

 

 

If contacts remain closed between terminals "2"

 

Defrost control contacts stuck

& "3" of the defrost control after preselected time

 

 

interval has passed, replace control

 

Defrost control bulb removed from or not making

Reinstall & be assured that good bulb to coil

 

good coil contact

contact is made

Problem

Possible Cause

Action

 

Exhaust or fresh air door open

Check if operating properly. Instruct customer on

 

proper use of control

 

 

 

Dirty filter

Clean as recommended in Owner's Manual

 

 

Check heat rise across coil. If unit operates

 

Unit undersized

efficiently, check if insulation can be added

 

to attic or walls. If insulation is adequate,

 

 

Does not heat

 

recommend additional unit or larger one

 

 

adequately

 

T-stat should close at 38°F. Check continuity of

 

Outdoor t-stat open (applicable models)

control. If temperature is below 38°F, replace

 

 

control

 

Heater hi-limit control cycling on & off

Check for adequate fan air across heater. Check

 

control for open at 160°F & close at 150°F

 

 

 

Shorted supplementary heater

Ohmmeter check, approx. 32-35 ohms

 

Incorrect wiring

Check applicable wiring diagram

21

Image 21
Contents 2007 Table of Contents Typical Unit Components IntroductionRoom AIR Conditioners Limited Warranty Routine Maintenance Unit Identification 08 L 1Performancedata Receptacle Electrical DataElectronic Controls Functional Component DefinitionsTesting the Electronic Control Error Code Listings Testing the Electronic Control XQ/WS Boards & QME BoardsSealed Refrigeration System Repairs Refrigeration System Sequence of OperationSpecialprocedureinthecaseofcompressor Motor Burnout Hermetic Component ReplacementRotarycompressorspecialtroubleshooting and Service Equipment RequiredMethod of Charging Refrigerant ChargingOvercharged Refrigerant Systems Undercharged Refrigerant SystemsRestricted Refrigerant System Malfunction of Valve Normal Function of ValveProblem Possible Cause Action Cooling only Room AIR Conditioners Troubleshooting TipsReplace fuse, reset breaker. If repeats, check To equalize before attempting to restart. Instruct Vents on applicable models are in the closed Heat / Cool Room AIR Conditioners Troubleshooting Tips Refrigerant System Diagnosis Heating Troubleshooting Chart CoolingElectrical Troubleshooting Chart Heat Pump Troubleshooting Chart HeatingSystem Cools When Heating is Desired YESModels RM18L30-A, KM18L30-A, KM21L30-A, RM24L30-A, KM24L30-A SS16L30-A/B, SM18L30-A/B, SM21L30-A/B, SM24L30-A/B Model SL28L30-A SL36L30-B EQ08L11-A ES12L33-A, ES16L33-A, EM18L34-A, EM24L35-A EL36L35-A YS09L10-A, YS09L10-B YS13L33-A, YM18L34-A YL24L35-A RAC-Svc-07