ROUTINE MAINTENANCE

NOTE: Units are to be inspected and serviced by qualified service personnel only.

Routine maintenance is required annually or semi-annually, depending upon annual usage.

1.Clean the unit air intake filter at least every 250 to 300 fan hours of operation or when the unit’s indicator light is on if so equipped. Clean the filters with a mild detergent in warm water and allow to dry thoroughly before reinstalling.

2.The indoor coil (evaporator coil), the outdoor coil (condenser coil) and base pan should be inspected periodically (yearly or bi-yearly) and cleaned of all debris (lint, dirt, leaves, paper, etc.). Clean the coils and base pan with a soft brush and compressed air or vacuum. If using a pressure washer, be careful not to bend the aluminium fin pack. Use a sweeping up and down motion in the direction of the vertical aluminum fin pack when pressure cleaning coils. Cover all electrical components to protect them from water or spray. Allow the unit to dry thoroughly before reinstalling it in the sleeve.

NOTE: Do not use a caustic coil cleaning agent on coils or base pan. Use a biodegradable cleaning agent and degreaser.

Inspect the indoor blower housing, evaporator blade, condenser fan blade, and condenser shroud periodically (yearly or bi-yearly) and clean of all debris (lint, dirt, mold, fungus, etc.) Clean the blower housing area and blower wheel with an antibacterial / antifungal cleaner. Use a biodegradable cleaning agent and degreaser on condenser fan and condenser shroud. Use warm or cold water when rinsing these items. Allow all items to dry thoroughly before reinstalling them.

3.Periodically (at least yearly or bi-yearly): inspect all control components, both electrical and mechanical, as well as the power supply. Use proper testing instruments (voltmeter, ohmmeter, ammeter, wattmeter, etc.) to perform electrical tests. Use an air conditioning or refrigeration thermometer to check room, outdoor and coil operating temperatures. Use a sling psychrometer to measure wet bulb temperatures indoors and outdoors.

4.Inspect the surrounding area (inside and outside) to ensure that the units’ clearances have not been compromised or altered.

5.Inspect the sleeve and drain system periodically (at least yearly or bi-yearly) and clean of all obstructions and debris. Clean both areas with an antibacterial and antifungal cleaner. Rinse both items thoroughly with water and ensure that the drain outlets are operating correctly. Check the sealant around the sleeve and reseal areas as needed.

6.Clean the front cover when needed. Use a mild detergent. Wash and rinse with warm water. Allow it to dry thoroughly before reinstalling it in the chassis.

5

Image 5
Contents 2007 Table of Contents Typical Unit Components IntroductionRoom AIR Conditioners Limited Warranty Routine Maintenance Unit Identification 08 L 1Performancedata Receptacle Electrical DataElectronic Controls Functional Component DefinitionsTesting the Electronic Control Error Code Listings Testing the Electronic Control XQ/WS Boards & QME BoardsSealed Refrigeration System Repairs Refrigeration System Sequence of OperationSpecialprocedureinthecaseofcompressor Motor Burnout Hermetic Component ReplacementRotarycompressorspecialtroubleshooting and Service Equipment RequiredMethod of Charging Refrigerant ChargingOvercharged Refrigerant Systems Undercharged Refrigerant SystemsRestricted Refrigerant System Malfunction of Valve Normal Function of ValveProblem Possible Cause Action Cooling only Room AIR Conditioners Troubleshooting TipsReplace fuse, reset breaker. If repeats, check To equalize before attempting to restart. Instruct Vents on applicable models are in the closed Heat / Cool Room AIR Conditioners Troubleshooting Tips Refrigerant System Diagnosis Heating Troubleshooting Chart CoolingElectrical Troubleshooting Chart Heat Pump Troubleshooting Chart HeatingSystem Cools When Heating is Desired YESModels RM18L30-A, KM18L30-A, KM21L30-A, RM24L30-A, KM24L30-A SS16L30-A/B, SM18L30-A/B, SM21L30-A/B, SM24L30-A/B Model SL28L30-A SL36L30-B EQ08L11-A ES12L33-A, ES16L33-A, EM18L34-A, EM24L35-A EL36L35-A YS09L10-A, YS09L10-B YS13L33-A, YM18L34-A YL24L35-A RAC-Svc-07