Green function - transfer threshold. Configure the master outlet to recognize when the master device has gone into sleep or standby mode. Configure the delay between when the Master unit turns off and the peripheral units turn off.
MASTER THRES: 25W
PRESS TO CHNG
CON ONDLY: 4 SEC
PRESS TO CHNG
CON OFFDLY: 4 SEC-
PRESS TO CHNG
Low battery warning. Set the time at which the unit will provide an audible warning that it almost exhausted battery power.
LOWBATTWARN: 2MIN
PRESS TO CHNG
Suggested battery replacement date. The Repdate shows the date on which the battery was last replaced. Update this date if a new battery pack is installed.
REPDATE: 3/04/12
PRESS TO CHNG
DO SELFTEST: NO
PRESS TO CHNG
Runtime calibration. Perform a runtime calibration test to completely discharge the batteries, and recharge them. This allows the unit to accurately predict runtime capacity. This test should be run once a year, after the unit has been in service for at least one year.
RUNTIME CAL: NO
PRESS TO CHNG
LED and audible alarms test. Perform this test to test the LEDs and the audible alarms on the unit.
PRESS TO CHNG
Screen saver. Turn the screen saver on or off.
SCREEN SAVER: ON
PRESS TO CHNG
Reset to factory defaults. Reset all settings to the factory default.
PRESS TO CHNG
8 | A/V J Type Power Conditioner and Battery Backup |