APC 865 W, 120 V, J35B, J25B, 1440 VA manual Troubleshooting, Problem Possible Cause Corrective Action

Page 13

Troubleshooting

Problem

Possible Cause

Corrective Action

 

 

 

The unit will not turn on.

The unit is not connected to utility power.

Ensure that the unit is securely connected to

 

 

a utility power outlet.

 

 

 

 

The internal battery is not connected.

Connect the battery.

The unit does not provide

Ensure that essential equipment is not

Disconnect equipment from the SURGE

power during a utility power

plugged into a SURGE ONLY outlet.

ONLY outlet and re-connect to a Battery

outage.

 

Backup outlet.

 

 

 

The unit is operating on

The plug has partially pulled out of the

Ensure that the plug is fully inserted into

battery power, while connected

wall outlet, the wall outlet is no longer

the wall outlet. Ensure that the wall outlet is

to utility power.

receiving utility power, or the circuit

receiving utility power by checking it with

 

breaker has been tripped.

another device.

 

 

 

 

The unit is performing an automatic self

No action is necessary.

 

test.

 

The utility input voltage is out of range, the frequency is out of range, or the waveform is distorted.

Adjust the transfer voltage and sensitivity range.

The circuit breaker has been tripped.

Disconnect non-essential equipment from the unit. Reset the circuit breaker. Re- connect equipment one item at a time. If the circuit breaker is tripped again, disconnect the device that caused the trip.

The unit does not provide the expected amount of backup time.

Battery Backup outlets may be fully or

Disconnect non-essential equipment from

improperly loaded.

the Battery Backup outlets and connect the

 

equipment to SURGE ONLY outlets.

 

 

The battery was recently discharged due

Charge the battery cartridge for 16 hours.

to a power outage and has not fully

 

recharged.

 

 

 

The battery has reached the end of its

Replace the battery.

useful life.

 

Power is not supplied to some outlets.

Power to the Controlled outlets has intentionally been turned off.

Confirm that the correct peripherals are connected to Controlled outlets. If this feature is not desired, disable the Power- Saving Master and Controlled outlets.

The Controlled outlets are not supplying power, even though the Master device is not in sleep mode.

The Master Outlet threshold may be incorrectly set.

Adjust the threshold when the Master outlet signals the Controlled outlets to shut down.

A/V J Type Power Conditioner and Battery Backup

9

Image 13
Contents Installation and Operation Page General Information Page Overview General InformationRear panel Front panelBattery Backup outlets InstallationPower-Saving Master and Controlled outlets J35 models only Start up menu screens OperationStatus menu Setup menu Audio Alarm OFF Press to Chng Screen saver. Turn the screen saver on or off Problem Possible Cause Corrective Action TroubleshootingReplacement Battery SpecificationsContact APC APV Technical Support Warranty Page Page Descripción general Información generalInventario Seguridad Vista delantera ComponentesVista posterior Conexión de la batería InstalaciónConexión de la alimentación de entrada Conexión de los equiposActivada Menús de la interfaz de pantalla FuncionamientoPantallas de menús de inicio Menú Status estadoTensión de entrada y salida Menú de configuraciónAlarma Sonora Desactivada Pulsar Para Cambiar Salvapantallas. Puede activar o desactivar el salvapantallas Problema Posible causa Acción correctiva Resolución de problemasBatería de recambio EspecificacionesPage Page Présentation Informations généralesInventaire Sécurité Vue de face ComposantsVue arrière Connexion de la batterie InstallationConnexion de l’alimentation d’entrée Connexion de l’équipementActivé Menus de l’interface d’affichage FonctionnementEcrans du menu de démarrage Menu Status EtatTension d’entrée et de sortie Menu Setup ConfigurationAlarme Sonore Désactivée Appuyez SUR Pour Modifier Ecran de veille. Activez ou désactivez l’écran de veille Problème Cause probable Mesure corrective DépannageBatterie de rechange CaractéristiquesAssistance technique d’APC APV Garantie Page Page 990-3712B 07/2011 APC Worldwide Customer Support
Related manuals
Manual 41 pages 54.97 Kb Manual 6 pages 46.95 Kb

J25B, 1440 VA, 865 W, J35B, 120 V specifications

The APC (American Power Conversion) brand is well-known for its high-quality power protection and management solutions. Among their various offerings, the APC 100 V, 230 V, SUA1000RM1U (120 V), and SUA1000RM2U models stand out for their reliability, efficiency, and rich feature set.

The APC SUA1000RM1U and SUA1000RM2U are designed primarily for protecting critical electronic devices and ensuring business continuity. Both models are part of the Smart-UPS series, which is renowned for its performance and innovative technologies. These uninterruptible power supplies (UPS) are particularly suitable for sensitive equipment, network systems, and telecommunication devices.

One main feature of the APC SUA1000RM1U is its line-interactive topology. This technology allows the UPS to automatically adjust voltage fluctuations, ensuring a stable power supply without depleting the battery unnecessarily. The SUA1000RM2U similarly utilizes this topology. Both models have a high-efficiency design that reduces energy consumption, making them environmentally friendly while also lowering operational costs.

In terms of specifications, the SUA1000RM1U provides a total power capacity of 1000 VA/700 W, making it capable of handling a variety of devices. The SUA1000RM2U offers similar capacity, ensuring users have ample backup power for critical applications. The compact 1U design of these models allows for easy integration into existing server racks, maximizing space utilization.

Key characteristics of these units include advanced monitoring capabilities. They are equipped with LCD displays that provide real-time information regarding battery status, load levels, and input/output voltages. This feature allows users to make informed decisions regarding their power management.

Both models come with multiple outlets to facilitate connection to various devices. They also feature network management capabilities, allowing for remote monitoring and management via SNMP, as well as compatibility with various operating systems for seamless integration.

Overall, APC's SUA1000RM1U and SUA1000RM2U models are ideal for businesses and individuals seeking reliable power protection. With their combination of efficiency, advanced technology, and robust design, these UPS units are essential for maintaining operational continuity and protecting valuable equipment against power disturbances.