Bard W38A1, W49A1, W61A1 manual Capacity and Efficiency Ratings, Specifications 3 Ton through 5 Ton

Page 2

Capacity and Efficiency Ratings

MODELS

Cooling Capacity BTUH 1

EER 2

W38A1

35,600

10.00

W49A1

46,500

10.00

W61A1

57,500

10.00

1 Capacity is certified in accordance with ANSI/ARI Standard 390-2003.

2 EER = Energy Efficiency Ratio and is certified in accordance with ANSI/ARI Standard 390-2003.

All ratings based on fresh air intake being 100% closed (no outside air introduction).

Specifications 3 Ton through 5 Ton

MODELS

W38A1-A

W38A1-B

W38A1-C

W49A1-A

W49A1-B

W49A1-C

W61A1-A

W61A1-B

W61A1-C

Electrical Rating--60 Hz

230/208-1

230/208-3

460-3

230/208-1

230/208-3

460-3

230/208-1

230/208-3

460-3

Operating Voltage Range

197-253

197-253

414-506

197-253

197-253

414-506

197-253

197-253

414-506

Compressor--Circuit A

 

 

 

 

 

 

 

 

 

Voltage

230/208

230/208

460

230/208

230/208

460

230/208

230/208

460

Rated Load Amps

14.3/15.6

10.6/11.6

5.3

18.9/20.4

13.1/14.2

6.3

24.2/26.9

16.5/18.4

8.6

Branch Circuit

18.0

13.3

6.0

23.1

16.1

7.1

30.2

20.6

9.7

Selection Current

 

 

 

 

 

 

 

 

 

Lock Rotor Amps

112/112

88/88

44

134/134

91/91

46

158/158

155/155

75

Compressor Type

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Fan Motor & Condenser

 

 

 

 

 

 

 

 

 

Fan Motor--HP-RPM-SPD

1/3-850-2

1/3-850-2

1/3-850-2

1/3-850-2

1/3-850-2

1/3-850-2

1/3-850-2

1/3-850-2

1/3-850-2

Fan Motor--Amps

2.5

2.5

1.3

2.5

2.5

1.3

2.5

2.5

1.3

Fan--DIA/CFM

24" - 2600

24" - 2600

24" - 2600

24" - 2600

24" - 2600

24" - 2600

24" - 2600

24" - 2600

24" - 2600

Blower Motor & Evap.

 

 

 

 

 

 

 

 

 

Blower Motor--HP-RPM-SPD

1/2 Variable

1/2 Variable

1/2 Variable

1/2 Variable

1/2 Variable

1/2 Variable

3/4 Variable

3/4 Variable

3/4 Variable

Blower Motor--Amps

4.5

4.5

4.5

5.0

5.0

5.0

5.0

5.0

5.0

CFM Cooling & E.S.P.

1100 - .15

1100 - .15

1100 - .15

1300 - .20

1300 - .20

1300 - .20

1450 - .20

1450 - .20

1450 - .20

w/Filter (Rated-Wet Coil)

 

 

 

 

 

 

 

 

 

Filter Sizes (inches) STD.

20x30x1

20x30x1

20x30x1

20x30x1

20x30x1

20x30x1

20x30x1

20x30x1

20x30x1

 

 

 

 

 

 

 

 

 

 

Shipping Weight --LBS.

525

525

525

525

525

525

575

575

575

 

 

 

 

 

 

 

 

 

 

Form No.

S3412-1112

Supersedes

S3412-712

Page

2 of 12

Image 2
Contents Engineered Features WALL-MOUNT Quiet Climate A/C 10.0 EERSpecifications 3 Ton through 5 Ton Capacity and Efficiency RatingsBarometric Fresh Air Damper Standard FeaturesVentilation System Packages Economizer ECONWM-SeriesElectrical Specifications Single Circuit Dual CircuitData Pending WHR = Performance and Application Data ERVF-*5CWVL = Ventilation RateW38A 1100 W49A 1300 W61A 1450 Heater Packages Field InstalledIndoor Blower Performance CFM 0.00 0.50 H20 B00 Models C00 ModelsSensible Cooling Cooling Application Data Outdoor TemperatureTotal Cooling Rated +10 Total Btuh 975 Sensible Btuh 950This page intentionally left blank This page intentionally left blank Ventilation Options Factory Installed Code Field Installed PartAir Conditioning Wall-Mount Model Nomenclature Models W38A1, W49A1, W61A1Form No S3412 November Bard Manufacturing Company, IncBryan, Ohio