Cooling Application Data - Outdoor Temperature 1
Model | D.B./W.B. | Cooling | 75oF | 80oF | 85oF | 90oF | 95oF | 100oF | 105oF | 110oF | 115oF | 120oF | |
| 2 | Capacity |
|
|
|
|
|
|
|
|
|
| |
| 75/ | Total Cooling | 37,700 | 35,900 | 34,200 | 32,600 | 31,000 | 29,600 | 28,200 | 26,900 | 25,700 | 24,400 | |
| 62 | Sensible Cooling | 28,600 | 27,800 | 27,100 | 26,300 | 25,600 | 24,900 | 24,100 | 23,400 | 22,700 | 22,000 | |
W38A1 | 80/ | Total Cooling | 40,200 | 39,100 | 38,000 | 36,800 | 35,600 | 34,500 | 33,300 | 32,100 | 30,900 | 29,600 | |
67 | Sensible Cooling | 27,700 | 27,200 | 26,800 | 26,300 | 25,800 | 25,300 | 24,700 | 24,200 | 23,600 | 23,000 | ||
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 85/ | Total Cooling | 47,900 | 45,700 | 43,700 | 41,600 | 39,600 | 37,800 | 35,900 | 34,200 | 32,500 | 30,800 | |
| 72 | Sensible Cooling | 28,400 | 27,600 | 26,900 | 26,100 | 25,300 | 24,500 | 23,600 | 22,700 | 21,800 | 20,800 | |
| 75/ | Total Cooling | 48,900 | 46,500 | 44,400 | 42,400 | 40,500 | 38,800 | 37,200 | 35,600 | 34,200 | 33,000 | |
| 62 | Sensible Cooling | 36,700 | 35,200 | 33,800 | 32,700 | 31,700 | 31,000 | 30,300 | 29,800 | 29,600 | 29,400 | |
W49A1 | 80/ | Total Cooling | 52,200 | 50,700 | 49,300 | 47,900 | 46,500 | 45,200 | 43,900 | 42,500 | 41,200 | 40,000 | |
67 | Sensible Cooling | 35,600 | 34,500 | 33,500 | 32,700 | 32,000 | 31,500 | 31,100 | 30,800 | 30,800 | 30,800 | ||
| |||||||||||||
| 85/ | Total Cooling | 62,200 | 59,300 | 56,600 | 54,100 | 51,700 | 49,500 | 47,300 | 45,200 | 43,300 | 41,600 | |
| 72 | Sensible Cooling | 36,500 | 35,000 | 33,700 | 32,500 | 31,400 | 30,500 | 29,700 | 28,900 | 28,400 | 27,800 | |
| 75/ | Total Cooling | 58,900 | 56,900 | 54,900 | 53,000 | 50,900 | 49,000 | 47,000 | 45,000 | 43,000 | 41,100 | |
| 62 | Sensible Cooling | 41,400 | 40,600 | 39,800 | 39,000 | 38,100 | 37,200 | 36,100 | 35,000 | 33,800 | 32,700 | |
|
|
|
|
|
|
|
|
|
|
|
|
| |
W61A1 | 80/ | Total Cooling | 62,900 | 62,000 | 61,000 | 59,000 | 57,500 | 56,500 | 55,500 | 53,700 | 51,800 | 49,800 | |
67 | Sensible Cooling | 40,100 | 39,800 | 39,400 | 39,000 | 38,400 | 37,800 | 37,000 | 36,200 | 35,200 | 34,200 | ||
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 85/ | Total Cooling | 74,900 | 72,500 | 70,100 | 67,600 | 65,000 | 62,500 | 59,800 | 57,100 | 54,400 | 51,800 | |
| 72 | Sensible Cooling | 41,100 | 40,400 | 39,600 | 38,800 | 37,700 | 36,600 | 35,300 | 34,000 | 32,400 | 30,900 |
1 Below 65°F (18.3C), unit requires a factory or field installed low ambient control. 2 Return air temperature.
Capacity Multiplier Factors
% of Rated Airflow | Rated | +10 | |
|
|
|
|
Total BTUH | 0.975 | 1.0 | 1.02 |
Sensible BTUH | 0.950 | 1.0 | 1.05 |