Air Conditioning Wall-Mount Model Nomenclature
SERIES
NOMINAL
CAPACITY
38 - 3 Ton
49 - 4 Ton
61 - 5 Ton
W38 A 1
REVISION
TYPE
Air Conditioner
VOLTS & PHASE
A - 230/208/60/1
B - 230/208/60/3
C - 460/60/3
A10 X
KW 1
VENTILATION OPTIONS
(See Table Below)
FILTER OPTIONS
X-
X | X | X | X | X | ||
|
|
|
|
|
| CONTROL MODULES |
|
|
|
|
|
| |
|
|
|
|
|
| (See Chart Below) |
|
|
|
|
| COIL OPTIONS | |
|
|
|
|
| X - Standard | |
| COLOR OPTIONS |
| 1 - Phenolic Coated Evaporator | |||
| X - Beige (Standard) |
| 2 - Phenolic Coated Condenser | |||
| 1 - White |
|
|
| 3 - Phenolic Coated Evaporator | |
| 4 - Buckeye Gray |
| and Condenser | |||
| 5 - Desert Brown |
|
|
|
8 - Dark Bronze | OUTLET OPTIONS | |
A - Aluminum | ||
X - Front (Standard) | ||
S - Stainless Steel | ||
|
1For 0KW and circuit breakers (230/208 Volt) or pull disconnects (460 Volt) applications, insert 0Z in the KW field of the model number.
P-
W -
Ventilation Options
Models |
| W38A1, W49A1, W61A1 |
|
| ||
Description | Factory Installed |
| Field Installed | |||
Code No. |
| Part No. |
|
| ||
|
|
|
|
| ||
Barometric Fresh Air Damper - Standard | X |
|
|
| ||
| B |
|
|
| ||
Motorized Fresh Air Damper |
| M |
|
|
| |
Commercial Ventilator - Spring Return w/Exhaust | V |
|
|
| ||
Commercial Ventilator - Power Return w/Exhaust | P |
|
|
| ||
Economizer - School Versions, Enthalpy | 4 | S |
| 23 | ||
Economizer - Equipment Bldg., Enthalpy 5 | W |
| 2 | |||
Economizer - Equipment Bldg., DB Temp 5 | T |
| ||||
Energy Recovery Ventilator - 230 Volt | 3 | R |
| 1 | ||
Energy Recovery Ventilator - 460 Volt | 3 | R |
| 1 | ||
Door Kit for ERVF (Required) |
| N/A |
| WMDK5- | 3 |
1Intake and exhaust can be independently adjusted.
2Insert color to match unit ("X" = Beige; "4" = Buckeye Gray; etc.)
3WMDK Door Kit must be ordered in addition to ERVF Assembly and ECONWMS & color matched to unit ("X" = Beige; "4" = Buckeye Gray; etc.)
4 Partial Full Flow (75% of Rated Cooling CFM). All ECONWMS versions have 3" deep intake hood. 5 Full Flow (100% of Rated Cooling CFM). ECONWMT5 has 18" deep intake hood.
Air Conditioning Control Modules |
|
|
| W38A1, W49A1, W61A1 |
| ||||||
|
| AVAILABLE CONTROL OPTIONS |
|
|
| Models with Scroll Compressors | |||||
|
|
|
|
|
|
|
| ||||
HPC 1 | LPC 2 | CCM 3 | LAC 4 | ALR 5 |
| SK 6 | ODT 8 | DDC 9 | Factory Installed Code | Field Installed Part | |
STD | STD | STD |
|
|
| STD |
|
| X | N/A |
|
STD | STD | STD |
|
| STD |
|
| E | |||
STD | STD | STD |
| STD |
|
| J | Factory Only | |||
STD | STD | STD |
|
|
| STD |
|
| Field Installed Only | SK111 | 7 |
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
| ||
STD | STD | STD |
|
|
| STD |
|
| Field Installed Only | SK113 | 7 |
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
| ||
STD | STD | STD |
|
|
| STD |
| Field Installed Only | |||
STD | STD | STD |
| STD |
| V | Factory Only | ||||
STD | STD | STD |
|
|
| STD |
| Field Installed Only |
STD = Standard equipment for these specified models.
1 HPC High pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note 3. 2 LPC Low pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note 3.
3CCM Compressor control module has adjustable
4 LAC Low ambient control permits cooling operation down to 0°F.
5 ALR The alarm relay has a set of normally open and normally closed dry contacts to provide the ability to signal a condition of shutdown on either high or low pressure controls.
6 SK PTCR start kit is standard with all
7 Start capacitor and potential relay start kit can be used with all
8 ODT. Outdoor thermostat is adjustable from 0 to 50°F. It is suitable for use as a compressor cutoff thermostat.
9 DDC. Incorporates 4 additional sensors: discharge air temperature, indoor blower airflow, compressor current, and dirty filter. These sensing devices function to input analog data such as temperature, as well as digital data such as air flow, compressor status or filter status.
“V” control module should be ordered in conjunction w/direct digital controller (DDC) model TCS24. Refer to DDC specification sheet S3280 for more information.
Form No. | |
Supersedes | |
Page | 11 of 12 |