Indoor Blower Performance - CFM (0.00" — 0.50" H20) 1
|
| 1 | 2 | 3 | 3 |
Model | Rated | Max | Blower | Cooling | Electric |
| ESP | ESP | Only |
| Heat |
W38A | .15 | .50 | 1100 | 1100 | 1100 |
W49A | .20 | .50 | 1300 | 1300 | 1300 |
W61A | .20 | .50 | 1450 | 1450 | 1450 |
|
|
|
|
|
|
NOTE: | These units are equipped with a variable speed (ECM) indoor motor that automatically adjusts itself to maintain approximately the same rate of |
| indoor airflow in both heating & cooling, dry & wet coil conditions and at both 230/208 or 460 volts. |
1 Maximum ESP (inches WC) shown is with 2" thick disposable filter.
2 Blower only CFM is the total air being circulated during continuous fan mode. 3 CFM output on Cooling or Electric Heat.
Electric Heat Table - Refer to Electrical Specifications for Availability by Unit Model
|
| At 240V (1) |
|
| At 208V (1) |
|
| At 480V (2) |
|
| At 460V (2) |
| ||
Nominal |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
KW | KW | BTUH | KW | BTUH | KW | BTUH | KW | BTUH | ||||||
| Amps | Amps | Amps | Amps | Amps | Amps | ||||||||
|
|
|
|
|
|
|
|
| ||||||
5.0 | 5.0 | 20.8 |
| 17,065 | 3.75 | 18.0 |
| 12,799 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
6.0 | 6.0 |
| 14.4 | 20,478 | 4.50 |
| 12.5 | 15,359 | 6.0 | 7.2 | 20,478 | 5.52 | 6.9 | 18,840 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
8.0 | 8.0 | 33.3 |
| 27,304 | 6.00 | 28.8 |
| 20,478 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
9.0 | 9.0 |
| 21.7 | 30,717 | 6.75 |
| 18.7 | 23,038 | 9.0 | 10.8 | 30,717 | 8.28 | 10.4 | 28,260 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10.0 | 10.0 | 41.7 |
| 34,130 | 7.50 | 36.1 |
| 25,598 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
15.0 | 15.0 | 62.5 | 36.1 | 51,195 | 11.25 | 54.1 | 31.2 | 38,396 | 15.0 | 18.0 | 51,195 | 13.80 | 17.3 | 47,099 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(1)These electric heaters are available in 230/208V units only.
(2)These electric heaters are available in 480V units only.
Heater Packages - Field Installed
• Designed for adding Electric Heat to 0 KW Units |
| • ETL US & Canada Listed |
|
|
| ||
• Circuit Breaker Standard on 230/208V Models |
|
|
|
| |||
|
|
|
|
|
| ||
• Rotary Disconnect Standard on 460V Models |
|
|
|
|
|
| |
Air Conditioner |
|
|
|
|
|
| |
|
|
|
| ||||
Models |
|
|
|
| |||
Heater Model # | KW | Heater Model # |
| KW | Heater Model # | KW | |
|
| ||||||
| 5 |
| 6 | 6 | |||
| 8 |
| |||||
W38A1 |
| 9 | 9 | ||||
10 |
| ||||||
|
| 15 | 15 | ||||
| 15 |
| |||||
|
|
|
|
|
| ||
| 5 |
| 6 | 6 | |||
| 8 |
| |||||
W49A1 |
| 9 | 9 | ||||
10 |
| ||||||
|
| 15 | 15 | ||||
| 15 |
| |||||
|
|
|
|
|
| ||
| 5 |
|
|
|
|
| |
W61A1 | 8 |
| 9 | 9 | |||
10 |
| 15 | 15 | ||||
|
| ||||||
| 15 |
|
|
|
|
|
Form No. | |
Supersedes | |
Page | 7 of 12 |