Baldor MN806 Old Style Non UL Spare Parts Size 0, 1 Size 3, 4, Braking Module Control Transformer

Page 4

Old Style (Non UL) Spare Parts

 

Size 0, 1 and 2

Size 3, 4 and 5

B

B

C

 

 

E

D

A

Mounted inside

E

C

A

D

A Braking Module

B Control Transformer

This module is not available. If the module can not be repaired the brake must be replaced. Sizes 0, 1 and 2 have the SCRs in the module and can be replaced.

C Fuses

Over a 15 year period many brands of transformers have been used., Control transformers are locally available. Baldor may stock a simular transformer. To check, get the VA, Voltage, of the existing transformer. See MN805.

 

 

Power Fuses

 

 

Control Transformer

 

Size

Baldor

Buss

Gould

Baldor

 

Buss

 

Gould

0,1

FU50020

FWP0020

A70P30

FUS0005

 

FNM1/2

 

TRM 1/2

2

FU50030

FWP60

A70P60

FUS0005

 

FNM1/2

 

TRM 1/2

3

FU50045

FWP150

A70P150

FUS0005

 

FNM1/2

 

TRM 1/2

4

FUS0050

FWP350

A70P350

FUS0010

 

FNM1

 

TRM 1

Baldor still uses the control transformer fuses. All of these fuses should be locally available.

There are 2 types of fuses. The large power fuses are in the fuse holder mounted on the panel. There are two brands available, Buss and Gould. The second type of fuse is a single fuse for the control power transformer.

D Braking Contactor

Over a 15 year period several brands of contactors have been used. They are available locally. Baldor may stock a simular contactor. To check, get the part number of the existing device.

E Replacement SCRs/Diode and power cells

Sizes 0-3: The SCR and Diode are in the same package. Size 0, 1 and 2 are mounted in the module. The SCR/Diode in the size 4 are separate.

 

 

SCR/Diode

 

 

Power Cell

Size

460 VAC

 

575 VAC

460 VAC

 

575 VAC

0/1/2

 

SCR0075

 

SCR0080

 

3

 

SCR085

 

SCR0087

BPC3A

 

BPC3B

4

 

SCR0120

 

SCR0123

BPC4A

 

BPC4B

 

SCR055

 

SCR0060

 

 

 

 

 

 

 

1If the SCR/Diode are replaced an SCR kit is also required. B-2

Image 4
Contents Solid State Starter Parts Table of Contents Old Style New StyleReplacement SCRs/Diode and power cells Old Style Non UL Spare Parts Size 0, 1 Size 3, 4Braking Module Control Transformer FusesThermostat SCR/Power Cells Part NumberingModule LCM MOV-All Sizes Line Load TerminalsIII Nema 3R Size Size 0 Size 4, 5, 6 CT1 CT2Sizes Part Number CAT. no Control Type Power Cell Replacement SCR AMP NON UL MAX SizeCT2 Cross Over Chart Control TransformersBypass Contactors Size General Ramp NON UL Purpose UP/DOWN MultipurposeSize General Ramp NON UL Purpose UP/DOWN Multipurpose