Studer Innotec C 1600-12, C 2600-24, C 4000-48 Temperature sensor, Standard setting, Reset value

Page 19

STUDER INNOTEC

COMPACT

Caution: No external voltage should be connected to this Input Control.

4.11 The Temperature sensor

Operating voltage of lead-acid batteries change depends on the temperature. To correct the operating voltages according to the actual temperatures, a temperature sensor can be connected to the COMPACT.

The compensation through the sensor is –3mV/°C/Cell.

Order Number: CT-35

Dimensions: H x B x T / 58 x 51.5 x 22mm

5 Programming

5.1Standard setting

The COMPACT is delivered with the default setting following:

5.1.1Working mode

The working of the charger, the inverter and the transfer are described in chapter 5.3/5.4/5.5.

5.1.2Battery voltage

Low voltage

11.6V / 23.2V / 46.4V

Float Charge

13.5V / 27.0V / 54.0V

End of Charge Voltage

14.4V / 28.8V / 57.6V

Equalization

15.3V / 30.6V / 61.2V

Absorption Time:

2 Hours

5.1.3Auxiliary contact

Active in case of defect or manual turn off with the LED 10/11/12/13

5.2Reset value

When the COMPACT is to be connected to a battery or after an interruption (RESET), it is always programmed with these standard settings.

In order to get to these settings during operation you must press the three Push Buttons 19/20/21 simultaneously for a minimum of 2 seconds.

5.3Battery voltages and absorption time

The voltage levels (low voltage, float charge, end of charge and equalization) and the duration of the absorption charge can be changed.

The display of these voltages and the times in the program mode are in accordance with the diagram shown below:

5.3.1Table of voltage and timing threshold

 

Low voltage

 

Float Charge

Absorption

 

Equalization

 

Absorpt.

 

LED 13

 

LED 12

 

LED 11

 

LED 10

 

Time

 

 

 

 

 

 

 

 

 

 

 

 

 

LED 10->13

LED

12V

24V

48V

12V

24V

48V

12V

24V

48V

12V

24V

48V

12/24/48V

14

12.0

24.0

48.0

13.7

27.4

54.8

16.2

32.4

64.8

16.2

32.4

64.8

4 h

15

11.8

23.6

47.2

13.6

27.2

54.4

15.6

31.2

62.4

15.9

31.8

63.6

3 h

16

11.6

23.2

46.4

13.5

27.0

54.0

15

30

60

15.6

31.2

62.4

2 h

17

11.4

22.8

45.6

13.4

26.8

53.6

14.4

28.8

57.6

15.3

30.6

61.2

1 h

18

11.2

22.4

44.8

13.3

26.6

53.2

14.2

28.4

56.8

15

30

60

0 – 1Min.

The heavy printed values show the standard settings.

User manual

COMPACT V4.0 E

19

Image 19
Contents Compact V4.0 E User and installer ManualIntroduction AssemblySummary General InformationProgramming Maintenance EC Compliance Technical Data Compact V4.0 EGeneral Information Special Precautions Introduction Principle schematicDescription of main functions Battery connections Connection AssemblyPlace of assembly FixingProtection cover for the terminals Connections Connecting Plan / Front sideSolar + Connection the 230Vac-Consumer Device AC Output Cabling/wiringPre-installation settings Connection to batteryConnect the solar modules Solar +/- Only for solar option Connection to Remote controlConnection to Temperature Sensor Temp Connection the 230Vac Input AC InputDisplay and operating control elements OperatingPush buttons Light Emitting DiodesTurning Knobs Overload Battery ConditionInverter Charge detection system „StandbyEqualization charging Battery chargerInput current repartition Power sharing Cycle of chargeCharging current Transfer systemSet the transfer voltage threshold Fast UPS- Mode for the Transfer SwitchDelayed mode of the Transfer System Solar charge controller optionMultifunctional Contact Remote ControlBattery voltages and absorption time Temperature sensorStandard setting Reset valuePrinciple Programming the auxiliary contactSet the voltage and timing Threshold LED11Manual operating of Auxiliary Contact As per the battery capacityDisabling some of the Compact functions ExamplesDiagram of the different modes MaintenanceModel Technical Data