Studer Innotec C 2600-24, C 1600-12 user manual Technical Data, Model

Page 23
C 1600-12

STUDER INNOTEC

COMPACT

8 Technical Data

Technical data

Model

C 2600-24

C 4000-48

Inverter

Nominal battery voltage

12V

 

24V

 

 

48V

Input voltage range

9.5 - 16V

 

19 - 32V

 

 

38 - 64V

Continuous power @ 25°C

1300VA

 

2300VA

 

 

3500VA

Power 30 min. @ 25°C

1600VA

 

2600VA

 

 

4000VA

Maximum power load 5 sec.

 

 

3 x Pnom

 

 

 

Maximum load

 

 

up to short circuit

Maximum asymmetric load

 

 

up to Pcont.

 

 

 

Stand-by adjustment

 

 

1 to 25W

 

 

 

Cos ϕ

 

0.1 - 1

 

 

 

Maximum efficiency

94%

 

 

95%

Consumption OFF/Stand-by/ON

0.5/0.6/6W

 

0.8/0.9/9W

 

 

1.2/1.4/12W

Output voltage

 

 

230Vac (- 10% / 0)

 

 

Output frequency crystal controlled

 

 

50Hz +/- 0.05%

Total harmonic distortion

 

< 2%

 

 

 

Dynamic behaviour on load change 0 to 100%

 

 

0.5 ms

 

 

 

Overload and short circuit protection

Automatic disconnection with 3 time restart attempt

Overheat protection

Acoustic warning before shut-off - with automatic restart

Battery charger (4 STEP) I-U-Uo-Equalize (every 25 cycles)

 

 

 

 

 

Charging current adjustable

0 - 55A

 

0 - 55A

 

 

0 - 50A

Input current balance adjustment (Power Sharing)

 

 

1 - 16A

 

 

 

Maximum input voltage

 

 

265Vac

 

 

 

Minimum input voltage

Adjustable threshold from 150 to 230Vac

Input frequency

 

 

45 - 65Hz

 

 

 

Power Factor Correction (PFC)

 

 

EN 61000-3-2

Optional solar charger (4 stages) I-U-Uo-Equalize (every 25 cycles)

 

 

 

 

 

Maximum PV open circuit voltage (V)

25V

 

45V

 

 

90V

Maximum charge current (A)

30A

 

30A

 

 

20A

Working principle: I-U-Uo-Equalize (every 25 cycles)

 

 

Shunt

 

 

 

Battery control (thresholds and times adjustable by the user)

 

 

 

 

 

Absorption time

 

 

0-4 h

 

 

 

End charge cycle voltage

14.4V

 

28.8V

 

 

57.6V

Floating voltage

13.6V

 

27.2V

 

 

54.4V

Equalization voltage

15.6V

 

31.2V

 

 

62.4V

Deep-discharge protection

10.8V

 

21.6V

 

 

43.2V

Temperature compensation (optional CT-35)

 

 

-3mV / o C / cell

 

 

General data

 

 

 

 

 

 

Multifunction contact - potential free (3 points)

 

 

16A - 250Vac

Max. current on transfer relay

16A/3.7kVA

 

16A/3.7kVA

 

 

16A/3.7kVA

Transfer time

 

 

< 20 ms

 

 

 

Weight

16 kg

 

17.1 kg

 

 

29.4 kg

Dimension h x l x L [mm]

124x215x480

 

 

124x215x670

Protection index IP20

IP23 with top cover CxxxxIP23

Certification ECE-R 10 (E24)

yes

 

yes

 

 

n.a.

EC conformity

EN 61000-6-1, EN 61000-6-3, EN 55014, EN 55022,

EN 61000-3-2, Dir. 89/336/EEC, LVD 73/23/EEC

 

Operating temperature range

 

 

-20 to 55 oC

 

 

 

Ventilation

 

 

from 45 oC

 

 

 

Acoustic level without / with ventilation

 

 

< 10 dB / < 35 dB

Warranty

 

 

2 years

 

 

 

Options

 

 

 

 

 

 

Solar charge controller

C-xxxx-S

 

 

 

 

 

Remote control (112 x 138 x 25mm / 20 m. cable)

RCC-01

 

 

 

 

 

Remote power sharing (20 m. cable)

RPS-01

 

 

 

 

 

IP-23 top cover

C-xxxx-IP23

 

 

 

 

 

AC cable cover

CFC-01

 

 

 

 

 

Battery temperature sensor (58 x 51.5 x 22mm / 3 m.

CT-35

 

 

 

 

 

cable)

 

 

 

 

 

 

Data may change without any notice

 

 

 

 

 

 

User manual

COMPACT V4.0 E

23

Image 23
Contents Compact V4.0 E Studer InnotecIntroduction AssemblySummary General InformationProgramming Maintenance EC Compliance Technical Data Compact V4.0 EGeneral Information Special Precautions Description of main functions Principle schematicIntroduction Battery connections Connection AssemblyPlace of assembly FixingSolar + Connecting Plan / Front sideProtection cover for the terminals Connections Connection the 230Vac-Consumer Device AC Output Cabling/wiringPre-installation settings Connection to batteryConnect the solar modules Solar +/- Only for solar option Connection to Remote controlConnection to Temperature Sensor Temp Connection the 230Vac Input AC InputDisplay and operating control elements OperatingTurning Knobs Light Emitting DiodesPush buttons Overload Battery ConditionInverter Charge detection system „StandbyEqualization charging Battery chargerInput current repartition Power sharing Cycle of chargeCharging current Transfer systemSet the transfer voltage threshold Fast UPS- Mode for the Transfer SwitchDelayed mode of the Transfer System Solar charge controller optionMultifunctional Contact Remote ControlBattery voltages and absorption time Temperature sensorStandard setting Reset valuePrinciple Programming the auxiliary contactSet the voltage and timing Threshold LED11Manual operating of Auxiliary Contact As per the battery capacityDisabling some of the Compact functions ExamplesDiagram of the different modes MaintenanceModel Technical Data