Troubleshooting
Problem |
| Possible Causes |
| Likely Solutions |
Compressor does | 1. | Incorrect power supply. | 1. | Check that circuit matches compressor requirements. |
not start or restart | 2. | No power at outlet. | 2. | Reset circuit breaker, or have outlet serviced by a qualified |
|
|
|
| technician. |
| 3. | Power cord not plugged in | 3. | Check that cord is plugged in securely. |
|
| properly. |
|
|
| 4. | Thermal overload switch | 4. | Turn off Tool. Turn off Compressor and wait for it to cool down. |
|
| tripped. |
| Press reset button. Resume operation. |
| 5. | Building power supply circuit | 5. | Reset circuit or replace fuse. Check for low voltage conditions. |
|
| tripped or blown fuse. |
| It may be necessary to disconnect other electrical appliances |
|
|
|
| from the circuit or move the compressor to its own circuit. |
| 6. | Tank(s) already pressurized. | 6. | No problem. Compressor will start when needed. |
| 7. | Cord wire size is too small or | 7. | Use larger diameter or shorter extension cord or eliminate |
|
| cord is too long to properly |
| extension cord. See Recommended Wire Gauge for Extension |
|
| power compressor. |
| Cords in Safety section. |
| 8. | Compressor needs service. | 8. | Have unit inspected by a qualified technician. |
Compressor builds | 1. | Incorrect power supply. | 1. | Check that circuit matches compressor requirements. |
pressure too slowly | 2. | Crankcase overfilled with oil or | 2. | Drain oil and refill to proper level with recommended oil. |
|
| oil too thick. |
|
|
3.Working environment too cold. 3. Move unit to a warmer location. Check that recommended oil is in crankcase.
| 4. | Safety valve needs service. | 4. | Listen for air leaking from valve. If leaking replace with |
|
|
|
| identical valve with same rating. |
| 5. | Loose fittings. | 5. | Reduce air pressure, then check all fittings with a soap solution |
|
|
|
| for air leaks and tighten as needed. Do not overtighten. |
Compressor not | 1. | Filters need cleaning/replacing. | 1. | Check inlet and outlet filters. Clean and/or replace as needed. |
building enough air | 2. | Crankcase oil too thick. | 2. | Drain oil and refill to proper level with recommended oil. |
pressure | 3. | Check Valve needs service. | 3. | Have technician clean or replace, as needed. |
| ||||
| 4. | Compressor not large enough | 4. | Check if accessory SCFM is met by Compressor. If |
|
| for job. |
| Compressor cannot supply enough air flow (SCFM), you need |
|
|
|
| a larger Compressor. |
| 5. | Loose fittings. | 5. | Reduce air pressure, then check all fittings with a soap solution |
|
|
|
| for air leaks and tighten as needed. Do not overtighten. |
| 6. | Hose or hose connections not | 6. | Replace with larger hose and/or hose connections. |
|
| adequate. |
|
|
| 7. | High altitude reducing air | 7. | You may need a larger compressor if you are situated in a high |
|
| output. |
| altitude location. |
High Oil | 1. | Crankcase oil too thin. | 1. | Drain oil and refill to proper level with recommended oil. |
Consumption | 2. | Unit not on level surface. | 2. | Reposition unit on a level surface. |
| 3. | Crankcase vent clogged. | 3. | Clean Crankcase vent. |
Follow all safety precautions whenever diagnosing or servicing the compressor. Disconnect power supply before service.
SKU 67708 | For technical questions, please call | Page 15 |