Exide S47-0079 manual Programming, Parameter Message Range

Page 13

2.1.12 Programming

To enter programming mode, press and hold the EDIT button and while holding it, press the INFO button. The display shows a message describing the current parameter followed by the parameter‘s value. While in programming mode, the buttons have the following functions:

STOP: Exit programming mode and save all parameters

=: Shift position of parameter being edited

EDIT: Change value of current position of parameter being edited

INFO: Change parameter to edit

Some of the parameters may be locked out in the programming mode. If a parameter is locked, the parameter is displayed along with the current value and a lock is displayed on the left side of the display. The parameter can not be changed. Refer to jumper settings section for information on locking out parameters. The following parameters are available for editing:

PARAMETER

MESSAGE

RANGE

BS

BATTERY AH SIZE

100-2200AH

VR

BATTERY VOLTAGE

12-999V

SR

SHUNT RATING

0-600A

AS

AUTO START MODE

0-2

 

 

 

CR

CABLE RESISTANCE

0-25mΩ

SA

START A/100AH

5.0-50.0 A/100AH

TP

80% TRIP POINT

2.35-2.45 V/C

FA

FINISH A/100AH

0.1-10.0 A/100AH

FV

FINISH VOLTAGE

2.50-3.00 V/C

CV

CUTOFF VOLTAGE

2.50-3.00 V/C

ST

80% TIMEOUT

0:00-24:00

 

 

 

FT

CHARGE TIMEOUT

0:00-24:00

 

 

 

MP

MAX POWER RATING

0.1-25.0 kW

CF

CHARGE FACTOR

0-150%

 

 

 

DS

DELAY START TIME

0:00-24:00

CT

COOL DOWN TIME

0:00-24:00

CU

DVDT PERIODS

0-15

 

 

 

EM

EQUALIZE MODE

0-1

 

 

 

EI

EQUALIZE A/100AH

0.1-10.0 A/100AH

ET

EQUALIZE TIME

0:00-24:00

EC

EQUALIZE CYCLES

0-30

N1

F1 FAULT DISABLE

0-1

N3

F3 FAULT DISABLE

0-1

N4

F4 FAULT DISABLE

0-1

N6

F6 FAULT DISABLE

0-1

N7

F7 FAULT DISABLE

0-1

AR

REFRESH TIME

00:00-72:00

NOTES

A setting of 0 enables current sensor operation

0:Manual Start

1:Auto-Start

2:Auto Start (restart on AC power)

Exceeding this voltage terminates the charge immediately. Exceeding this time results in an F1 if F1 is enabled and ends normally if F1 is disabled. (see N1 parameter)

Exceeding this time results in an F7 if F7 is enabled and ends normally if F7 is disabled. (see N7 parameter)

*DO NOT EXCEED RATING OF CHARGER

Maximum return based on battery AH size. Setting this to 0 disables the charge factor.

Each period is 5 minutes. Setting this to 0 causes the charge to terminate when the trip point is reached. (opportunity charge)

0:Equalize disabled

1:Normal equalize

Setting this to 0 disables automatic equalize.

0:Enabled, 1: Disabled

0:Enabled, 1: Disabled

0:Enabled, 1: Disabled

0:Enabled, 1: Disabled

0:Enabled, 1: Disabled

Setting this to 0:00 disables automatic refresh.

LOCK

13

Image 13
Contents GNB Section Description IndexImportant Save These Instructions Line Voltage Adjustments InstallationReceiving LocationPower Transformer Setting Connecting AC Service to the Charger AC Service RequirementsCharging Rate Adjustment Battery Connector and Charging CableGrounding the Charger Operation 1 046-0371 Control Feature SummaryNormal Daily Charge OperationEqualize Charge Delayed StartAuto- Refresh Charge Charge Time Viewing Charge InformationDisplay Description Charge IndicationsJumper Settings 10 F3 Low Battery OverrideParameter Message Range ProgrammingPossible Cause Optional FeaturesGeneral Maintenance Excessive water loss in batteryAC fuse blows DC fuse blowsOrdering Information Replaceable PartsRecommended Spares Part Number Description Condensers Spare Parts ListThree Phase Charger Schematic # Single Phase Charger Schematic # 02-490